SSX / MF

A1.2 · Upper-floor life safety Home2 Suites · Bradenton

A1.2 · UPPER-FLOOR LIFE SAFETY

SYMBOL TAKEOFF / COUNTS

22 numbered symbols · select a type to isolate its marks.

PLAN NOTES / ROOMS / ASSEMBLIES

01 · Interior wood-stud wall

Wall legend identifies an interior wood-stud wall. Match each wall to the A0.2 assembly for stud size, board layers, insulation and finish.

02 · Fire-rated wood-stud wall

Separate wall-legend symbol identifies fire-rated interior wood-stud construction, with rating per wall types. Link the selected assembly and opening/penetration details to corridor and enclosure locations.

03 · Standard king studios · 15

201, 203, 209, 211, 213, 215, 217, 219, 221; 204, 206, 208, 210, 212, 214.

04 · Connecting king studio · 1

205. Coordinate connecting-door assembly and hardware with the enlarged room plan and door schedule.

05 · King one-bedroom · 1

202, adjacent to the west stair.

06 · Accessible king one-bedroom · 1

207. Green travel path connects this room to the west exit stair. Coordinate its room layout and door approach with A0.3.

07 · Queen-queen rooms · 4

216, 218, 220 and 222, along the southeast wing.

08 · Connecting queen-queen · 1

224. Coordinate connecting-door assembly and hardware with the enlarged room plan and door schedule.

09 · Accessible queen-queen · 1

226 at the southeast end. Coordinate the accessible room route and door clearances with A0.3.

10 · Exit stairs · 2

Stair 2 / 002 is shown at the west end; Stair 1 / 001 at the east end. Corridor 228 connects the two stair approaches.

11 · Exit travel paths

Green lines show travel toward the stairs. The red longest-path route starts in King Studio 213 and proceeds east along Corridor 228 to Stair 1.

12 · Emergency lighting / exit signs

Life-safety legend refers emergency lighting and exit signs to electrical drawings. Match upper-floor locations and sign direction to the corresponding electrical floor sheet.

13 · Fire extinguisher / cabinet

Life-safety legend includes extinguisher/cabinet. Coordinate selected cabinet, mounting and wall recess with the wall assembly and accessible corridor clear width.

14 · Elevator lobby / storage

Elevator Lobby 200 and Storage 223 are at the northeast core. Coordinate elevator-lobby openings and storage door with the door schedule and enclosure details.

SOURCE

A1.2 · 04.30.2025 · PDF page 10
36″ × 24″ sheet

All source text

Select an item to highlight its source.

A1.2 Typical Upper Level Life Safety with wall legend, guestrooms, stairs and travel paths
A1.2 · SHEET REVIEW

SHOWN PLAN COUNTS

Guestrooms24
Accessible guestrooms2 of 24
Connecting-labeled rooms2 of 24
Exit stairs2
Elevator lobby1
Storage room1

BROKEN CHAINS & PLAN ISSUES

PI-01 · Coordination

Stair room numbers reverse between sheets: A1.1 labels west Stair 2 as 001 and east Stair 1 as 002; A1.2 labels west Stair 2 as 002 and east Stair 1 as 001. Reconcile schedules and stair references.

PI-02 · Coordination

A small space near the south edge is labeled “Room 436” on this 200-series plan. Confirm its room name, number and use.

BC-01 · Coordination

The red longest-path route from Room 213 has no printed length. Link its measured travel distance and the upper-floor egress criteria before closing the life-safety review.

BC-02 · Coordination

“Typical upper level” does not identify the applicable floors. Match this layout and the 24 shown guestrooms to each upper-floor plan before multiplying quantities.

BC-03 · Coordination

Link the fire-rated wood-stud legend to specific A0.2 wall types and rated door/penetration details at corridors, stairs and shafts.

BC-04 · Coordination

Match emergency lights and exit signs to each corresponding upper-floor electrical sheet, including exit direction and emergency supply.

BC-05 · Coordination

Coordinate accessible rooms 207 and 226 with enlarged room plans, door hardware and A0.3 clearances; carry each applicable floor’s room numbers.

BC-06 · Cabinet locations

A1.2 includes the fire extinguisher/cabinet symbol in its legend but plots no locations. Obtain the upper-floor cabinet/extinguisher layout and coordinate wall recesses and corridor clearance.

Add working issue

Working notes · This session

TAKEOFF12 emergency lights · 10 exit signs
SCALEPrinted ⅛″ = 1′-0″
COORDINATIONArchitectural · electrical · fire protection
SOURCEA1.2 · 04.30.2025