C-9 · Drainage and Grading Plan Bradenton Hotel and Restaurant
TAKEOFF / ACTUAL SOURCE MARKS
Select a type to isolate its numbered source marks.
IMPORTANT CIVIL NOTES
MEASURED QUANTITIES
Select a row to draw its exact saved path on the plan.
PRINTED DIMENSIONS / REQUIREMENTS
Existing impervious: 3,132.13 SF (0.07 AC)
Demolition walks/drives/pavers: 3,284.2 SF
Demolition curb: 266.2 LF
Proposed buildings: 14,482.71 SF
Proposed walks: 4,474.80 SF
Proposed parking and drives: 41,198.38 SF
Proposed pool: 1,933.74 SF
Total proposed impervious: 62,089.67 SF (1.43 AC)
SOURCE
C-9 · Civil PDF page 9
Issued 02.23.2024 · 1" = 20 FT · PRINTED SCALE

DRAINAGE AND GRADING PLAN
BROKEN CHAINS & PLAN ISSUES
CIV-ADDR · Project address requires reconciliation
The civil set identifies 308 8th Street West. The architectural/MEP takeoff set identifies 716 3rd Avenue Drive West. Confirm the governing parcel and address before bid documents and RFIs are issued.
CIV-ROOMS · Civil hotel program conflicts with architectural takeoff
C-8 through C-10 label a 131-room hotel. The architectural takeoff verifies 85 guestrooms, while the mechanical schedules reference 107. Preserve all three values until the design team identifies the governing program.
C9-03 · Underground storage detail reference is broken
The chamber callout says SEE DETAILS but does not identify a sheet or detail number.
C9-04 · Pipe sizes are not certified from this sheet alone
Visible storm centerlines are measured, but run sizes, chamber manifold lengths and fittings must be reconciled to drainage details and profiles.
C9-05 · Title-block sequence is offset
C-9 prints 10 of 20 in its title block; C-10 prints 11 of 20. Confirm the issue-set sheet numbering.