  "sheet": "E6.2",
  "notes": [
    "General note 1. CONTRACTOR SHALL PROVIDE A PERMANENTLY AFFIXED LABEL WITH THE MAXIMUM FAULT CURRENT PER ARTICLE 110.24. THE LABEL SHALL INCLUDE THE DATE THE FAULT-CURRENT CALCULATION WAS PERFORMED AND BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. THE LABEL SHALL BE 2”X3” IN SIZE AND SHALL BE BLUE LETTERING ON A CONTRASTING BACKGROUND.",
    "General note 2. CONTRACTOR TO VERIFY FINAL CURRENT VALUES FROM ELECTRICAL UTILITY COMPANY AND PROVIDE AIC PROTECTION ACCORDINGLY.",
    "General note 3. AIC RATINGS OF ALL THE PANELS & BRANCH BREAKERS SHALL MATCH THE FAULT CURRENT OF THE TRANSFORMER.",
    "L1.E note 1. VERIFY HPs, BREAKER SIZES, CABLES SIZES FOR THE HVAC EQUIPMENT WITH THE MECHANICAL EQUIPMENT SCHEDULE PRIOR TO INSTALLATION.",
    "L1.E note 2. FIELD VERIFICATION BREAKER SIZES, CABLE SIZES, ETC WITH EV CHARGING SUPPLIER/ MANUFACTURER PRIOR TO INSTALLATION.",
    "EP note 1. PROVIDE FIRE ALARM CIRCUIT BREAKER WITH RED MARKING PER NEC REQUIREMENTS.",
    "EP note 2. VERIFY HPs, BREAKER SIZES, ETC FOR ELEVATOR WITH ELEVATOR MANUFACTURER & CODE REQUIREMENTS PRIOR TO PLACING ORDERS/ INSTALLATION.",
    "EP note 3. THE BREAKER WILL BE SHUT OFF WHEN A FIRE OCCURS VIA THE SIGNAL FROM FACP.",
    "PP note 1. FIELD VERIFICATION BREAKER SIZES, CABLE SIZES, ETC WITH KITCHEN SUPPLIER PRIOR TO INSTALLATION.",
    "SP note 1. CONTROLLED BY A 20A, 1P, TIME CLOCK WITH 4 HR BATTERIES.",
    "SP note 2. FIELD VERIFICATION BREAKER SIZES, CABLE SIZES, ETC WITH POOL CONTRACTOR PRIOR TO INSTALLATION.",
    "SP note 3. BREAKERS AND BRANCH CIRCUITS WILL BE INSTALLED UNDER THE POOL PERMIT AND THIS PERMIT COVERS ONLY THE INSTALLATION OF THE PANEL AND GROUND.",
    "MDP note 1. SWITCHBOARD IS 'FULLY' RATED TO INCLUDE 65K AIC BREAKER.",
    "MDP note 2. SEE ONE-LINE DIAGRAM FOR COMPLETE FEEDER SIZES.",
    "MDP note 3. FIELD VERIFICATION HP PRIOR TO INSTALLING BRKR, CONDUIT, WIRE, ETC.",
    "MDP note 4. PANELS WITH BREAKERS 1200A AND OVER REQUIRE ARC FLASH REDUCTION PER NEC 240.87.",
    "MDP note 5. CONTRACTOR WILL PROVIDE PANEL WITH ENERGY REDUCING MAINTENANCE SWITCH.",
    "MDP note 6. THE CONTRACTOR HAS TO CHECK THE SIZE OF THE ELECTRICAL ROOM TO PROVIDE THE MAIN SWITCHGEAR WITH SUITABLE DIMENSIONS AND COMPLIANT WITH CODES FOR THE CLEARANCE REQUIREMENTS.",
    "GENSET note 1. ELECTRICAL CONTRACTOR SHALL VERIFY HPs, CABLE SIZES, BREAKER LUGS, DS, ETC OF FIRE PUMPS WITH FIRE CONTRACTOR PRIOR TO INSTALLATION."
  ],
  "assemblies": [
    [
      "L1.E",
      "120/208V, 3PH, 4W; 400 AMP COPPER; 400 AMP M.L.O; 42 KA; fed from MDP; ELEC. RM. 1ST FLOOR. 42 complete circuit positions."
    ],
    [
      "EP",
      "120/208V, 3PH, 4W; 250 AMP COPPER; 250 AMP M.C.B; 42 KA; fed from MDP/GENSET VIA ATS; ELECT. 1ST FLOOR. 42 complete circuit positions."
    ],
    [
      "PP",
      "120/208V, 3PH, 4W; 150 AMP COPPER; 150 AMP M.L.O; 30 KA; fed from MDP; FOOD PREP. 1ST FLOOR. 42 complete circuit positions."
    ],
    [
      "SP",
      "120/208V, 3PH, 4W; 100 AMP COPPER; 100 AMP M.L.O; 10 KA; fed from MDP; POOL EQUIP. RM. 24 complete circuit positions."
    ],
    [
      "MDP",
      "120/208V, 3PH, 4W; 2500 AMP COPPER; 2500 AMP M.C.B; 65 KA; fed from SERVICE TRANSFORMER; ELECT. 1ST FLOOR. 66 complete circuit positions."
    ],
    [
      "GENSET PANEL (BUILT-IN)",
      "120/208V, 3PH, 4W; 500 AMP COPPER; 500 AMP M.C.B; 42 KA; 6 circuit positions; 163 kVA selected from printed fire/operational calculations."
    ]
  ],
  "registers": {
    "fullAudit": {
      "sheet": "E6.2",
      "title": "ELECTRICAL PANELS SCHEDULE",
      "engineeringPdfPage": 55,
      "source": {
        "pdf": "/workspace/sites/ssx-cover-release/source-plans/engineering.pdf",
        "sheetRaster": "/workspace/sites/ssx-cover-release/tmp/pdfs/final3-e62-e80/thumb-55.png",
        "sheetRasterPixels": [
          7200,
          4800
        ],
        "embeddedScheduleImages": [
          "img-003.png",
          "img-004.png",
          "img-005.png",
          "img-006.png",
          "img-007.png",
          "img-008.png",
          "img-009.png"
        ]
      },
      "scale": {
        "printed": null,
        "basis": "schedule sheet; no drawing scale applies"
      },
      "coordinateSystem": {
        "space": "normalized sheet landscape",
        "width": 1920,
        "height": 1280,
        "transform": "x=sourceX/3.75; y=sourceY/3.75"
      },
      "titleBlock": {
        "project": "HOME 2 SUITES",
        "location": "BRADENTON, FL.",
        "projectNo": "210729",
        "drawnBy": "PL",
        "checkedBy": "DV",
        "date": "NOV. 22, 2024",
        "sheet": "E6.2",
        "architect": "FIRM-O CONSTRUCTION / Fawley Bryant Architecture",
        "architectAddress": "205 N. Orange Ave, Suite 301, Sarasota, FL 34236",
        "engineerSeal": {
          "name": "Dung D. Vu",
          "license": "No. 83005",
          "state": "Florida"
        },
        "revisions": [],
        "revisionTableBlank": true
      },
      "regions": [
        {
          "id": "L1E",
          "label": "Panel L1.E schedule",
          "bbox": [
            93,
            92,
            824,
            361
          ]
        },
        {
          "id": "EP",
          "label": "Panel EP schedule",
          "bbox": [
            858,
            92,
            1593,
            361
          ]
        },
        {
          "id": "PP",
          "label": "Panel PP schedule",
          "bbox": [
            93,
            395,
            824,
            669
          ]
        },
        {
          "id": "GENSET",
          "label": "GENSET PANEL (BUILT-IN) schedule and generator calculation",
          "bbox": [
            858,
            395,
            1593,
            604
          ]
        },
        {
          "id": "SP",
          "label": "Panel SP schedule",
          "bbox": [
            93,
            703,
            824,
            917
          ]
        },
        {
          "id": "MDP",
          "label": "MDP schedule, feeder calculation and notes",
          "bbox": [
            858,
            655,
            1593,
            1104
          ]
        },
        {
          "id": "PANEL_INDEX",
          "label": "Panel index",
          "bbox": [
            1627,
            89,
            1724,
            175
          ]
        },
        {
          "id": "GENERAL_NOTES",
          "label": "General notes",
          "bbox": [
            93,
            949,
            824,
            1036
          ]
        },
        {
          "id": "TITLE_BLOCK",
          "label": "Title block / seal / revisions",
          "bbox": [
            1740,
            38,
            1885,
            1244
          ]
        },
        {
          "id": "FOOTER",
          "label": "Copyright footer",
          "bbox": [
            82,
            1220,
            800,
            1248
          ]
        }
      ],
      "groups": [
        {
          "id": "panel_schedules",
          "count": 6,
          "basis": "SCHED",
          "markers": [
            {
              "x": 459,
              "y": 226,
              "sourceNote": "L1.E (FED FROM MDP)"
            },
            {
              "x": 1226,
              "y": 226,
              "sourceNote": "EP (FED FROM MDP/GENSET VIA ATS)"
            },
            {
              "x": 459,
              "y": 532,
              "sourceNote": "PP (FED FROM MDP)"
            },
            {
              "x": 1226,
              "y": 500,
              "sourceNote": "GENSET PANEL (BUILT-IN)"
            },
            {
              "x": 459,
              "y": 810,
              "sourceNote": "SP (FED FROM MDP)"
            },
            {
              "x": 1226,
              "y": 880,
              "sourceNote": "MDP (FED FROM SERVICE TRANSFORMER)"
            }
          ]
        },
        {
          "id": "panel_index_entries",
          "count": 4,
          "basis": "INDEX",
          "markers": [
            {
              "x": 1654,
              "y": 122,
              "sourceNote": "L1.E"
            },
            {
              "x": 1695,
              "y": 122,
              "sourceNote": "MDP"
            },
            {
              "x": 1654,
              "y": 144,
              "sourceNote": "PP"
            },
            {
              "x": 1654,
              "y": 166,
              "sourceNote": "SP"
            }
          ]
        },
        {
          "id": "general_notes",
          "count": 3,
          "basis": "NOTE",
          "markers": [
            {
              "x": 108,
              "y": 979,
              "sourceNote": "General note 1"
            },
            {
              "x": 108,
              "y": 1001,
              "sourceNote": "General note 2"
            },
            {
              "x": 108,
              "y": 1021,
              "sourceNote": "General note 3"
            }
          ]
        }
      ],
      "rowSchema": [
        "ckt",
        "side",
        "loadType",
        "description",
        "notes",
        "poles",
        "breaker",
        "wire",
        "voltAmps",
        "phase",
        "combinedPhaseVA",
        "continuationOf"
      ],
      "panels": [
        {
          "id": "L1.E",
          "fedFrom": "MDP",
          "header": {
            "voltage": "120/208V",
            "phase": 3,
            "wires": 4,
            "nema": "NEMA-1",
            "aic": "42 KA",
            "bus": "400 AMP COPPER",
            "mains": "400 AMP M.L.O.",
            "mounting": "SURFACE MOUNTED",
            "location": "ELEC. RM. 1ST FLOOR"
          },
          "circuitPositionCount": 42,
          "rows": [
            [
              1,
              "L",
              "HTG",
              "AHU-1.1",
              null,
              2,
              "30/2",
              "10",
              3110,
              "A",
              6219,
              null
            ],
            [
              2,
              "R",
              "HTG",
              "AHU-1.5",
              null,
              2,
              "30/2",
              "10",
              3110,
              "A",
              6219,
              null
            ],
            [
              3,
              "L",
              "HTG",
              "AHU-1.1",
              null,
              null,
              null,
              null,
              3110,
              "B",
              6219,
              1
            ],
            [
              4,
              "R",
              "HTG",
              "AHU-1.5",
              null,
              null,
              null,
              null,
              3110,
              "B",
              6219,
              2
            ],
            [
              5,
              "L",
              "AC",
              "ACCU-1.1",
              null,
              2,
              "50/2",
              "6",
              3058,
              "C",
              6115,
              null
            ],
            [
              6,
              "R",
              "LGR",
              "ACCU-1.5",
              null,
              2,
              "50/2",
              "6",
              3058,
              "C",
              6115,
              null
            ],
            [
              7,
              "L",
              "AC",
              "ACCU-1.1",
              null,
              null,
              null,
              null,
              3058,
              "A",
              6115,
              5
            ],
            [
              8,
              "R",
              "LGR",
              "ACCU-1.5",
              null,
              null,
              null,
              null,
              3058,
              "A",
              6115,
              6
            ],
            [
              9,
              "L",
              "HTG",
              "AHU-1.2",
              null,
              2,
              "30/2",
              "10",
              3110,
              "B",
              5970,
              null
            ],
            [
              10,
              "R",
              "HTG",
              "AHU-1.6",
              null,
              2,
              "30/2",
              "10",
              2860,
              "B",
              5970,
              null
            ],
            [
              11,
              "L",
              "HTG",
              "AHU-1.2",
              null,
              null,
              null,
              null,
              3110,
              "C",
              5970,
              9
            ],
            [
              12,
              "R",
              "HTG",
              "AHU-1.6",
              null,
              null,
              null,
              null,
              2860,
              "C",
              5970,
              10
            ],
            [
              13,
              "L",
              "AC",
              "ACCU-1.2",
              null,
              2,
              "50/2",
              "6",
              3058,
              "A",
              5054,
