A7.12 · Workstations, Manager and Employee Break Room Home2 Suites · Bradenton
TAKEOFF / SOURCE COUNTS
Select a row for its source and quantity basis.
AREAS / LENGTHS
Select a quantity to show its source boundary.
ASSEMBLIES / RECONCILIATION
Workstations / manager
Laminate worktops, cleats, metal brackets, end panels where occurring and field-cut grommets. Overall heights 2ft7 shown at workstation details; manager span is not independently dimensioned.
Break casework
Stepped upper cabinet pair; accessible sink knee-space; adjacent two-door/two-drawer base cabinet, black melamine interior, laminate exposed faces and leg levelers.
Equipment / services
One two-compartment sink/faucet and one refrigerator. Final equipment specs control openings, plumbing and electrical coordination.
PLAN NOTES / REFERENCES
Selected plan tops, chairs, equipment and cabinet components counted once. Generic details and elevations repeat those assets.
Break cabinet has black melamine interiors, laminate exposed surfaces, specified pulls and leg levelers. Sink support/knee clearance and final appliance sizes remain required.
Worktops require continuous cleats at walls/sides, scribing, field-cut 2-1/4in grommets and brackets at 48in OC maximum. Clearance dimensions remain requirements, not actual installed verification.
Match source occurrences to actual room/asset IDs before project totals. This takeoff publication does not represent an estimate import or Mason Brain synchronization.
SOURCE
A7.12 · PDF page49 · 36″ × 24″
Printed04.30.2025
Select a source region.

WORKSTATIONS, MANAGER AND EMPLOYEE BREAK ROOM
BROKEN CHAINS & PLAN ISSUES
PI-01 · Counter dimension extents differ across views
Break elevation shows 4ft7-1/2 base run; plan also shows 4ft7 and 4ft9-1/2 extents. Register body, end panels and overhangs before final top fabrication; traced envelope remains provisional.
PI-02 · Manager overall length needs field confirmation
Manager surface is drawn about 7.55ft long at sheet scale without a corresponding overall dimension. Do not mistake vertical 7ft6 cabinet height for its plan length.
PI-03 · Equipment specifications and services pending
Source expressly requires final equipment coordination. Refrigerator VIF size, sink cutout, faucet, waste/supply and circuiting remain unresolved. Two bowls do not create two sink assemblies.
PI-04 · Supports and clearances must be registered
Selected plans show two manager brackets and one center workstation bracket, while generic detail limits spacing to 48in maximum. Verify cleat/end-panel support and required knee widths with fabricated layout.
Add working issue
Working notes · This session