A2.3 · Third floor plan Home2 Suites · Bradenton
TAKEOFF / COUNTS
Select a takeoff to isolate its colored, numbered marks.
AREAS / WALL RUNS / FLOOR BUILDUP
⅛″ scale · common grid checked with A1.4.
30 room/core records · 24 bathroom zones.
Select a quantity to show its boundary and basis.
Room / wall quantity basis
Guestroom footprints include internal partition footprints. Each bathroom zone is part of its room total; the remaining footprint is shown separately. Final finish breaks follow the finish plans.
Room wall faces are gross perimeters before openings. Shared construction-wall runs are counted once in their own register. Wall heights and board layers come from the assigned assembly and sections.
Stair and elevator records are floor-level core footprints. Their full footprints are excluded from the floor-deck basis; reconcile landings and actual openings with structural details.
WALL TYPE ASSEMBLIES
A0.2 library · exact wall-run assignment open.
W1 · Corridor · 1 hr · STC 50 min.
Framing per structural; sound-attenuating batt insulation; 5/8″ Type X gypsum on resilient channels at one face; 5/8″ CDX plywood and 5/8″ Type X gypsum at the corridor face; acoustic/fire sealant at top and base, both sides; base per schedule.
Open assembly sourceW1A · Unrated · no CDX plywood
Use W1 construction with no rating and omit the CDX plywood. Retain the other shown layers unless coordinated otherwise.
Open assembly sourceW1B · 1 hr · no CDX plywood
Use W1 construction, maintain the one-hour rating, and omit the CDX plywood. Coordinate the applicable tested assembly for this variant.
Open assembly sourceW2 · 1 hr · UL U305
5/8″ Type X gypsum each face; sound-attenuating batt insulation in the framing cavity; acoustic sealant at top and base, both sides; base per schedule. Confirm framing with structural and the specified UL U305 assembly.
Open assembly sourceW2A · Unrated variant of W2
Same construction shown for W2, except no fire rating. Preserve sound batt and perimeter acoustic sealant.
Open assembly sourceW3 · Shear / party wall · 1 hr
Framing per structural; sound batt; 5/8″ Type X gypsum on resilient channels at one face; 5/8″ CDX plywood plus 5/8″ Type X gypsum at opposite face; acoustic/fire sealant both sides at top and base; scheduled base.
Open assembly sourceW3A · Unrated variant of W3
Same construction shown for W3, except no fire rating. The source does not omit the CDX plywood for this variant.
Open assembly sourceW4 · 1 hr · STC 65
Framing per structural; sound batt; two layers of 5/8″ Type X gypsum on resilient channels at one face (one base layer plus the additional layer called out); 5/8″ CDX plywood plus 5/8″ Type X gypsum on opposite face; scheduled base. Carry rated/acoustic continuity requirements from partition notes.
Open assembly sourceW5 · CMU · two details shown
Exterior detail: reinforced CMU per structural; continuous air/vapor barrier; direct-applied stucco or alternate exterior finish per elevations; interior 1-5/8″ metal furring and painted 5/8″ gypsum; scheduled base. Third W5 detail: masonry core with 1-5/8″ metal furring and painted 5/8″ gypsum on both faces. Keep these as separate W5 configurations pending tag clarification.
Open assembly sourceW6 · W5 variant · omit furring / insulation
Both W5 captions state W6 is similar without interior furring and insulation. Confirm the exposed interior finish and gypsum termination where furring is omitted; confirm which W5 configuration applies.
Open assembly sourceFLOOR / ROOM ASSEMBLIES
UL L514 · One-hour floor
Finish flooring per specifications · 1-1/2 inch gypcrete · 3/4 inch OSB deck · Wood framing per structural · 3-1/2 inch sound batt · 1/2 inch resilient channels at 16 inches on center · One layer 5/8 inch Firecore Type C gypsum.
Floor-deck basis 11,811.0 SF; 1½″ gypcrete 54.7 CY before waste. Core deductions and structural deck limits are recorded with the selectable quantities.
Open floor buildup24 guest kitchenette assemblies
24 sink locations counted. Carry each room’s shown appliance bays, worktops, cabinets, backsplash, hardware and connections into the enlarged-room takeoff using its room identity.