              null
            ],
            [
              14,
              "R",
              "AC",
              "ACCU-1.6",
              null,
              2,
              "30/2",
              "10",
              1997,
              "A",
              5054,
              null
            ],
            [
              15,
              "L",
              "AC",
              "ACCU-1.2",
              null,
              null,
              null,
              null,
              3058,
              "B",
              5054,
              13
            ],
            [
              16,
              "R",
              "AC",
              "ACCU-1.6",
              null,
              null,
              null,
              null,
              1997,
              "B",
              5054,
              14
            ],
            [
              17,
              "L",
              "HTG",
              "AHU-1.3",
              null,
              2,
              "30/2",
              "10",
              2860,
              "C",
              6460,
              null
            ],
            [
              18,
              "R",
              "EVCS",
              "EV CHARGING STATION",
              null,
              2,
              "40/2",
              "8",
              3600,
              "C",
              6460,
              null
            ],
            [
              19,
              "L",
              "HTG",
              "AHU-1.3",
              null,
              null,
              null,
              null,
              2860,
              "A",
              6460,
              17
            ],
            [
              20,
              "R",
              "EVCS",
              "EV CHARGING STATION",
              null,
              null,
              null,
              null,
              3600,
              "A",
              6460,
              18
            ],
            [
              21,
              "L",
              "AC",
              "ACCU-1.3",
              null,
              2,
              "30/2",
              "10",
              1997,
              "B",
              5597,
              null
            ],
            [
              22,
              "R",
              "EVCS",
              "EV CHARGING STATION",
              null,
              2,
              "40/2",
              "8",
              3600,
              "B",
              5597,
              null
            ],
            [
              23,
              "L",
              "AC",
              "ACCU-1.3",
              null,
              null,
              null,
              null,
              1997,
              "C",
              5597,
              21
            ],
            [
              24,
              "R",
              "EVCS",
              "EV CHARGING STATION",
              null,
              null,
              null,
              null,
              3600,
              "C",
              5597,
              22
            ],
            [
              25,
              "L",
              "HTG",
              "AHU-1.4",
              null,
              2,
              "30/2",
              "10",
              2860,
              "A",
              5360,
              null
            ],
            [
              26,
              "R",
              "HTG",
              "EUH",
              null,
              2,
              "30/2",
              "10",
              2500,
              "A",
              5360,
              null
            ],
            [
              27,
              "L",
              "HTG",
              "AHU-1.4",
              null,
              null,
              null,
              null,
              2860,
              "B",
              5360,
              25
            ],
            [
              28,
              "R",
              "HTG",
              "EUH",
              null,
              null,
              null,
              null,
              2500,
              "B",
              5360,
              26
            ],
            [
              29,
              "L",
              "AC",
              "ACCU-1.4",
              null,
              2,
              "20/2",
              "12",
              1404,
              "C",
              1404,
              null
            ],
            [
              30,
              "R",
              null,
              "SPARE",
              null,
              1,
              "20/1",
              null,
              null,
              "C",
              1404,
              null
            ],
            [
              31,
              "L",
              "AC",
              "ACCU-1.4",
              null,
              null,
              null,
              null,
              1404,
              "A",
              1404,
              29
            ],
            [
              32,
              "R",
              null,
              "SPARE",
              null,
              1,
              "20/1",
              null,
              null,
              "A",
              1404,
              30
            ],
            [
              33,
              "L",
              "AC",
              "CU-1",
              null,
              2,
              "30/2",
              "10",
              1976,
              "B",
              1976,
              null
            ],
            [
              34,
              "R",
              null,
              "SPARE",
              null,
              1,
              "20/1",
              null,
              null,
              "B",
              1976,
              30
            ],
            [
              35,
              "L",
              "AC",
              "CU-1",
              null,
              null,
              null,
              null,
              1976,
              "C",
              1976,
              33
            ],
            [
              36,
              "R",
              null,
              "SPARE",
              null,
              1,
              "20/1",
              null,
              null,
              "C",
              1976,
              30
            ],
            [
              37,
              "L",
              "AC",
              "CU-2",
              null,
              2,
              "15/2",
              "12",
              1560,
              "A",
              1560,
              null
            ],
            [
              38,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "A",
              1560,
              null
            ],
            [
              39,
              "L",
              "AC",
              "CU-2",
              null,
              null,
              null,
              null,
              1560,
              "B",
              1560,
              37
            ],
            [
              40,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "B",
              1560,
              38
            ],
            [
              41,
              "L",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "C",
              0,
              null
            ],
            [
              42,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "C",
              0,
              38
            ]
          ],
          "loadCodes": {
            "LTG": {
              "connected": 0,
              "demand": 0,
              "formula": "125% LIGHTING LOAD (N/A)"
            },
            "REC": {
              "connected": 0,
              "demand": 0,
              "formula": "RCPTS LOAD (N/A)"
            },
            "EQUIP": {
              "connected": 0,
              "demand": 0,
              "formula": "EQUIPMENT LOAD (N/A)"
            },
            "AC": {
              "connected": 30098,
              "demand": 30098,
              "formula": "HVAC LOAD"
            },
            "HTG": {
              "connected": 40818,
              "demand": 40818,
              "formula": "HEATING LOAD"
            },
            "LGR": {
              "connected": 6115,
              "demand": 7644,
              "formula": "125% LARGEST MOTOR"
            },
            "KIT": {
              "connected": 0,
              "demand": 0,
              "formula": "KITCHEN LOAD (N/A)"
            },
            "SUB": {
              "connected": 0,
              "demand": 0,
              "formula": "SUB PANEL x PF (N/A)"
            },
            "GLTG": {
              "connected": 0,
              "demand": 0,
              "formula": "GUESTROOM LIGHTING LOAD (N/A)"
            },
            "EVCS": {
              "connected": 14400,
              "demand": 18000,
              "formula": "125% ELECTRIC VEHICLE CHARGING STATION"
            }
          },
          "totals": {
            "connectedVA": 91430,
            "connectedAmps": 254,
            "demandVA": 96559,
            "demandAmps": 268,
            "connectedPhaseKVA": {
              "A": 32.17,
              "B": 31.74,
              "C": 27.52
            },
            "connectedPhaseAmps": {
              "A": 268.11,
              "B": 264.47,
              "C": 229.35
            },
            "demandPhaseKVA": {
              "A": 33.84,
              "B": 32.64,
              "C": 30.09
            },
            "demandPhaseAmps": {
              "A": 281.98,
              "B": 271.97,
              "C": 250.72
            }
          },
          "notes": [
            "VERIFY HPs, BREAKER SIZES, CABLES SIZES FOR THE HVAC EQUIPMENT WITH THE MECHANICAL EQUIPMENT SCHEDULE PRIOR TO INSTALLATION.",
            "FIELD VERIFICATION BREAKER SIZES, CABLE SIZES, ETC WITH EV CHARGING SUPPLIER/MANUFACTURER PRIOR TO INSTALLATION"
          ]
        },
        {
          "id": "EP",
          "fedFrom": "MDP/GENSET VIA ATS",
          "header": {
            "voltage": "120/208V",
            "phase": 3,
            "wires": 4,
            "nema": "NEMA-1",
            "aic": "42 KA",
            "bus": "250 AMP COPPER",
            "mains": "250 AMP M.C.B.",
            "mounting": "SURFACE MOUNTED",
            "location": "ELECT. 1ST FLOOR"
          },
          "circuitPositionCount": 42,
          "rows": [
            [
              1,
              "L",
              "LTG",
              "LTS - ELEVATOR SHAFT #1",
              null,
              1,
              "20/1",
              "12",
              100,
              "A",
              8924,
              null
            ],
            [
              2,
              "R",
              "LGR",
              "ELEVATOR #1",
              "SHUNT-TRIP BREAKER",
              3,
              "125/3",
              "1",
              8824,
              "A",
              8924,
              null
            ],
            [
              3,
              "L",
              "REC",
              "RCPTS - ELEVATOR SHAFT #1",
              null,
              1,
              "20/1",
              "12",
              360,
              "B",
              9184,
              null
            ],
            [
              4,
              "R",
              "LGR",
              "ELEVATOR #1",
              "SHUNT-TRIP BREAKER",
              null,
              null,
              null,
              8824,
              "B",
              9184,
              2
            ],
            [
              5,
              "L",
              "EQUIP",
              "SUMP PUMP CONTROL PNL (SP-1)",
              "CLASS A GFCI BREAKER",
              1,
              "20/1",
              "12",
              441,
              "C",
              9265,
              null
            ],
            [
              6,
              "R",
              "LGR",
              "ELEVATOR #1",
              "SHUNT-TRIP BREAKER",
              null,
              null,
              null,
              8824,
              "C",
              9265,
              2
            ],
            [
              7,
              "L",
              "LTG",
              "LTS - ELEVATOR SHAFT #2",
              null,
              1,
              "20/1",
              "12",
              100,
              "A",
              8924,
              null
            ],
            [
              8,
              "R",
              "EQUIP",
              "ELEVATOR #2",
              "SHUNT-TRIP BREAKER",
              3,
              "125/3",
              "1",
              8824,
              "A",
              8924,
              null
            ],
            [
              9,
              "L",
              "REC",
              "RCPTS - ELEVATOR SHAFT #2",
              null,
              1,
              "20/1",
              "12",
              360,
              "B",
              9184,
              null
            ],
            [
              10,
              "R",
              "EQUIP",
              "ELEVATOR #2",
              "SHUNT-TRIP BREAKER",
              null,
              null,
              null,
              8824,
              "B",
              9184,
              8
            ],
            [
              11,
              "L",
