C-4 · Demolitions Plan Bradenton Hotel and Restaurant

C-4 · TAKEOFF

TAKEOFF / SOURCE COUNTS

Select a type to isolate its numbered source marks.

IMPORTANT CIVIL NOTES

QUANTITIES / DIMENSIONS

No linear, area or volume quantity is reported unless supported by an explicit printed value. Graphic-only geometry remains open rather than estimated.

NOTES / REFERENCES

Demolition plan with 14 legend definitions, ten removal-directive callouts and eight remain-directive callouts. No demolition length or area is certified from uncalibrated graphic linework.

SOURCE

C-4 · Civil PDF page 4
Issued 02.23.2024 · 1" = 20' · PRINTED SCALE ONLY

C-4 Demolitions Plan original civil source
C-4 · SHEET REVIEW

DEMOLITIONS PLAN

Removal directive callouts10 REQ
Remain directive callouts8 REQ
Demolition legend definitions14 REF
Certified demolition LF / area0

BROKEN CHAINS & PLAN ISSUES

CIV-ADDR · Project address requires reconciliation

This civil set identifies 308 8th Street West. The architectural/MEP takeoff set identifies 716 3rd Avenue Drive West. The layouts appear to describe the same development, but the governing parcel/address has not been confirmed.

C4-02 · Plural and composite callouts are not physical counts

“Power poles” and “power pole and overhead wire” identify scope but do not establish separate verified object totals without field/plan confirmation.

C4-03 · Demolition lengths and areas remain open

No dimension chain independently supports asphalt, curb, utility-line or wire removal quantities; no scaled LF/SF is guessed.

C4-04 · Tree demolition is not shown here

Tree removal remains referred to the landscape/tree-removal documents.

C4-05 · Existing utilities to remain cross demolition limits

Protect and coordinate all remain items during removals; conflicts must be field located.

Add working issue

Working notes · This session

SCOPE18 directive callouts
BASIS10 remove / 8 remain
QUANTITYNo guessed LF or SF
REVIEW5 visible issues