A6.1 · Wall Sections and Assembly Key Home2 Suites · Bradenton

A6.1 · TAKEOFF

TAKEOFF / SOURCE COUNTS

Select a row for its source and quantity basis.

AREAS / LENGTHS

Select a quantity to show its source boundary.

ASSEMBLIES / RECONCILIATION

Exterior walls · keys2/5/6

Selected WRAP/CORE/SUPPORT finish; weather and air barrier; exterior sheathing; insulation;2x6 framing; gypsum board. Layer thicknesses, stud spacing, fastening and rating unresolved.

Roof · key8

White roofing system, rigid insulation, exterior roof sheathing, wood structure and gypsum ceiling. Slopes, insulation values and member sizing unresolved.

Alternate roof · key32

White roofing, rigid insulation and exterior roof sheathing; complete support/ceiling system not specified by this key.

Floor · key10

CMU block and plank is the literal source definition; conflicts with joist/subfloor/Gypcrete detail onA6.2. Selection must be resolved.

Slab / foundations · keys11/13

Concrete slab over vapor barrier; concrete flooring/foundation wall. Thickness, reinforcement, footing dimensions and design criteria absent.

Window / PTAC / shade · keys15/21/30

Fixed aluminum window with integral louver, PTAC unit and shade system. Tie to actual room/window and trade schedule; typical occurrences are not extra installations.

Door / ceiling / paving · keys17/22/26

Aluminum wide-stile door, suspended ceiling and precast concrete/natural-stone pavers. Complete product selection, supporting assembly and applicability unresolved.

PLAN NOTES / REFERENCES

No printed drawing scale or numbered wall-section titles found on A6.1. Left/center/right source views retained by location. Break symbols interrupt vertical stacks; no full wall-height or SF measurement across breaks.

Explicit8-foot minimum ceiling clearances are minima, not exact calibration lengths. Other printed dimensions recorded separately.

Finish key references A4.1 and adds EX-8A REVEAL and EX-8B BAND to EX-8 BEAM. A4.1 groups the beacon under EX-8; coordinate subdivision before applying its face quantities.

SOURCE

A6.1 · PDF page42 · 36″ × 24″
Printed04.30.2025

Select a source region.

A6.1 Wall Sections and Assembly Key original source
A6.1 · SHEET REVIEW

WALL SECTIONS AND ASSEMBLY KEY

Source marks78
Measurement rows12
Scope basisBroken typical wall sections

BROKEN CHAINS & PLAN ISSUES

PI-01 · Floor assembly conflicts with detail construction

Key10 says CMU BLOCK AND PLANK. Drawn section floors and A6.2 detail callouts show floor joists/subfloor and1-1/2-inch Gypcrete. Select the actual structural assembly with structural design; do not combine both systems.

PI-02 · Missing scale / numbered wall-section identities

These wall sections have no printed scale or numbered titles. Vertical break symbols prevent full-height measurement. Explicit dimensions remain usable locally, but full geometry and cross-sheet detail mappings require clarification.

PI-03 · Level04 is skipped in the typical stack

The source labels LEVEL01,02,03,05, roof truss bearing and parapet; LEVEL04 is absent and break symbols are present. Do not infer an omitted floor or multiply visible typical components as the whole building.

PI-04 · 8/A-303 reference unresolved

Ground king/PTAC detail bubble points to8/A-303. No exact destination established in the current indexed A3.x set. Similar A3.3 or a ceiling plan is not a confirmed replacement.

PI-05 · Wall framing specified but full build-up missing

Keys2/5/6 state2x6 framing with finish, weather/air barrier, exterior sheathing, insulation and gypsum board. Stud spacing, grades, sheathing/gypsum thickness, insulation performance, fastening and rated assembly remain unspecified here.

PI-06 · EX-8 subdivisions need elevation reconciliation

A6.1 distinguishes EX-8 BEAM,EX-8A REVEAL,EX-8B BAND; A4.1 groups the beacon under EX-8. Source tags do not alone resolve exact material or all subdivision extents.

BC-01 · Typical views are not additional installed assets

Match these details and sections to actual rooms, walls, roof edges and foundations already counted. REF/source occurrences identify construction scope; they do not multiply actual quantities.

SYNC · Mason Brain / estimate transfer

No verified Mason Brain synchronization or estimate import. Preserve dimensions, applicability, conflicts and source-view identity when transferring.

Add working issue

Working notes · This session

TAKEOFFA6.1 · Wall Sections and Assembly Key
SCALEUnlabeled · printed dimensions only
QUANTITIESActual floors · scope classes separate
REVIEWVisible coordination issues