              "EQUIP",
              "SUMP PUMP CONTROL PNL (SP-2)",
              "CLASS A GFCI BREAKER",
              1,
              "20/1",
              "12",
              441,
              "C",
              9265,
              null
            ],
            [
              12,
              "R",
              "EQUIP",
              "ELEVATOR #2",
              "SHUNT-TRIP BREAKER",
              null,
              null,
              null,
              8824,
              "C",
              9265,
              8
            ],
            [
              13,
              "L",
              null,
              "SPARE FOR EMERGENCY RADIO RESPONDERS COVERAGE 1ST FL.",
              null,
              1,
              "20/1",
              null,
              null,
              "A",
              0,
              null
            ],
            [
              14,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "A",
              0,
              null
            ],
            [
              15,
              "L",
              null,
              "SPARE FOR EMERGENCY RADIO RESPONDERS COVERAGE 2ND FL.",
              null,
              1,
              "20/1",
              null,
              null,
              "B",
              0,
              null
            ],
            [
              16,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "B",
              0,
              14
            ],
            [
              17,
              "L",
              null,
              "SPARE FOR EMERGENCY RADIO RESPONDERS COVERAGE 3RD FL.",
              null,
              1,
              "20/1",
              null,
              null,
              "C",
              0,
              null
            ],
            [
              18,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "C",
              0,
              14
            ],
            [
              19,
              "L",
              null,
              "SPARE FOR EMERGENCY RADIO RESPONDERS COVERAGE 4TH FL.",
              null,
              1,
              "20/1",
              null,
              null,
              "A",
              0,
              null
            ],
            [
              20,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "A",
              0,
              14
            ],
            [
              21,
              "L",
              "EQUIP",
              "FACP",
              "NOTE 1",
              1,
              "20/1",
              "12",
              1500,
              "B",
              1500,
              null
            ],
            [
              22,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "B",
              1500,
              14
            ],
            [
              23,
              "L",
              null,
              "SPARE",
              null,
              1,
              "20/1",
              null,
              null,
              "C",
              0,
              null
            ],
            [
              24,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "C",
              0,
              14
            ],
            [
              25,
              "L",
              null,
              "SPARE",
              null,
              1,
              "20/1",
              null,
              null,
              "A",
              0,
              23
            ],
            [
              26,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "A",
              0,
              14
            ],
            [
              27,
              "L",
              null,
              "SPARE",
              null,
              1,
              "20/1",
              null,
              null,
              "B",
              0,
              23
            ],
            [
              28,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "B",
              0,
              14
            ],
            [
              29,
              "L",
              null,
              "SPARE",
              null,
              1,
              "20/1",
              null,
              null,
              "C",
              0,
              23
            ],
            [
              30,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "C",
              0,
              14
            ],
            [
              31,
              "L",
              null,
              "SPARE",
              null,
              1,
              "20/1",
              null,
              null,
              "A",
              0,
              23
            ],
            [
              32,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "A",
              0,
              14
            ],
            [
              33,
              "L",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "B",
              0,
              null
            ],
            [
              34,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "B",
              0,
              14
            ],
            [
              35,
              "L",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "C",
              0,
              33
            ],
            [
              36,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "C",
              0,
              14
            ],
            [
              37,
              "L",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "A",
              0,
              33
            ],
            [
              38,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "A",
              0,
              14
            ],
            [
              39,
              "L",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "B",
              0,
              33
            ],
            [
              40,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "B",
              0,
              14
            ],
            [
              41,
              "L",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "C",
              0,
              33
            ],
            [
              42,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "C",
              0,
              14
            ]
          ],
          "loadCodes": {
            "LTG": {
              "connected": 200,
              "demand": 250,
              "formula": "125% LIGHTING LOAD"
            },
            "REC": {
              "connected": 720,
              "demand": 720,
              "formula": "RCPTS LOAD (100% FIRST 10KVA +50% REMAIN)"
            },
            "EQUIP": {
              "connected": 28853,
              "demand": 28853,
              "formula": "EQUIPMENT LOAD"
            },
            "AC": {
              "connected": 0,
              "demand": 0,
              "formula": "HVAC LOAD (N/A)"
            },
            "HTG": {
              "connected": 0,
              "demand": 0,
              "formula": "HEATING LOAD (N/A)"
            },
            "LGR": {
              "connected": 26471,
              "demand": 33088,
              "formula": "125% LARGEST MOTOR"
            },
            "KIT": {
              "connected": 0,
              "demand": 0,
              "formula": "KITCHEN LOAD (N/A)"
            },
            "SUB": {
              "connected": 0,
              "demand": 0,
              "formula": "SUB PANEL x PF (N/A)"
            },
            "GLTG": {
              "connected": 0,
              "demand": 0,
              "formula": "GUESTROOM LIGHTING LOAD (N/A)"
            },
            "EVCS": {
              "connected": 0,
              "demand": 0,
              "formula": "125% ELECTRIC VEHICLE CHARGING STATION (N/A)"
            }
          },
          "totals": {
            "connectedVA": 56244,
            "connectedAmps": 156,
            "demandVA": 62911,
            "demandAmps": 175,
            "connectedPhaseKVA": {
              "A": 17.85,
              "B": 19.87,
              "C": 18.53
            },
            "connectedPhaseAmps": {
              "A": 148.73,
              "B": 165.56,
              "C": 154.41
            },
            "demandPhaseKVA": {
              "A": 20.1,
              "B": 22.07,
              "C": 20.74
            },
            "demandPhaseAmps": {
              "A": 167.52,
              "B": 183.94,
              "C": 172.79
            }
          },
          "notes": [
            "PROVIDE FIRE ALARM CIRCUIT BREAKER WITH RED MARKING PER NEC REQUIREMENTS.",
            "VERIFY HPs, BREAKER SIZES, ETC FOR ELEVATOR WITH ELEVATOR MANUFACTURER & CODE REQUIREMENTS PRIOR TO PLACING ORDERS/INSTALLATION.",
            "THE BREAKER WILL BE SHUT OFF WHEN A FIRE OCCURS VIA THE SIGNAL FROM FACP."
          ]
        },
        {
          "id": "PP",
          "fedFrom": "MDP",
          "header": {
            "voltage": "120/208V",
            "phase": 3,
            "wires": 4,
            "nema": "NEMA-3R",
            "aic": "30 KA",
            "bus": "150 AMP COPPER",
            "mains": "150 AMP M.L.O.",
            "mounting": "SURFACE MOUNTED",
            "location": "FOOD PREP. 1ST FLOOR"
          },
          "circuitPositionCount": 42,
          "rows": [
            [
              1,
              "L",
              "EQUIP",
              "(01) - MOBILE REACH-IN FREEZER",
              "GFCI BREAKER",
              1,
              "20/1",
              "12",
              1152,
              "A",
              2880,
              null
            ],
            [
              2,
              "R",
              "EQUIP",
              "(26) - CONVEYOR TOASTER",
              null,
              1,
              "20/1",
              "12",
              1728,
              "A",
              2880,
              null
            ],
            [
              3,
              "L",
              "EQUIP",
              "(02) - MOBILE REACH-IN REF.",
              "GFCI BREAKER",
              1,
              "20/1",
              "12",
              648,
              "B",
              2448,
              null
            ],
            [
              4,
              "R",
              "EQUIP",
              "(27) - DISPLAY SHOWCASE",
              null,
              1,
              "20/1",
              "12",
              1800,
              "B",
              2448,
              null
            ],
            [
              5,
              "L",
              "EQUIP",
              "(02) - MOBILE REACH-IN REF.",
              "GFCI BREAKER",
              1,
              "20/1",
              "12",
              648,
              "C",
              1368,
              null
            ],
            [
              6,
              "R",
              "EQUIP",
              "(28) - JUICE DISPENSER",
              null,
              1,
              "20/1",
              "12",
              720,
              "C",
              1368,
              null
            ],
            [
              7,
              "L",
              "EQUIP",
              "(05) - UNDERCOUNTER DISHMACHINE",
              "GFCI BREAKER",
              3,
              "40/3",
              "8",
              3483,
              "A",
              4287,
              null
            ],
            [
              8,
              "R",
              "EQUIP",
              "(29) - WARMING KETTLE",
              null,
              1,
              "20/1",
              "12",
              804,
              "A",
              4287,
              null
            ],
            [
              9,
              "L",
              "EQUIP",
              "(05) - UNDERCOUNTER DISHMACHINE",
              "GFCI BREAKER",
              null,
              null,
              null,
              3483,
              "B",
              3651,
              7
            ],
            [
              10,
              "R",
              "EQUIP",
              "(34) - YOGURT DISPENSER",
              null,
              1,
              "20/1",
              "12",
              168,
              "B",
              3651,
              null
            ],
            [
              11,
              "L",
              "EQUIP",
              "(05) - UNDERCOUNTER DISHMACHINE",
              "GFCI BREAKER",
              null,
              null,
              null,
              3483,
              "C",
              4983,
              7
            ],
            [
              12,
              "R",
              "EQUIP",
              "(E901) - CONVENIENCE",
              null,
              1,
              "20/1",
              "12",
              1500,
              "C",
              4983,
              null
            ],
            [
              13,
              "L",
              "EQUIP",
              "(14) - COFFEE MAKER",
              null,
              2,
              "30/2",
              "10",
              2340,
              "A",
              2715,
              null
            ],
            [
              14,
              "R",
              "EQUIP",
              "DISPOSER",
              null,
              1,
              "20/1",
              "12",
