E3.3 · Power Fourth Floor Plan Home2 Suites · Bradenton
TAKEOFF / ACTUAL PLAN COUNTS
Select a type to isolate its numbered source marks.
IMPORTANT HVAC / ELECTRICAL NOTES
QUANTITIES / DIMENSIONS
Select a row to show its exact source basis.
ASSEMBLIES / ACCESSORIES
Fourth-floor power
Six unqualified corridor duplex-family occurrences, one half-filled receptacle-family point, one HP point, two panels and two home-run callouts are retained.
Neutral classification
The recurring corridor symbols are not classified as fire/smoke-damper J-boxes. Their subtype/use remains unresolved.
Guestroom scope
Twenty-four room labels are evidence only; no guestroom power devices or typical mapping are shown on E3.3.
NOTES / REFERENCES
1. FOR HOME RUNS (FROM UNITS) 100 FT OR MORE, THE ELECTRICAL CONTRACTOR HAS TO CHECK THE VOLTAGE DROP AND SELECT THE SUITABLE CABLES SIZE TO COMPLY WITH THE MAXIMUM ALLOWED VOLTAGE DROP FOR THE FEEDER CONDUCTOR (3%). THE MAXIMUM COMBINED VOLTAGE DROP ON BOTH INSTALLED FEEDER CONDUCTORS AND BRANCH CIRCUIT CONDUCTORS TO THE FARTHEST CONNECTED LOAD OR OUTLET SHALL NOT EXCEED 5 PERCENT.
2. THE CONTRACTOR SHALL VERIFY WITH THE OWNER/FRANCHISE FOR THE QUANTITIES AND LOCATIONS OF THE LOW VOLTAGE SYSTEM DEVICES (CAMERA, CARD READER, WIRELESS ACCESS POINT, ETC.) AND PROVIDE ALL NECESSARY ACCESSORIES TO COMPLETE THE WIRING, POWER SUPPLY FOR THE DEVICES AS PER THE MANUFACTURER SPECIFICATIONS/ INSTALLATION GUIDELINES.
3. THE CONTRACTOR SHALL VERIFY LOCATION OF ALL FLOOR OUTLETS WITH FURNITURE/ ARCH. PRIOR TO INSTALLATION.
4. ELECTRICAL CONTRACTORS MUST VERIFY ALL ELECTRICAL REQUIREMENTS WITH THE HVAC AND PLUMBING SYSTEMS TO PROVIDE ALL NECESSARY ACCESSORIES TO COMPLETE THE CONTROL WIRING FOR THE MOTORS.
1. CONTRACTOR SHALL PROVIDE J-BOXES FOR FIRE SMOKE DAMPERS AT 4TH FLOOR, CONNECT TO L4.A-30, USING 2#12, 1/2"C.
1. THE PANELBOARD SHALL BE LOCKABLE AND ACCESSIBLE TO QUALIFIED PERSONS ONLY. FIELD VERIFICATION OF THE BEST LOCATION OF ELECTRICAL PANELS PRIOR TO INSTALLATION. THE LOCATION OF ELECTRICAL PANELS MUST COMPLY WITH 110.26 AND 240.24 OF THE NEC.
{"detail": "12 installed/circuit-callout markers plus 2 non-installed keynote references", "id": "C01", "result": "pass", "test": "marker/count reconciliation"}
{"detail": "six distinct corridor occurrences: three north-wall and three south-wall positions; plotted FSD J-box count is zero", "id": "C02", "result": "pass", "test": "unqualified duplex-family occurrence count"}
{"detail": "6 source paths = 181.124 raw LF = 181.0 LF aggregate rounded to 0.5", "id": "C03", "result": "pass", "test": "wire arithmetic"}
{"detail": "W01-W03 form the L4.A-26 west duplex-family chain; W04-W06 form the continuous L4.A-28 east/HP/storage chain; no path is drawn between them and neither network is assigned to the note-only FSD requirement", "id": "C04", "result": "pass", "test": "network continuity"}
{"detail": "24 guestroom labels retained; zero power devices inferred from furniture/background geometry", "id": "C05", "result": "pass", "test": "guestroom double-count protection"}
{"detail": "10800/2592 = 7200/1728 = 4.1666667 raster pixels/PDF point; 9 PDF points/ft = 37.5 raster pixels/ft", "id": "C06", "result": "pass", "test": "scale resolution"}
SOURCE
E3.3 · Engineering PDF page 45
Issued 11.22.2024 · 1/8" = 1'-0" · PRINTED SCALE ONLY

POWER FOURTH FLOOR PLAN
BROKEN CHAINS & PLAN ISSUES
E33-01 · Fire/Smoke-Damper Requirement Is Note-Only
The dedicated note requires fourth-floor FSD J-boxes on L4.A-30 using 2#12 in 1/2-inch conduit, but no FSD J-box locations are plotted. The two visible networks are labeled L4.A-26 and L4.A-28 and are not assigned to the FSD note. Installed FSD J-box quantity remains null.
E33-02 · Six Corridor Device Subtypes And Uses Unresolved
The six corridor occurrences are circular duplex/receptacle-family graphics and are counted neutrally. They are not FSD J-boxes and are not associated with the note-only L4.A-30 requirement. Confirm exact receptacle subtype and served use.
E33-03 · No Typical Guestroom Power Reference
The sheet contains 24 guestrooms but plots no guestroom power devices and gives no explicit typical-room sheet/mapping. No typical quantity is inferred; the guestroom power scope is an unresolved cross-sheet chain.
E33-04 · Hp Tag Not Defined Locally
One duplex-family wall occurrence in Elevator Lobby 400 is tagged HP. E3.3 does not expand HP, so equipment/service identity and mounting requirement remain unresolved.
E33-05 · Half-Filled Receptacle Subtype Unlabeled
One half-filled circular receptacle-family symbol is plotted by L4.A and the L4.A-28 home run without a readable GFI/switch/emergency modifier. Counted once but not assigned a subtype.
E33-06 · Installed/Conductor Quantities Unavailable
Only drawn plan curves are measured. Vertical rises, panel routing, hidden routing, conductor allocation, fittings and installed conductor/conduit LF are not shown and remain null.
E33-07 · Panel Locations Are Provisional
Key note 1 requires field verification of panel location and NEC 110.26/240.24 compliance; L4.A and L4.B are plotted once each, but final locations are not certified.
E33-08 · No Independent Scale Dimension
The printed scale is internally checked against PDF/raster resolution, but no legible independent plan dimension chain is available.
E33-09 · Ocr Omission
source-45.txt omits the substantive notes and most plotted callouts. Counts and paths therefore rely on the full-resolution raster and page vector geometry.
Add working issue
Working notes · This session