  "schemaVersion": "1.0",
  "sheet": {
    "number": "C-4",
    "title": "Demolitions Plan",
    "civilPdfPage": 4,
    "sourcePdf": "BRADENTON HOTEL AND RESTAURANT Civil Set.pdf",
    "issueDate": "2024-02-23",
    "addressPrinted": "308 8th Street West, City of Bradenton, Florida",
    "scale": "1\" = 20' · PRINTED SCALE ONLY"
  },
  "coordinateSpace": {
    "width": 1920,
    "height": 1280
  },
  "groups": [
    {
      "id": "remove",
      "label": "Removal directive callouts",
      "count": 10,
      "unit": "REQ",
      "color": "#299bba",
      "basis": "SHOWN / SOURCE-LINKED",
      "status": "PLAN"
    },
    {
      "id": "remain",
      "label": "Remain directive callouts",
      "count": 8,
      "unit": "REQ",
      "color": "#d66a35",
      "basis": "SHOWN / SOURCE-LINKED",
      "status": "PLAN"
    }
  ],
  "regions": {
    "plan": [
      80,
      25,
      1660,
      1230
    ],
    "demo-core": [
      265,
      250,
      860,
      720
    ],
    "remain-core": [
      390,
      250,
      540,
      760
    ],
    "legend": [
      1475,
      30,
      260,
      300
    ],
    "title-block": [
      1735,
      25,
      165,
      1230
    ]
  },
  "requirements": [
    [
      "critical",
      "DEMOLITION",
      "Ten explicit removal callouts are identified",
      "Includes overhead wiring/poles, catch basin, drainage structure, sanitary sewer main, water services and a wooden shed. Physical item counts require field verification where callouts use plural or combine objects.",
      "demo-core"
    ],
    [
      "cost",
      "PROTECTION",
      "Eight remain callouts require protection and coordination",
      "Existing water mains, drainage structure, sanitary manhole, cleanouts and a city water line are labeled to remain.",
      "remain-core"
    ],
    [
      "critical",
      "LIMITS / RFI",
      "No dimensioned demolition limits are certified",
      "The sheet provides graphic linework and a printed plan scale, but removal lengths and pavement/curb areas are not dimensioned or independently calibrated. They remain unquantified.",
      "plan"
    ]
  ],
  "issues": [
    {
      "id": "CIV-ADDR",
      "title": "Project address requires reconciliation",
      "text": "This civil set identifies 308 8th Street West. The architectural/MEP takeoff set identifies 716 3rd Avenue Drive West. The layouts appear to describe the same development, but the governing parcel/address has not been confirmed."
    },
    {
      "id": "C4-02",
      "title": "Plural and composite callouts are not physical counts",
      "text": "“Power poles” and “power pole and overhead wire” identify scope but do not establish separate verified object totals without field/plan confirmation."
    },
    {
      "id": "C4-03",
      "title": "Demolition lengths and areas remain open",
      "text": "No dimension chain independently supports asphalt, curb, utility-line or wire removal quantities; no scaled LF/SF is guessed."
    },
    {
      "id": "C4-04",
      "title": "Tree demolition is not shown here",
      "text": "Tree removal remains referred to the landscape/tree-removal documents."
    },
    {
      "id": "C4-05",
      "title": "Existing utilities to remain cross demolition limits",
      "text": "Protect and coordinate all remain items during removals; conflicts must be field located."
    }
  ],
  "measurementPolicy": "No scaled quantity is reported without a printed dimension chain and independent calibration. Graphic-only geometry remains null.",
  "completeSheetGate": "PASS"
}