24 bath / shower assemblies
Bathroom zones, lavatories, water closets and bath/shower footprints are recorded separately. Carry wet-area board, tile backing, waterproofing, accessories, grab bars and supports from the applicable enlarged details.
Guest furniture / window-wall assemblies
24 sofa/workstation groupings; 29 beds; 26 window assemblies. Coordinate side tables, lamps, media panels, curtains, window-wall equipment, blocking and FF&E selections by room.
Interior signage / background music
24 guestroom identities establish a door-sign schedule basis. Coordinate directional and other interior signage and background music with the corrected brand standards.
PLAN NOTES / REFERENCES
Interior identification, directional and guestroom signage per the printed brand note. Background music designed and installed to brand standards.
Ice provision · linked from A2.2
A2.2 Hilton review requires ice-machine provision on every guestroom level; carry this floor’s device, drain, exhaust, finish and connections into coordination.
Open source annotationPrinted dimensions / references
No dimension chain is printed on this sheet. Scale is registered to the common structural grids.
References include A4.1, A5.1 and A5.2. Floor Plan Key Notes is blank.
SOURCE / TRACING VIEW
Original sheet · all furniture and review information.
A2.3 · PDF page 15 · 36″ × 24″
Printed date 04.30.2025
Select a source reference to highlight its location.

ROOM MATRIX · THIRD / TOTAL
DRAWN CONNECTIONS
305 ↔ 307 · 312 ↔ 314 · 324 ↔ 326
BROKEN CHAINS & PLAN ISSUES
PI-01 · Connecting rooms
Three physical connecting locations: 305–307, 312–314 and 324–326. The central pair is tagged X, not GR-03; two elevator openings also use X.Rooms 312 and 314 are labeled ordinary king studios despite the connecting opening.
PI-02 · Room mix / beds
Room 326 is an accessible king studio with one king bed. This floor has 19 king beds and 10 queen beds; do not carry the second floor’s two-queen layout into this room.
PI-03 · Accessible-room totals
The building matrix contains nine ADA rooms; the adjacent note states four accessible rooms without roll-in showers plus one with a roll-in shower. Reconcile those totals and the separately stated nine hearing-impaired rooms.
PI-04 · Connecting-room basis
The note uses 81 rooms × 10% = eight required and ten provided, while the matrix totals 107 rooms and eleven connecting-room entries. Resolve the room-versus-pair basis.
PI-05 · Signage brand
The general note names HAMPTON INN interior signage on this Home2 Suites project. Confirm room identification, directional and other interior sign standards.
BC-01 · Wall types
No W1–W6 wall tags are identified on this sheet. Corridor, shared guestroom and exterior runs are kept separate. Assign exact A0.2 assemblies and heights from the applicable wall sections; do not infer material from line weight or hatch alone.
BC-02 · Floor buildup
The 54.7 CY gypcrete basis uses the A0.2 1½-inch layer on 11,811.0 SF after full stair/core deductions. Reconcile stair landings, actual slab openings, wet-area buildup and structural deck limits before final material quantities.
BC-03 · Ice provision / cross-sheet note
A2.2 requires an ice machine at every guestroom level. One provision is carried for floor 3; its location, floor drain, finish and exhaust are not plotted here.
BC-04 · Room finishes / furniture
24 bathroom zones and remaining room footprints are retained. Resolve finish boundaries, cabinet/appliance specifications, media panels, side tables, lamps, accessories and mounting/backing through enlarged rooms and FF&E. Small freestanding outlines remain furniture-type coordination items.
BC-05 · Life safety / continuing systems
Reconcile emergency lights, exit signs and fire cabinets with the floor-specific life-safety/electrical sheets. Stair zones and elevator shaft outlines continue the existing building systems; they are not additional systems per floor.
BC-06 · Opening schedules
Only the bath access in suite 307 carries GR-06. Suite 302 does not repeat the second floor’s extra GR-06 location. Match actual opening locations and paired leaves to the door/hardware schedules.
PI-06 · Missing references
Floor Plan Key Notes has a heading without note text. A section marker near grid 12 has a blank/dash destination. Resolve the references.
Add working issue
Working notes · This session