              375,
              "A",
              2715,
              null
            ],
            [
              15,
              "L",
              "EQUIP",
              "(14) - COFFEE MAKER",
              null,
              null,
              null,
              null,
              2340,
              "B",
              2880,
              13
            ],
            [
              16,
              "R",
              "REC",
              "RCPTS - KITCHEN",
              null,
              1,
              "20/1",
              "12",
              540,
              "B",
              2880,
              null
            ],
            [
              17,
              "L",
              "EQUIP",
              "(16) - CONVECTION OVEN",
              null,
              2,
              "35/2",
              "8",
              2891,
              "C",
              2891,
              null
            ],
            [
              18,
              "R",
              null,
              "SPARE",
              null,
              1,
              "20/1",
              null,
              null,
              "C",
              2891,
              null
            ],
            [
              19,
              "L",
              "EQUIP",
              "(16) - CONVECTION OVEN",
              null,
              null,
              null,
              null,
              2891,
              "A",
              2891,
              17
            ],
            [
              20,
              "R",
              null,
              "SPARE",
              null,
              1,
              "20/1",
              null,
              null,
              "A",
              2891,
              18
            ],
            [
              21,
              "L",
              "EQUIP",
              "(18) - MOBILE REACH-IN FREEZER",
              "GFCI BREAKER",
              1,
              "20/1",
              "12",
              864,
              "B",
              864,
              null
            ],
            [
              22,
              "R",
              null,
              "SPARE",
              null,
              1,
              "20/1",
              null,
              null,
              "B",
              864,
              18
            ],
            [
              23,
              "L",
              "EQUIP",
              "(20) - CONVECTION OVEN",
              null,
              2,
              "35/2",
              "8",
              2891,
              "C",
              2891,
              null
            ],
            [
              24,
              "R",
              null,
              "SPARE",
              null,
              1,
              "20/1",
              null,
              null,
              "C",
              2891,
              18
            ],
            [
              25,
              "L",
              "EQUIP",
              "(20) - CONVECTION OVEN",
              null,
              null,
              null,
              null,
              2891,
              "A",
              2891,
              23
            ],
            [
              26,
              "R",
              null,
              "SPARE",
              null,
              1,
              "20/1",
              null,
              null,
              "A",
              2891,
              18
            ],
            [
              27,
              "L",
              "EQUIP",
              "(22) - MICROWAVE OVEN",
              null,
              1,
              "20/1",
              "12",
              2016,
              "B",
              2016,
              null
            ],
            [
              28,
              "R",
              null,
              "SPARE",
              null,
              1,
              "20/1",
              null,
              null,
              "B",
              2016,
              18
            ],
            [
              29,
              "L",
              "EQUIP",
              "(24) - WAFFLE MAKER",
              null,
              1,
              "20/1",
              "12",
              1560,
              "C",
              1560,
              null
            ],
            [
              30,
              "R",
              null,
              "SPARE",
              null,
              1,
              "20/1",
              null,
              null,
              "C",
              1560,
              18
            ],
            [
              31,
              "L",
              "EQUIP",
              "(25) - WAFFLE MAKER",
              null,
              1,
              "20/1",
              "12",
              1560,
              "A",
              1560,
              null
            ],
            [
              32,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "A",
              1560,
              null
            ],
            [
              33,
              "L",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "B",
              0,
              null
            ],
            [
              34,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "B",
              0,
              32
            ],
            [
              35,
              "L",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "C",
              0,
              33
            ],
            [
              36,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "C",
              0,
              32
            ],
            [
              37,
              "L",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "A",
              0,
              33
            ],
            [
              38,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "A",
              0,
              32
            ],
            [
              39,
              "L",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "B",
              0,
              33
            ],
            [
              40,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "B",
              0,
              32
            ],
            [
              41,
              "L",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "C",
              0,
              33
            ],
            [
              42,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "C",
              0,
              32
            ]
          ],
          "loadCodes": {
            "LTG": {
              "connected": 0,
              "demand": 0,
              "formula": "125% LIGHTING LOAD (N/A)"
            },
            "REC": {
              "connected": 540,
              "demand": 540,
              "formula": "RCPTS LOAD (100% FIRST 10KVA +50% REMAIN)"
            },
            "EQUIP": {
              "connected": 42236,
              "demand": 42236,
              "formula": "EQUIPMENT LOAD"
            },
            "AC": {
              "connected": 0,
              "demand": 0,
              "formula": "HVAC LOAD (N/A)"
            },
            "HTG": {
              "connected": 0,
              "demand": 0,
              "formula": "HEATING LOAD (N/A)"
            },
            "LGR": {
              "connected": 0,
              "demand": 0,
              "formula": "125% LARGEST MOTOR (N/A)"
            },
            "KIT": {
              "connected": 0,
              "demand": 0,
              "formula": "KITCHEN LOAD (N/A)"
            },
            "SUB": {
              "connected": 0,
              "demand": 0,
              "formula": "SUB PANEL x PF (N/A)"
            },
            "GLTG": {
              "connected": 0,
              "demand": 0,
              "formula": "GUESTROOM LIGHTING LOAD (N/A)"
            },
            "EVCS": {
              "connected": 0,
              "demand": 0,
              "formula": "125% ELECTRIC VEHICLE CHARGING STATION (N/A)"
            }
          },
          "totals": {
            "connectedVA": 42776,
            "connectedAmps": 119,
            "demandVA": 42776,
            "demandAmps": 119,
            "connectedPhaseKVA": {
              "A": 17.22,
              "B": 11.86,
              "C": 13.69
            },
            "connectedPhaseAmps": {
              "A": 143.53,
              "B": 98.82,
              "C": 114.11
            },
            "demandPhaseKVA": {
              "A": 17.22,
              "B": 11.86,
              "C": 13.69
            },
            "demandPhaseAmps": {
              "A": 143.53,
              "B": 98.82,
              "C": 114.11
            }
          },
          "notes": [
            "FIELD VERIFICATION BREAKER SIZES, CABLE SIZES, ETC WITH KITCHEN SUPPLIER PRIOR TO INSTALLATION"
          ]
        },
        {
          "id": "GENSET PANEL (BUILT-IN)",
          "fedFrom": null,
          "header": {
            "voltage": "120/208V",
            "phase": 3,
            "wires": 4,
            "nema": "NEMA-3R",
            "aic": "42 KA",
            "bus": "500 AMP COPPER",
            "mains": "500 AMP M.C.B.",
            "mounting": "SURFACE MOUNTED",
            "location": "OUTDOOR"
          },
          "circuitPositionCount": 6,
          "rows": [
            [
              1,
              "L",
              "EQUIP",
              "FIRE PUMP CONTROL PANEL",
              "NOTE 2",
              3,
              "300/3",
              "400",
              22059,
              "A",
              42162,
              null
            ],
            [
              2,
              "R",
              "SUB",
              "PANEL EP",
              null,
              3,
              "250/3",
              "300",
              20103,
              "A",
              42162,
              null
            ],
            [
              3,
              "L",
              "EQUIP",
              "FIRE PUMP CONTROL PANEL",
              "NOTE 2",
              null,
              null,
              null,
              22059,
              "B",
              44132,
              1
            ],
            [
              4,
              "R",
              "SUB",
              "PANEL EP",
              null,
              null,
              null,
              null,
              22073,
              "B",
              44132,
              2
            ],
            [
              5,
              "L",
              "EQUIP",
              "FIRE PUMP CONTROL PANEL",
              "NOTE 2",
              null,
              null,
              null,
              22059,
              "C",
              42794,
              1
            ],
            [
              6,
              "R",
              "SUB",
              "PANEL EP",
              null,
              null,
              null,
              null,
              20735,
              "C",
              42794,
              2
            ]
          ],
          "generatorCalculation": {
            "standard": "NEC ART. 220",
            "columns": [
              "category",
              "connectedKVA",
              "factor",
              "sizingKVA"
            ],
            "fireMode": [
              [
                "1.1 - LARGEST MOTOR (FP) 75HP (66.2KVA) @125%",
                66.2,
                1.25,
                82.7
              ],
              [
                "1.2 - MISC. ALARM, ETC. @100%",
                1.5,
                1,
                1.5
              ],
              [
                "1.3 - ELEVATOR (2@30HP (26.4KVA)) @100%",
                52.8,
                1,
                52.8
              ],
              [
                "1.4 - LIGHTING (ELEV. PIT #1,2) @125%",
                0.2,
                1.25,
                0.3
              ],
              [
                "1.5 - RECEPTACLES (ELEV. #1,2) @100%",
                0.7,
                1,
                0.7
              ],
              [
                "1.6 - SUMP PUMP @100%",
                0.9,
                1,
                0.9
              ]
            ],
            "fireModeTotalKVA": 138.9,
            "operationalMode": [
              [
                "2.1 - MISC. ALARM, ETC. @100%",
                1.5,
                1,
                1.5
              ],
              [
                "2.2 - ELEVATOR (1@30HP (26.4KVA) @100% & 1@30HP (26.4KVA) @125%)",
                52.8,
                "1 & 1.25",
                59.4
              ],
              [
                "2.3 - LIGHTING (ELEV. PIT #1,2) @125%",
                0.2,
                1.25,
                0.3
              ],
              [
                "2.4 - RECEPTACLES (ELEV. #1,2) @100%",
                0.7,
                1,
                0.7
              ],
              [
                "2.5 - SUMP PUMP @100%",
                0.9,
                1,
                0.9
              ]
            ],
            "operationalModeTotalKVA": 62.8,
            "usedDemandKVA": 138.9,
            "selectionKVA": 163
          },
          "notes": [
            "ELECTRICAL CONTRACTOR SHALL VERIFY HPs, CABLE SIZES, BREAKER LUGS, DS, ETC OF FIRE PUMPS WITH FIRE CONTRACTOR PRIOR TO INSTALLATION."
