A6.2 · Wall / Roof / PTAC / Foundation Details Home2 Suites · Bradenton

A6.2 · TAKEOFF

TAKEOFF / SOURCE COUNTS

Select a row for its source and quantity basis.

AREAS / LENGTHS

Select a quantity to show its source boundary.

ASSEMBLIES / RECONCILIATION

Window / PTAC interface

Window tabs, integral louver, sleeve/blank-off, PTAC/sub-base, foam insulation, drywall closure, stone sill and sealant; reconcile exact opening and manufacturer installation.

Condensate variant

Route through wall to project-selected discharge. Pipe size, slope, termination and full route remain unresolved; alternate destination text is not a design selection.

Floor layer

Carpet over1-1/2-inch Gypcrete and subfloor, with joist/resilient channel/gypsum beneath. Repeated details do not double the topping thickness.

Coping / fascia roof edges

Aluminum coping/fascia, blocking, roof layers, framing, hanger/header, flashing and drip edge. KEEP excluded from repeated one-foot profile direction.

Vented roof edge

Wood kicker, airflow openings, venting louver and insect screen in the shown option. Opening sizes and net free area unspecified.

Foundation core

Core finish, sheathing, barrier, framing, gypsum, insulation, flashing and trim; align finish start to window-sill bottom where indicated.

Foundation support

Support finish, mortar bed, insulation, concrete slab/vapor barrier, joint/sealant, regional perimeter insulation and sill gasket.8-inch minimum grade relation retained.

Shade / overflow conditions

Blackout/sheer shades, motorized J-box where required, overflow scupper where occurs and piping beyond. Typical labels do not establish actual installed counts.

PLAN NOTES / REFERENCES

Nine unnumbered details: two plan details, two window/PTAC sections, three roof-edge sections, and two foundation conditions. Similar details are not separate actual installations.

PTAC assembly includes sleeve/blank-off panel, integral window louver, sealant, engineered stone sill, foam insulation and drywall closure; condensate variant adds sub-base and routing requirements.

1-1/2-inch Gypcrete appears in both PTAC floor sections with carpet, subfloor, floor joist/resilient channel/gypsum below. This is one repeated nominal thickness, not two stacked layers.

Roof details identify coping/fascia, blocking, roof sheathing/insulation/roofing, double plates, hanger, header and flashing. Vented option includes wood kicker, venting louver and insect-screened airflow openings.

Foundation support adds mortar setting bed, perimeter insulation by regional requirements, sill gasket, vapor barrier and preformed joint/sealant; support/core finishes remain separate conditions.

No printed detail scale. Dimensions are recorded as explicit local requirements; do not measure through break symbols or infer lengths for piping/wiring beyond the depicted detail.

SOURCE

A6.2 · PDF page43 · 36″ × 24″
Printed04.30.2025

Select a source region.

A6.2 Wall / Roof / PTAC / Foundation Details original source
A6.2 · SHEET REVIEW

WALL / ROOF / PTAC / FOUNDATION DETAILS

Source marks130
Measurement rows16
Scope basisNine typical assembly details

BROKEN CHAINS & PLAN ISSUES

PI-01 · Condensate discharge destination is conditional

Note lists storm, sanitary or dry-well routing depending on design, with landscape discharge where local requirements dictate. No project-selected destination, pipe size/slope, trap, connection detail or whole route length is established here.

PI-02 · Joist / Gypcrete detail versus A6.1 key10

A6.2 calls out floor joist, subfloor and1-1/2-inch Gypcrete; A6.1 key10 says CMU block and plank. Confirm actual structural floor and topping before assigning Gypcrete area/volume or joist quantities.

PI-03 · Unnumbered details and no printed scale

All nine detail titles lack detail numbers and scales. Plan/PTAC views include breaks. Match exact detail locations and dimension strings; references such as6/A-602 are not resolved merely because A6.2 exists.

PI-04 · Coping perimeter exception at KEEP

One-foot projection direction applies around the perimeter EXCEPT AT KEEP. Do not extend that profile into the KEEP without its separate detail. Material thickness, laps, corners, joints and fixing remain unspecified.

PI-05 · Overflow and motorized shade are conditional

Scupper is shown BEYOND/WHERE OCCURS, and shade J-box WHERE REQUIRED. These typical references do not establish installed scupper or motorized-shade counts; reconcile A4.2 five scupper callouts and actual accessible-room requirements.

PI-06 · Vented roof-edge opening sizes missing

Venting louver, airflow openings and insect screen are required in the depicted option, but opening dimensions, free area, screen mesh and quantity along perimeter are not provided. Do not convert detail labels into installed vent EA.

PI-07 · Foundation clearances / finish selection

Support detail shows8-inch MIN grade clearance and2-inch local offsets; core detail shows6-inch TYP and finish start aligned with bottom of aluminum window sill. Resolve site grades, finish transitions and insulation requirements at each actual location.

BC-01 · Typical views are not additional installed assets

Match these details and sections to actual rooms, walls, roof edges and foundations already counted. REF/source occurrences identify construction scope; they do not multiply actual quantities.

SYNC · Mason Brain / estimate transfer

No verified Mason Brain synchronization or estimate import. Preserve dimensions, applicability, conflicts and source-view identity when transferring.

Add working issue

Working notes · This session

TAKEOFFA6.2 · Wall / Roof / PTAC / Foundation Details
SCALEUnlabeled · printed dimensions only
QUANTITIESActual floors · scope classes separate
REVIEWVisible coordination issues