E3.5 · Power Roof Plan Home2 Suites · Bradenton

E3.5 · TAKEOFF

TAKEOFF / ACTUAL PLAN COUNTS

Select a type to isolate its numbered source marks.

IMPORTANT HVAC / ELECTRICAL NOTES

QUANTITIES / DIMENSIONS

Select a row to show its exact source basis.

ASSEMBLIES / ACCESSORIES

Roof equipment

DOAS-1, DOAS-2 and EF-10 plus their plotted WP disconnect/GFI accessories are individually marked; ratings and unshown controls are not inferred.

Circuit callouts

Five home-run/circuit callouts contain nine printed circuit numbers. Callout arrows and slashes are not measurable route length.

Sign power

One WP sign safety switch and one WP sign J-box are retained; architectural sign location/detail reference remains broken.

NOTES / REFERENCES

1. DISCONNECT FOR SIGN.

2. LOCATION FOR SIGN CONNECTION. VERIFY LOCATION WITH ARCHITECTURAL PLAN PRIOR TO INSTALLATION.

2

0

0

0

0

The two-line KEY NOTE table is the only note block on E3.5. HVAC coordination is conveyed by the DOAS-1, DOAS-2 and EF-10 tags and circuit associations, not by a separate note. No plumbing load or plumbing coordination note is printed.

SOURCE

E3.5 · Engineering PDF page 47
Issued 11.22.2024 · 1/8" = 1'-0" · PRINTED SCALE ONLY

E3.5 Power Roof Plan original source
E3.5 · SHEET REVIEW

POWER ROOF PLAN

Installed equipment / devices11 EA
Circuit callouts / circuit numbers5 / 9
Visible roof centerlines2 · 142.5 drawing LF
Keyed notes2

BROKEN CHAINS & PLAN ISSUES

I1 · Open Coordination Reference

Keyed Note 2 requires verification with the architectural plan but gives no architectural sheet or detail number.

I2 · Open Panel Reference

MDP, L5.A and L1.B circuits are identified, but E3.5 gives no panel-schedule sheet/detail references for breaker, load or conductor validation.

I3 · Rating Gap

DOAS-1, DOAS-2, EF-10 and sign disconnect ratings, poles, voltage, phase, MCA/MOCP and enclosure/NEMA ratings are not printed on E3.5; WP alone means weather proof per E1.1.

I4 · Mechanical Coordination Gap

Mechanical equipment tags are plotted without a mechanical plan/schedule cross-reference; electrical sizing cannot be closed from E3.5 alone.

I5 · Routing Limit

The two measured curves are drawing centerlines/diagrammatic connections. Installed route, conduit, conductor, verticals, concealed routing, slack and fittings are not derivable and remain null.

I6 · Reference Background

Light-gray roof outlines, grids, roof drains and other architectural/plumbing background graphics are reference context and were excluded from electrical quantities.

I7 · Schedule Absence

No electrical, equipment or roof-device schedule is printed on E3.5; no SCHED or ALT quantity can be certified from this sheet.

Add working issue

Working notes · This session

PLAN MARKERS19
RUNS2
DRAWN LF142.5
REVIEW7 visible issues