          ]
        },
        {
          "id": "SP",
          "fedFrom": "MDP",
          "header": {
            "voltage": "120/208V",
            "phase": 3,
            "wires": 4,
            "nema": "NEMA-4X",
            "aic": "10 KA",
            "bus": "100 AMP COPPER",
            "mains": "100 AMP M.L.O.",
            "mounting": "SURFACE MOUNTED",
            "location": "POOL EQUIP. RM"
          },
          "circuitPositionCount": 24,
          "rows": [
            [
              1,
              "L",
              "LTG",
              "LTS - SWIMMING POOL",
              "GFCI BREAKER, NOTE 1",
              1,
              "20/1",
              "12",
              100,
              "A",
              600,
              null
            ],
            [
              2,
              "R",
              "LTG",
              "LTS - POOL EQUIP RM",
              "GFCI BREAKER",
              1,
              "20/1",
              "12",
              500,
              "A",
              600,
              null
            ],
            [
              3,
              "L",
              "EQUIP",
              "POOL PUMP #1",
              "GFCI BREAKER",
              2,
              "20/2",
              "12",
              1500,
              "B",
              1860,
              null
            ],
            [
              4,
              "R",
              "REC",
              "RCPTS - POOL EQUIP RM",
              null,
              1,
              "20/1",
              "12",
              360,
              "B",
              1860,
              null
            ],
            [
              5,
              "L",
              "EQUIP",
              "POOL PUMP #1",
              "GFCI BREAKER",
              null,
              null,
              null,
              1500,
              "C",
              2940,
              3
            ],
            [
              6,
              "R",
              "REC",
              "RCPTS - POOL AREA",
              null,
              1,
              "20/1",
              "12",
              1440,
              "C",
              2940,
              null
            ],
            [
              7,
              "L",
              "EQUIP",
              "POOL PUMP #2",
              "GFCI BREAKER",
              2,
              "25/2",
              "10",
              1800,
              "A",
              2800,
              null
            ],
            [
              8,
              "R",
              "EQUIP",
              "POOL LIFT STATION",
              "GFCI BREAKER",
              1,
              "20/1",
              "12",
              1000,
              "A",
              2800,
              null
            ],
            [
              9,
              "L",
              "EQUIP",
              "POOL PUMP #2",
              "GFCI BREAKER",
              null,
              null,
              null,
              1800,
              "B",
              1800,
              7
            ],
            [
              10,
              "R",
              null,
              "SPARE",
              null,
              1,
              "20/1",
              null,
              null,
              "B",
              1800,
              null
            ],
            [
              11,
              "L",
              "LTG",
              "LTS - SWIMMING POOL AREA",
              "GFCI BREAKER, NOTE 1",
              1,
              "20/1",
              "12",
              500,
              "C",
              2000,
              null
            ],
            [
              12,
              "R",
              "EQUIP",
              "DRINKING FOUNTAIN",
              "CLASS A GFCI BREAKER",
              1,
              "20/1",
              "12",
              1500,
              "C",
              2000,
              null
            ],
            [
              13,
              "L",
              null,
              "SPARE",
              "GFCI BREAKER",
              1,
              "20/1",
              null,
              null,
              "A",
              0,
              null
            ],
            [
              14,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "A",
              0,
              null
            ],
            [
              15,
              "L",
              null,
              "SPARE",
              "GFCI BREAKER",
              1,
              "20/1",
              null,
              null,
              "B",
              0,
              null
            ],
            [
              16,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "B",
              0,
              14
            ],
            [
              17,
              "L",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "C",
              0,
              null
            ],
            [
              18,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "C",
              0,
              14
            ],
            [
              19,
              "L",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "A",
              0,
              17
            ],
            [
              20,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "A",
              0,
              14
            ],
            [
              21,
              "L",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "B",
              0,
              17
            ],
            [
              22,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "B",
              0,
              14
            ],
            [
              23,
              "L",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "C",
              0,
              17
            ],
            [
              24,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "C",
              0,
              14
            ]
          ],
          "loadCodes": {
            "LTG": {
              "connected": 1100,
              "demand": 1375,
              "formula": "125% LIGHTING LOAD"
            },
            "REC": {
              "connected": 1800,
              "demand": 1800,
              "formula": "RCPTS LOAD (100% FIRST 10KVA +50% REMAIN)"
            },
            "EQUIP": {
              "connected": 9100,
              "demand": 9100,
              "formula": "EQUIPMENT LOAD"
            },
            "AC": {
              "connected": 0,
              "demand": 0,
              "formula": "HVAC LOAD (N/A)"
            },
            "HTG": {
              "connected": 0,
              "demand": 0,
              "formula": "HEATING LOAD (N/A)"
            },
            "LGR": {
              "connected": 0,
              "demand": 0,
              "formula": "125% LARGEST MOTOR (N/A)"
            },
            "KIT": {
              "connected": 0,
              "demand": 0,
              "formula": "KITCHEN LOAD (N/A)"
            },
            "SUB": {
              "connected": 0,
              "demand": 0,
              "formula": "SUB PANEL x PF (N/A)"
            },
            "GLTG": {
              "connected": 0,
              "demand": 0,
              "formula": "GUESTROOM LIGHTING LOAD: N/A"
            },
            "EVCS": {
              "connected": 0,
              "demand": 0,
              "formula": "125% ELECTRIC VEHICLE CHARGING STATION (N/A)"
            }
          },
          "totals": {
            "connectedVA": 12000,
            "connectedAmps": 33,
            "demandVA": 12275,
            "demandAmps": 34,
            "connectedPhaseKVA": {
              "A": 3.4,
              "B": 3.66,
              "C": 4.94
            },
            "connectedPhaseAmps": {
              "A": 28.33,
              "B": 30.5,
              "C": 41.17
            },
            "demandPhaseKVA": {
              "A": 3.55,
              "B": 3.66,
              "C": 5.07
            },
            "demandPhaseAmps": {
              "A": 29.58,
              "B": 30.5,
              "C": 42.21
            }
          },
          "notes": [
            "CONTROLLED BY A 20A, 1P, TIME CLOCK WITH 4 HR BATTERIES.",
            "FIELD VERIFICATION BREAKER SIZES, CABLE SIZES, ETC WITH POOL CONTRACTOR PRIOR TO INSTALLATION.",
            "BREAKERS AND BRANCH CIRCUITS WILL BE INSTALLED UNDER THE POOL PERMIT AND THIS PERMIT COVERS ONLY THE INSTALLATION OF THE PANEL AND GROUND."
          ]
        },
        {
          "id": "MDP",
          "fedFrom": "SERVICE TRANSFORMER",
          "header": {
            "voltage": "120/208V",
            "phase": 3,
            "wires": 4,
            "nema": "NEMA-1",
            "aic": "65 KA",
            "bus": "2500 AMP COPPER",
            "mains": "2500 AMP M.C.B.",
            "mounting": "FLOOR MOUNTED",
            "location": "ELECT. 1ST FLOOR"
          },
          "circuitPositionCount": 66,
          "rows": [
            [
              1,
              "L",
              "SUB",
              "PANEL L5.A",
              "5TH FLOOR",
              3,
              "250/3",
              "300",
              22947,
              "A",
              42654,
              null
            ],
            [
              2,
              "R",
              "SUB",
              "PANEL L1.A",
              "1ST FLOOR",
              3,
              "225/3",
              "4/0",
              19707,
              "A",
              42654,
              null
            ],
            [
              3,
              "L",
              "SUB",
              "PANEL L5.A",
              "5TH FLOOR",
              null,
              null,
              null,
              22947,
              "B",
              42654,
              1
            ],
            [
              4,
              "R",
              "SUB",
              "PANEL L1.A",
              "1ST FLOOR",
              null,
              null,
              null,
              19707,
              "B",
              42654,
              2
            ],
            [
              5,
              "L",
              "SUB",
              "PANEL L5.A",
              "5TH FLOOR",
              null,
              null,
              null,
              22947,
              "C",
              42654,
              1
            ],
            [
              6,
              "R",
              "SUB",
              "PANEL L1.A",
              "1ST FLOOR",
              null,
              null,
              null,
              19707,
              "C",
              42654,
              2
            ],
            [
              7,
              "L",
              "SUB",
              "PANEL L5.B",
              "5TH FLOOR",
              3,
              "250/3",
              "300",
              21603,
              "A",
              26431,
              null
            ],
            [
              8,
              "R",
              "SUB",
              "PANEL L1.B",
              "1ST FLOOR",
              3,
              "100/3",
              "1",
              4828,
              "A",
              26431,
              null
            ],
            [
              9,
              "L",
              "SUB",
              "PANEL L5.B",
              "5TH FLOOR",
              null,
              null,
              null,
              21603,
              "B",
              28197,
              7
            ],
            [
              10,
              "R",
              "SUB",
              "PANEL L1.B",
              "1ST FLOOR",
              null,
              null,
              null,
              6593,
              "B",
              28197,
              8
            ],
            [
              11,
              "L",
              "SUB",
              "PANEL L5.B",
              "5TH FLOOR",
              null,
              null,
              null,
              21603,
              "C",
              26360,
              7
            ],
            [
              12,
              "R",
              "SUB",
              "PANEL L1.B",
              "1ST FLOOR",
              null,
              null,
              null,
              4757,
              "C",
              26360,
              8
            ],
            [
              13,
              "L",
              "SUB",
              "PANEL L4.A",
              "4TH FLOOR",
              3,
              "250/3",
              "300",
              22750,
              "A",
              39467,
              null
            ],
            [
              14,
              "R",
              "SUB",
              "PANEL L1.C",
              "1ST FLOOR",
              3,
              "200/3",
              "4/0",
              16717,
              "A",
              39467,
              null
            ],
            [
              15,
              "L",
              "SUB",
              "PANEL L4.A",
              "4TH FLOOR",
              null,
              null,
              null,
              22750,
              "B",
              40751,
              13
            ],
            [
              16,
              "R",
              "SUB",
              "PANEL L1.C",
              "1ST FLOOR",
              null,
              null,
              null,
              18001,
              "B",
              40751,
              14
            ],
            [
              17,
              "L",
              "SUB",
              "PANEL L4.A",
              "4TH FLOOR",
              null,
              null,
              null,
              22750,
              "C",
              40587,
              13
            ],
            [
              18,
              "R",
              "SUB",
              "PANEL L1.C",
              "1ST FLOOR",
              null,
              null,
              null,
              17837,
              "C",
              40587,
              14
            ],
            [
              19,
              "L",
              "SUB",
              "PANEL L4.B",
              "4TH FLOOR",
              3,
              "250/3",
              "300",
              21603,
              "A",
              38781,
              null
            ],
            [
              20,
              "R",
              "SUB",
              "PANEL L1.D",
              "1ST FLOOR",
              3,
              "200/3",
              "4/0",
              17178,
              "A",
              38781,
              null
            ],
            [
              21,
              "L",
              "SUB",
              "PANEL L4.B",
              "4TH FLOOR",
              null,
              null,
              null,
              21603,
              "B",
              38298,
              19
            ],
            [
              22,
              "R",
              "SUB",
              "PANEL L1.D",
              "1ST FLOOR",
              null,
              null,
              null,
              16695,
              "B",
              38298,
              20
            ],
            [
              23,
              "L",
              "SUB",
              "PANEL L4.B",
              "4TH FLOOR",
              null,
              null,
              null,
              21603,
