A1.1 · First floor life safety Home2 Suites · Bradenton

A1.1 · LIFE SAFETY TAKEOFF

SYMBOL TAKEOFF / COUNTS

65 numbered symbols · select a type to isolate its marks.

PLAN NOTES / REQUIREMENTS

01 · Building / occupancy

Assembly A-2, business B and residential R-1. Construction Type V-A; sprinklered building. Printed building height: 40′-4″.

02 · Rated shaft enclosure

1-hour rated shaft enclosures. Coordinate wall construction, openings and penetrations with A0.2 wall assemblies and the shaft details.

03 · Exit travel paths

Green arrows identify exit travel paths; the red route identifies the longest path. Red route starts in Mechanical 109 and runs to the south exterior exit beside Sales 122.

04 · Stairs / vertical circulation

Two labeled stairs: Stair 2 / 001 at the west end and Stair 1 / 002 at the east end. Elevator 003 is adjacent to Stair 1.

05 · Common path / dead ends

Code table: common path to an exit 75′, with less than 75′ provided; dead-end corridor 20′, with less than 20′ provided.

06 · Exit travel distance

Code table prints maximum travel distance to exit 95′, while the provided column says less than 200′. Resolve the conflicting values against the red route.

07 · Corridor / door clearance

Code table prints minimum corridor width 44″, while provided column says minimum 36″. Exit-door clear opening is listed as 32″ minimum, with 32″ minimum provided at each door.

08 · Fire extinguisher / cabinet

Legend identifies fire extinguisher/cabinet. General contractor installs extinguishers with handle at 48″. Coordinate cabinet depth, wall construction and accessible-route projections.

09 · Emergency lighting

Legend identifies emergency lights and refers to electrical drawings. Reconcile architectural locations with E2.0 fixture types, emergency operation and switching.

10 · Exit signs

Legend identifies exit signs and refers to electrical drawings. Coordinate sign direction and visibility with the actual exit routes and electrical fixture schedule.

11 · Sprinkler / fire alarm

Building is sprinklered. A1.1 directs sprinkler and alarm system detail to fire protection and fire alarm drawings. Proposed Sprinkler Room 121 is labeled along the north service area.

12 · Guestroom / accessible route

Guestroom corridor connects the west and east circulation areas. Accessible Bedroom King One 107 is labeled; coordinate its route, door approach and clearances with A0.3 and enlarged room plans.

13 · Pool / exterior coordination

Plan labels pool, grilling patio, Pool Equipment 015 and Unisex ADA Restroom 017. Notes call out drain-line connections for equipment/restroom and a half wall with fence.

14 · Zoning reference

Full zoning data is referred to the civil drawing zoning-data block.

SOURCE

A1.1 · 04.30.2025 · PDF page 9
36″ × 24″ sheet

All source text

Select an item to highlight its source.

A1.1 First Floor Life Safety with exit paths, emergency lighting, exit signs and code review
A1.1 · SHEET REVIEW

BUILDING DATA

OccupanciesA-2 / B / R-1
ConstructionV-A
SprinkleredYES
Building height40′-4″
Shaft enclosure1 HR
Labeled stairs2
Extinguisher handle48″

BROKEN CHAINS & PLAN ISSUES

PI-01 · Coordination

The code table lists 95′ maximum exit travel but describes the provided distance as less than 200′. Reconcile both entries with the red longest-path route and its dimension.

PI-02 · Coordination

The code table lists 44″ minimum corridor width but says minimum 36″ provided. Confirm the required width and actual clear corridor width, then correct the table.

BC-01 · Coordination

A1.1 shows 49 emergency-light units and 16 exit-sign symbols. Reconcile each marked location with E2.0 fixture types and quantities, emergency supply, and sign direction.

BC-02 · Coordination

The 1-hour shaft requirement needs the selected A0.2 wall assembly, rated opening details and penetration/firestopping systems linked to each shaft.

BC-03 · Coordination

Link the sprinklered-building designation and Proposed Sprinkler Room 121 to fire protection, fire alarm and equipment layouts.

BC-04 · Coordination

A1.1 includes the fire extinguisher/cabinet symbol in its legend but plots no locations. Obtain the cabinet/extinguisher layout and coordinate the 48″ handle mounting note, wall depth and route clearance.

BC-05 · Coordination

Carry the civil zoning-data reference and exterior pool/fence/drain notes to the civil, pool and plumbing sheets.

Add working issue

Working notes · This session

TAKEOFF49 emergency lights · 16 exit signs
SCALEPrinted ⅛″ = 1′-0″
COORDINATIONArchitectural · electrical · fire protection
SOURCEA1.1 · 04.30.2025