              "C",
              37370,
              19
            ],
            [
              24,
              "R",
              "SUB",
              "PANEL L1.D",
              "1ST FLOOR",
              null,
              null,
              null,
              15766,
              "C",
              37370,
              20
            ],
            [
              25,
              "L",
              "SUB",
              "PANEL L3.A",
              "3RD FLOOR",
              3,
              "250/3",
              "300",
              22897,
              "A",
              56735,
              null
            ],
            [
              26,
              "R",
              "SUB",
              "PANEL L1.E",
              "1ST FLOOR",
              3,
              "400/3",
              "600",
              33837,
              "A",
              56735,
              null
            ],
            [
              27,
              "L",
              "SUB",
              "PANEL L3.A",
              "3RD FLOOR",
              null,
              null,
              null,
              22897,
              "B",
              55533,
              25
            ],
            [
              28,
              "R",
              "SUB",
              "PANEL L1.E",
              "1ST FLOOR",
              null,
              null,
              null,
              32636,
              "B",
              55533,
              26
            ],
            [
              29,
              "L",
              "SUB",
              "PANEL L3.A",
              "3RD FLOOR",
              null,
              null,
              null,
              22897,
              "C",
              52983,
              25
            ],
            [
              30,
              "R",
              "SUB",
              "PANEL L1.E",
              "1ST FLOOR",
              null,
              null,
              null,
              30086,
              "C",
              52983,
              26
            ],
            [
              31,
              "L",
              "SUB",
              "PANEL L3.B",
              "3RD FLOOR",
              3,
              "250/3",
              "300",
              21603,
              "A",
              38827,
              null
            ],
            [
              32,
              "R",
              "SUB",
              "PANEL PP",
              "1ST FLOOR",
              3,
              "150/3",
              "2/0",
              17224,
              "A",
              38827,
              null
            ],
            [
              33,
              "L",
              "SUB",
              "PANEL L3.B",
              "3RD FLOOR",
              null,
              null,
              null,
              21603,
              "B",
              33462,
              31
            ],
            [
              34,
              "R",
              "SUB",
              "PANEL PP",
              "1ST FLOOR",
              null,
              null,
              null,
              11859,
              "B",
              33462,
              32
            ],
            [
              35,
              "L",
              "SUB",
              "PANEL L3.B",
              "3RD FLOOR",
              null,
              null,
              null,
              21603,
              "C",
              35296,
              31
            ],
            [
              36,
              "R",
              "SUB",
              "PANEL PP",
              "1ST FLOOR",
              null,
              null,
              null,
              13693,
              "C",
              35296,
              32
            ],
            [
              37,
              "L",
              "SUB",
              "PANEL L2.A",
              "3RD FLOOR",
              3,
              "250/3",
              "300",
              22750,
              "A",
              26300,
              null
            ],
            [
              38,
              "R",
              "SUB",
              "PANEL SP",
              "1ST FLOOR",
              3,
              "100/3",
              "1",
              3550,
              "A",
              26300,
              null
            ],
            [
              39,
              "L",
              "SUB",
              "PANEL L2.A",
              "3RD FLOOR",
              null,
              null,
              null,
              22750,
              "B",
              26410,
              37
            ],
            [
              40,
              "R",
              "SUB",
              "PANEL SP",
              "1ST FLOOR",
              null,
              null,
              null,
              3660,
              "B",
              26410,
              38
            ],
            [
              41,
              "L",
              "SUB",
              "PANEL L2.A",
              "3RD FLOOR",
              null,
              null,
              null,
              22750,
              "C",
              27815,
              37
            ],
            [
              42,
              "R",
              "SUB",
              "PANEL SP",
              "1ST FLOOR",
              null,
              null,
              null,
              5065,
              "C",
              27815,
              38
            ],
            [
              43,
              "L",
              "SUB",
              "PANEL L2.B",
              "3RD FLOOR",
              3,
              "250/3",
              "300",
              21603,
              "A",
              36614,
              null
            ],
            [
              44,
              "R",
              "LGR",
              "DOAS-1",
              "ROOF",
              3,
              "150/3",
              "2/0",
              15011,
              "A",
              36614,
              null
            ],
            [
              45,
              "L",
              "SUB",
              "PANEL L2.B",
              "3RD FLOOR",
              null,
              null,
              null,
              21603,
              "B",
              36614,
              43
            ],
            [
              46,
              "R",
              "LGR",
              "DOAS-1",
              "ROOF",
              null,
              null,
              null,
              15011,
              "B",
              36614,
              44
            ],
            [
              47,
              "L",
              "SUB",
              "PANEL L2.B",
              "3RD FLOOR",
              null,
              null,
              null,
              21603,
              "C",
              36614,
              43
            ],
            [
              48,
              "R",
              "LGR",
              "DOAS-1",
              "ROOF",
              null,
              null,
              null,
              15011,
              "C",
              36614,
              44
            ],
            [
              49,
              "L",
              "EQUIP",
              "SURGE PROTECTIVE DEVICE IN \"MDP\"",
              null,
              3,
              "60/3",
              "6",
              null,
              "A",
              15011,
              null
            ],
            [
              50,
              "R",
              "AC",
              "DOAS-2",
              "ROOF",
              3,
              "150/3",
              "2/0",
              15011,
              "A",
              15011,
              null
            ],
            [
              51,
              "L",
              "EQUIP",
              "SURGE PROTECTIVE DEVICE IN \"MDP\"",
              null,
              null,
              null,
              null,
              null,
              "B",
              15011,
              49
            ],
            [
              52,
              "R",
              "AC",
              "DOAS-2",
              "ROOF",
              null,
              null,
              null,
              15011,
              "B",
              15011,
              50
            ],
            [
              53,
              "L",
              "EQUIP",
              "SURGE PROTECTIVE DEVICE IN \"MDP\"",
              null,
              null,
              null,
              null,
              null,
              "C",
              15011,
              49
            ],
            [
              54,
              "R",
              "AC",
              "DOAS-2",
              "ROOF",
              null,
              null,
              null,
              15011,
              "C",
              15011,
              50
            ],
            [
              55,
              "L",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "A",
              20103,
              null
            ],
            [
              56,
              "R",
              "SUB",
              "PANEL EP",
              null,
              3,
              "250/3",
              "300",
              20103,
              "A",
              20103,
              null
            ],
            [
              57,
              "L",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "B",
              22073,
              55
            ],
            [
              58,
              "R",
              "SUB",
              "PANEL EP",
              null,
              null,
              null,
              null,
              22073,
              "B",
              22073,
              56
            ],
            [
              59,
              "L",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "C",
              20735,
              55
            ],
            [
              60,
              "R",
              "SUB",
              "PANEL EP",
              null,
              null,
              null,
              null,
              20735,
              "C",
              20735,
              56
            ],
            [
              61,
              "L",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "A",
              0,
              55
            ],
            [
              62,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "A",
              0,
              null
            ],
            [
              63,
              "L",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "B",
              0,
              55
            ],
            [
              64,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "B",
              0,
              62
            ],
            [
              65,
              "L",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "C",
              0,
              55
            ],
            [
              66,
              "R",
              null,
              "SPACE ONLY",
              null,
              null,
              null,
              null,
              null,
              "C",
              0,
              62
            ]
          ],
          "feederCalculation": {
            "standard": "NEC ART. 220",
            "columns": [
              "category",
              "connectedLoadKVA",
              "feederSizingFactor",
              "feederSizingLoadKVA"
            ],
            "rows": [
              [
                "1 - GENERAL LIGHTING",
                23.0,
                1.25,
                28.8
              ],
              [
                "2 - KITCHENETTE GUEST ROOMS UNIT LOADS",
                1475.9,
                0.23,
                339.5
              ],
              [
                "3 - HOUSE LOAD",
                null,
                null,
                null
              ],
              [
                "3.1 - DRYER 2@1.5KVA & 2@5KVA",
                13.0,
                1,
                13.0
              ],
              [
                "3.2 - WASHER 2@7.1KVA & 1@2.1KVA",
                18.4,
                1,
                18.4
              ],
              [
                "3.3 - VENDING/ICE MACHINES: 5@1.5KVA",
                7.5,
                1,
                7.5
              ],
              [
                "3.4 - SERVICE EQUIPMENT",
                82.0,
                0.65,
                53.3
              ],
              [
                "3.5 - ELECTRIC CHARGING STATION: 2 @ 7.2KVA @125%",
                14.4,
                1.25,
                18.0
              ],
              [
                "3.6 - MISCELLANEOUS (FIRE ALARM, DOOR MOTOR, ELV, ETC..)",
                15.0,
                1,
                15.0
              ],
              [
                "4 - RECEPTACLES",
                29.7,
                "First 10KVA+50%",
                19.9
              ],
              [
                "5 - MECHANICAL LOAD",
                null,
                null,
                null
              ],
              [
                "5.1 - AHU'S (HEATING)/COOLING EUHS",
                137.9,
                1,
                137.9
              ],
              [
                "5.2 - ELEVATOR: 1 @ 30HP (26.4KVA) @ 100%",
                52.8,
                1,
                52.8
              ],
              [
                "5.3 - PUMPS",
                18.3,
                1,
                18.3
              ],
              [
                "5.4 - LARGEST MOTOR ELEVATOR: 1 @ 30HP (26.4KVA) @ 125%",
                45.0,
                1.25,
                56.3
              ]
            ],
            "feederSizingLoadKVA": 779,
            "feederSizingLoadAmps": 2161
          },
          "notes": [
            "SWITCHBOARD IS \"FULLY\" RATED TO INCLUDE 65K AIC BREAKER.",
            "SEE ONE-LINE DIAGRAM FOR COMPLETE FEEDER SIZES.",
            "FIELD VERIFICATION HP PRIOR TO INSTALLING BRKR, CONDUIT,WIRE, ETC.",
            "PANELS WITH BREAKERS 1200A AND OVER REQUIRE ARC FLASH REDUCTION PER NEC 240.87.",
            "CONTRACTOR WILL PROVIDE PANEL WITH ENERGY REDUCING MAINTENANCE SWITCH.",
            "THE CONTRACTOR HAS TO CHECK THE SIZE OF THE ELECTRICAL ROOM TO PROVIDE THE MAIN SWITCHGEAR WITH SUITABLE DIMENSIONS AND COMPLIANT WITH CODES FOR THE CLEARANCE REQUIREMENTS."
          ]
        }
      ],
      "panelIndex": {
        "entries": [
          "L1.E",
          "MDP",
          "PP",
          "SP"
        ],
        "blankCellsPreserved": true,
        "rowGrid": [
          [
            "L1.E",
            "MDP"
          ],
          [
            "PP",
            null
          ],
          [
            "SP",
            null
          ]
        ]
      },
      "generalNotes": [
        "CONTRACTOR SHALL PROVIDE A PERMANENTLY AFFIXED LABEL WITH THE MAXIMUM FAULT CURRENT PER ARTICLE 110.24. THE LABEL SHALL INCLUDE THE DATE THE FAULT-CURRENT CALCULATION WAS PERFORMED AND BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. THE LABEL SHALL BE 2\"X3\" IN SIZE AND SHALL BE BLUE LETTERING ON A CONTRASTING BACKGROUND.",
        "CONTRACTOR TO VERIFY FINAL CURRENT VALUES FROM ELECTRICAL UTILITY COMPANY AND PROVIDE AIC PROTECTION ACCORDINGLY.",
        "AIC RATINGS OF ALL THE PANELS & BRANCH BREAKERS SHALL MATCH THE FAULT CURRENT OF THE TRANSFORMER."
      ],
      "measurements": [
        {
          "type": "IN",
          "quantity": 2,
          "label": "fault-current label width",
          "basis": "general note 1, printed 2\"X3\""
        },
        {
          "type": "IN",
          "quantity": 3,
          "label": "fault-current label height",
          "basis": "general note 1, printed 2\"X3\""
        },
        {
          "type": "EA",
          "quantity": 6,
          "label": "panel schedules",
          "basis": "six distinct schedule blocks"
        },
        {
          "type": "EA",
          "quantity": 222,
          "label": "scheduled circuit positions",
          "basis": "42+42+42+6+24+66; includes every spare, space and continuation position"
        },
        {
          "type": "FORMULA",
          "quantity": null,
          "label": "MDP feeder sizing",
          "basis": "NEC Article 220 table; 779 kVA / 2161 A printed"
        },
        {
          "type": "FORMULA",
          "quantity": null,
          "label": "generator selection",
          "basis": "138.9 kVA governing fire-mode demand; 163 kVA printed selection"
        }
      ],
      "assemblies": [
        {
          "name": "normal distribution",
          "relationship": "SERVICE TRANSFORMER -> MDP -> L1.E, PP, SP and other floor panels",
          "basis": "SCHED"
        },
        {
          "name": "emergency distribution",
          "relationship": "GENSET PANEL (BUILT-IN) -> PANEL EP; EP is marked FED FROM MDP/GENSET VIA ATS",
          "basis": "SCHED",
          "ambiguity": "ATS tag is not printed in the E6.2 panel headers"
        },
        {
          "name": "roof DOAS feeders",
          "relationship": "MDP-44/46/48 -> DOAS-1 and MDP-50/52/54 -> DOAS-2",
          "basis": "SCHED + cross-sheet E3.5 confirmation"
        },
        {
          "name": "first-floor HVAC panel",
          "relationship": "MDP-26/28/30 -> L1.E; L1.E schedules six AHUs, six ACCUs, CU-1, CU-2, one generic EUH and two EV charging stations",
          "basis": "SCHED"
        }
      ],
      "crossSheetReconciliation": [
        {
          "status": "MATCH",
          "sources": [
            "E3.5",
            "E6.2"
          ],
          "statement": "DOAS-1 circuits MDP-44/46/48 and DOAS-2 circuits MDP-50/52/54 match exactly."
        },
        {
          "status": "CORRECTION",
          "sources": [
            "E1.0 audit",
            "E3.5",
            "E6.2"
          ],
          "statement": "Prior E1.0 audit assembly wording 'EP to DOAS-1/2' is superseded by direct MDP-to-DOAS circuits shown here and on E3.5."
        },
        {
          "status": "MATCH",
          "sources": [
            "E3.0",
            "E6.2"
          ],
          "statement": "L1.E schedules AHU-1.1 through AHU-1.6, ACCU-1.1 through ACCU-1.6, CU-1 and CU-2, aligning with the first-floor equipment tags; the unnumbered EUH remains ambiguous."
        },
        {
          "status": "MATCH",
          "sources": [
            "E5.0",
            "E6.2"
          ],
          "statement": "Two EV charging station branch circuits are scheduled; this is schedule evidence only and is not converted into an installed-device count."
        },
        {
          "status": "PARTIAL",
          "sources": [
            "E3.0 food-service schedule",
            "E6.2 PP"
          ],
          "statement": "PP includes food-service items 01, 02 twice, 05, 14, 16, 18, 20, 22, 24, 25, 26, 27, 28, 29, 34 and E901 plus disposer and kitchen receptacles. E3.0 items 35, 36 and 37 are not represented in PP."
        },
        {
          "status": "RESOLVED_ON_THIS_SHEET",
          "sources": [
            "E6.0/E6.1 audits",
            "E6.2"
          ],
          "statement": "Earlier E6 index pages omitted L1.E, PP and SP; E6.2's local panel index explicitly lists L1.E, PP, SP and MDP."
        },
        {
          "status": "OPEN",
          "sources": [
            "E1.0A",
            "M1.2",
            "E3.5",
            "E6.2"
          ],
          "statement": "E6.2 shows 150A/3P and 2/0 for each DOAS; prior reconciliation flags E1.0's 175A basis against M1.2's 150A maximum fuse and DOAS-2 voltage drop of 3.26%."
        }
      ],
      "importantHighlights": [
        "Schedules define circuits and loads; they do not prove installed quantities.",
        "All spare, space-only and continuation positions are retained in the 222-position register.",
        "General note 2 leaves final utility fault current to field verification; each printed AIC value remains design/schedule evidence only.",
        "SP note 3 explicitly limits permit scope to panel installation and grounding; pool breakers and branch circuits are under the pool permit.",
        "MDP notes require a fully rated 65 kAIC switchboard, one-line verification of feeder sizes, NEC 240.87 arc-flash reduction for breakers 1200A and over, and an energy-reducing maintenance switch."
      ],
      "issues": [
        {
          "id": 1,
          "severity": "HIGH",
          "title": "GENSET fire-pump row references nonexistent note 2",
          "evidence": "GENSET circuits 1/3/5 print NOTE 2, but the GENSET block contains only note 1.",
          "status": "BROKEN_REFERENCE"
        },
        {
          "id": 2,
          "severity": "MEDIUM",
          "title": "Panel index is incomplete",
          "evidence": "Local index lists only L1.E, MDP, PP and SP; EP and GENSET PANEL (BUILT-IN), both scheduled on this sheet, are omitted. Other MDP-fed floor panels are also absent.",
          "status": "INCOMPLETE_INDEX"
        },
        {
          "id": 3,
          "severity": "MEDIUM",
          "title": "L2.A and L2.B are labeled 3RD FLOOR",
          "evidence": "MDP circuits 37-47 print PANEL L2.A and PANEL L2.B with note (3RD FLOOR), inconsistent with their L2 naming and the separate L3.A/L3.B third-floor feeders.",
          "status": "PRINTED_CONFLICT"
        },
        {
          "id": 4,
          "severity": "HIGH",
          "title": "MDP elevator feeder-calculation row is internally inconsistent",
          "evidence": "Row 5.2 says one 30HP elevator at 26.4 kVA @100% but prints 52.8 kVA connected and sizing load; 52.8 corresponds to two such loads.",
          "status": "CALCULATION_AMBIGUITY"
        },
        {
          "id": 5,
          "severity": "MEDIUM",
          "title": "DOAS load-code classification differs",
          "evidence": "DOAS-1 is coded LGR on circuits 44/46/48 while otherwise-identical DOAS-2 is coded AC on circuits 50/52/54; each prints 15,011 VA/phase, 150/3 breaker and 2/0 wire.",
          "status": "CLASSIFICATION_CONFLICT"
        },
        {
          "id": 6,
          "severity": "HIGH",
          "title": "DOAS coordination conflict remains open",
          "evidence": "E6.2 confirms 150A/3P, 2/0 feeders; earlier E1.0A/E3.5 reconciliation records a 175A basis and DOAS-2 voltage drop of 3.26%, above the stated 3% limit, while M1.2 lists 150A maximum fuse.",
          "status": "CROSS_SHEET_CONFLICT"
        },
        {
          "id": 7,
          "severity": "MEDIUM",
          "title": "PP does not preserve optional/future qualifiers",
          "evidence": "E3.0 food-service evidence identified optional/future basis for items including 20, 25 and 29; PP schedules them as ordinary active circuit loads without those qualifiers.",
          "status": "SCOPE_AMBIGUITY"
        },
        {
          "id": 8,
          "severity": "MEDIUM",
          "title": "Food-service items 35, 36 and 37 have no PP row",
          "evidence": "They appear in prior E3.0 dry schedule evidence but are absent from all PP circuit descriptions.",
          "status": "CROSS_SHEET_OMISSION"
        },
        {
          "id": 9,
          "severity": "LOW",
          "title": "L1.E EUH tag is not uniquely numbered",
          "evidence": "Circuits 26/28 print only EUH; prior first-floor/mechanical evidence includes more than one EUH designation, so equipment identity cannot be certified from E6.2 alone.",
          "status": "AMBIGUOUS_TAG"
        },
        {
          "id": 10,
          "severity": "HIGH",
          "title": "Fault-current basis remains field-dependent",
          "evidence": "General note 2 requires final current values from the utility; scheduled AIC values of 10, 30, 42 and 65 kA are not a substitute for the final verified available-fault-current calculation.",
          "status": "OPEN_COORDINATION"
        },
        {
          "id": 11,
          "severity": "MEDIUM",
          "title": "Emergency source path lacks an ATS identifier",
          "evidence": "EP header says MDP/GENSET VIA ATS, but no ATS tag or rating is printed in the panel schedule block.",
          "status": "AMBIGUOUS_REFERENCE"
        },
        {
          "id": 12,
          "severity": "LOW",
          "title": "PP equipment basis requires supplier verification",
          "evidence": "PP note 1 directs field verification of breaker and cable sizes with the kitchen supplier; schedule values are not released fabrication values.",
          "status": "VERIFY"
        },
        {
          "id": 13,
          "severity": "LOW",
          "title": "SP branch scope is not installed by this permit",
          "evidence": "SP note 3 states breakers and branch circuits are installed under the pool permit; only panel and ground are covered here.",
          "status": "PERMIT_SCOPE"
        }
      ],
      "facts": {
        "scheduleCount": 6,
        "circuitPositionCount": 222,
        "panelIndexEntryCount": 4,
        "generalNoteCount": 3,
        "panelSpecificNoteCount": 16,
        "generatorCalculationRowCount": 11,
        "mdpFeederCalculationRowCount": 15,
        "installedQuantityInference": false,
        "linealFeet": null,
        "validation": "Full 7200x4800 raster and all seven high-resolution embedded schedule images were visually checked; every circuit number from each schedule was retained, including blanks/spares/spaces/continuations."
      },
      "secondaryAudit": {
        "schema": "E6.2-secondary-independent-verification-v1",
        "sheet": {
          "number": "E6.2",
          "title": "ELECTRICAL PANELS SCHEDULE",
          "engineeringPdfPage": 55,
          "pdfIndex": 54,
          "date": "NOV. 22, 2024",
          "sources": [
            "/workspace/sites/ssx-cover-release/source-plans/engineering.pdf",
            "/workspace/sites/ssx-cover-release/tmp/pdfs/final3-e62-e80/thumb-55.png",
            "/workspace/sites/ssx-cover-release/tmp/pdfs/final3-e62-e80/embedded/img-003.png through img-009.png"
          ],
          "normalizedCanvas": [
            1920,
            1280
          ]
        },
        "panelIndex": {
          "printedEntries": [
            "L1.E",
            "MDP",
            "PP",
            "SP"
          ],
          "omissions": [
            "EP",
            "GENSET PANEL (BUILT-IN)"
          ]
        },
        "schedules": [
          {
            "kind": "panel schedule",
            "panel": "L1.E",
            "feed": "MDP",
            "project": "HOME 2 SUITES, BRADENTON, FL",
            "projectNumber": "#210729",
            "voltage": "120/208V, 3PH, 4W",
            "aic": "42 KA",
            "bus": "400 AMP COPPER",
            "mains": "400 AMP M.L.O",
            "enclosure": "NEMA-1",
            "location": "ELEC. RM. 1ST FLOOR",
            "mounting": "SURFACE MOUNTED",
            "rows": [
              {
                "circuits": [
                  1,
                  3
                ],
                "description": "AHU-1.1",
                "loadType": "HTG",
                "breaker": "30/2",
                "wire": 10,
                "voltAmps": [
                  3110,
                  3110
                ],
                "note": null
              },
              {
                "circuits": [
                  2,
                  4
                ],
                "description": "AHU-1.5",
                "loadType": "HTG",
                "breaker": "30/2",
                "wire": 10,
                "voltAmps": [
                  3110,
                  3110
                ],
                "note": null
              },
              {
                "circuits": [
                  5,
                  7
                ],
                "description": "ACCU-1.1",
                "loadType": "AC",
                "breaker": "50/2",
                "wire": 6,
                "voltAmps": [
                  3058,
                  3058
                ],
                "note": null
              },
              {
                "circuits": [
                  6,
                  8
                ],
                "description": "ACCU-1.5",
                "loadType": "LGR",
                "breaker": "50/2",
                "wire": 6,
                "voltAmps": [
                  3058,
                  3058
                ],
                "note": null
              },
              {
                "circuits": [
                  9,
                  11
                ],
                "description": "AHU-1.2",
                "loadType": "HTG",
                "breaker": "30/2",
                "wire": 10,
                "voltAmps": [
                  3110,
                  3110
                ],
                "note": null
              },
              {
                "circuits": [
                  10,
                  12
                ],
                "description": "AHU-1.6",
                "loadType": "HTG",
                "breaker": "30/2",
                "wire": 10,
                "voltAmps": [
                  2860,
                  2860
                ],
                "note": null
              },
              {
                "circuits": [
                  13,
                  15
                ],
                "description": "ACCU-1.2",
                "loadType": "AC",
                "breaker": "50/2",
                "wire": 6,
                "voltAmps": [
                  3058,
                  3058
                ],
                "note": null
              },
              {
                "circuits": [
                  14,
                  16
                ],
                "description": "ACCU-1.6",
                "loadType": "AC",
                "breaker": "30/2",
                "wire": 10,
                "voltAmps": [
                  1997,
                  1997
                ],
                "note": null
              },
              {
                "circuits": [
                  17,
                  19
                ],
                "description": "AHU-1.3",
                "loadType": "HTG",
                "breaker": "30/2",
                "wire": 10,
                "voltAmps": [
                  2860,
                  2860
                ],
                "note": null
              },
              {
                "circuits": [
                  18,
                  20
                ],
                "description": "EV CHARGING STATION",
                "loadType": "EVCS",
                "breaker": "40/2",
                "wire": 8,
                "voltAmps": [
                  3600,
                  3600
                ],
                "note": null
              },
              {
                "circuits": [
                  21,
                  23
                ],
                "description": "ACCU-1.3",
                "loadType": "AC",
                "breaker": "30/2",
                "wire": null,
                "voltAmps": [
                  1997,
                  1997
                ],
                "note": "wire size visually blank/ambiguous"
              },
              {
                "circuits": [
                  22,
                  24
                ],
                "description": "EV CHARGING STATION",
                "loadType": "EVCS",
                "breaker": "40/2",
                "wire": 8,
                "voltAmps": [
                  3600,
                  3600
                ],
                "note": null
              },
              {
                "circuits": [
                  25,
                  27
                ],
                "description": "AHU-1.4",
                "loadType": "HTG",
                "breaker": "30/2",
                "wire": 10,
                "voltAmps": [
                  2860,
                  2860
                ],
                "note": null
              },
              {
                "circuits": [
                  26,
                  28
                ],
                "description": "EUH",
                "loadType": "HTG",
                "breaker": "30/2",
                "wire": 10,
                "voltAmps": [
                  2500,
                  2500
                ],
                "note": null
              },
              {
                "circuits": [
                  29,
                  31
                ],
                "description": "ACCU-1.4",
                "loadType": "AC",
                "breaker": "20/2",
                "wire": 12,
                "voltAmps": [
                  1404,
                  1404
                ],
                "note": null
              },
              {
                "circuits": [
                  30,
                  32,
                  34,
                  36
                ],
                "description": "SPARE",
                "loadType": null,
                "breaker": "20/1",
                "wire": null,
                "voltAmps": [
                  0,
                  0,
                  0,
                  0
                ],
                "note": null
              },
              {
                "circuits": [
                  33,
                  35
                ],
                "description": "CU-1",
                "loadType": "AC",
                "breaker": "30/2",
                "wire": 10,
                "voltAmps": [
                  1976,
                  1976
                ],
                "note": null
              },
              {
                "circuits": [
                  37,
                  39
                ],
                "description": "CU-2",
                "loadType": "AC",
                "breaker": "15/2",
                "wire": 12,
                "voltAmps": [
                  1560,
                  1560
                ],
                "note": null
              },
              {
                "circuits": [
                  38,
                  40,
                  42
                ],
                "description": "SPACE ONLY",
                "loadType": null,
                "breaker": null,
                "wire": null,
                "voltAmps": [
                  0,
                  0,
                  0
                ],
                "note": null
              },
              {
                "circuits": [
                  41
                ],
                "description": "SPACE ONLY",
                "loadType": null,
                "breaker": null,
                "wire": null,
                "voltAmps": [
                  0
                ],
                "note": null
              }
            ],
            "loadTotals": {
              "LTG": {
                "connected": 0,
                "demand": 0
              },
              "REC": {
                "connected": 0,
                "demand": 0
              },
              "EQUIP": {
                "connected": 0,
                "demand": 0
              },
              "AC": {
                "connected": 30098,
                "demand": 30098
              },
              "HTG": {
                "connected": 40818,
                "demand": 40818
              },
              "LGR": {
                "connected": 6115,
                "demand": 7644
              },
              "KIT": {
                "connected": 0,
                "demand": 0
              },
              "SUB": {
                "connected": 0,
                "demand": 0
              },
              "GLTG": {
                "connected": 0,
                "demand": 0
              },
              "EVCS": {
                "connected": 14400,
                "demand": 18000
              },
              "VA": {
                "connected": 91430,
                "demand": 96559
              },
              "AMPS": {
                "connected": 254,
                "demand": 268
              }
            },
            "phase": {
              "connectedKVA": {
                "A": 32.17,
                "B": 31.74,
                "C": 27.52
              },
              "connectedAmps": {
                "A": 268.11,
                "B": 264.47,
                "C": 229.35
              },
              "demandKVA": {
                "A": 33.84,
                "B": 32.64,
                "C": 30.09
              },
              "demandAmps": {
                "A": 281.98,
                "B": 271.97,
                "C": 250.72
              }
            },
            "panelNotes": [
              "VERIFY HPs, BREAKER SIZES, CABLES SIZES FOR THE HVAC EQUIPMENT WITH THE MECHANICAL EQUIPMENT SCHEDULE PRIOR TO INSTALLATION.",
              "FIELD VERIFICATION BREAKER SIZES, CABLE SIZES, ETC WITH EV CHARGING SUPPLIER/ MANUFACTURER PRIOR TO INSTALLATION."
            ]
          },
          {
            "kind": "panel schedule",
            "panel": "EP",
            "feed": "MDP/GENSET VIA ATS",
            "project": "HOME 2 SUITES, BRADENTON, FL",
            "projectNumber": "#210729",
            "voltage": "120/208V, 3PH, 4W",
            "aic": "42 KA",
            "bus": "250 AMP COPPER",
            "mains": "250 AMP M.C.B",
            "enclosure": "NEMA-1",
            "location": "ELECT. 1ST FLOOR",
            "mounting": "SURFACE MOUNTED",
            "rows": [
              {
                "circuits": [
                  1
                ],
                "description": "LTS - ELEVATOR SHAFT #1",
                "loadType": "LTG",
                "breaker": "20/1",
                "wire": 12,
                "voltAmps": [
                  100
                ],
                "note": null
              },
              {
                "circuits": [
                  3
                ],
                "description": "RCPTS - ELEVATOR SHAFT #1",
                "loadType": "REC",
                "breaker": "20/1",
                "wire": 12,
                "voltAmps": [
                  360
                ],
                "note": null
              },
              {
                "circuits": [
                  5
                ],
                "description": "SUMP PUMP CONTROL PNL (SP-1)",
                "loadType": "EQUIP",
                "breaker": "20/1",
                "wire": 12,
                "voltAmps": [
                  441
                ],
                "note": "(CLASS A GFCI BREAKER)"
              },
              {
                "circuits": [
                  7
                ],
                "description": "LTS - ELEVATOR SHAFT #2",
                "loadType": "LTG",
                "breaker": "20/1",
                "wire": 12,
                "voltAmps": [
                  100
                ],
                "note": null
              },
              {
                "circuits": [
                  9
                ],
                "description": "RCPTS - ELEVATOR SHAFT #2",
                "loadType": "REC",
                "breaker": "20/1",
                "wire": 12,
                "voltAmps": [
                  360
                ],
                "note": null
              },
              {
                "circuits": [
                  11
                ],
                "description": "SUMP PUMP CONTROL PNL (SP-2)",
                "loadType": "EQUIP",
                "breaker": "20/1",
                "wire": 12,
                "voltAmps": [
                  441
                ],
                "note": "(CLASS A GFCI BREAKER)"
              },
              {
                "circuits": [
                  13
                ],
                "description": "SPARE FOR EMERGENCY RADIO RESPONDERS COVERAGE 1ST FL.",
                "loadType": null,
                "breaker": "20/1",
                "wire": null,
                "voltAmps": [
                  0
                ],
                "note": null
              },
              {
                "circuits": [
                  15
                ],
                "description": "SPARE FOR EMERGENCY RADIO RESPONDERS COVERAGE 2ND FL.",
                "loadType": null,
                "breaker": "20/1",
                "wire": null,
                "voltAmps": [
                  0
                ],
                "note": null
              },
              {
                "circuits": [
                  17
                ],
                "description": "SPARE FOR EMERGENCY RADIO RESPONDERS COVERAGE 3RD FL.",
                "loadType": null,
                "breaker": "20/1",
                "wire": null,
                "voltAmps": [
                  0
                ],
                "note": null
              },
              {
                "circuits": [
                  19
                ],
                "description": "SPARE FOR EMERGENCY RADIO RESPONDERS COVERAGE 4TH FL.",
                "loadType": null,
                "breaker": "20/1",
                "wire": null,
                "voltAmps": [
                  0
                ],
                "note": null
              },
              {
                "circuits": [
                  21
                ],
                "description": "FACP",
                "loadType": "EQUIP",
                "breaker": "20/1",
                "wire": 12,
                "voltAmps": [
                  1500
                ],
                "note": "(NOTE 1)"
              },
              {
                "circuits": [
                  23,
                  25,
                  27,
                  29,
                  31
                ],
                "description": "SPARE",
                "loadType": null,
                "breaker": "20/1",
                "wire": null,
                "voltAmps": [
                  0,
                  0,
                  0,
                  0,
                  0
                ],
                "note": null
              },
              {
                "circuits": [
                  33,
                  35,
                  37,
                  39,
                  41
                ],
                "description": "SPACE ONLY",
                "loadType": null,
                "breaker": null,
                "wire": null,
                "voltAmps": [
                  0,
                  0,
                  0,
                  0,
                  0
                ],
                "note": null
              },
              {
                "circuits": [
                  2,
                  4,
                  6
                ],
                "description": "ELEVATOR #1",
                "loadType": "LGR",
                "breaker": "125/3",
                "wire": 1,
                "voltAmps": [
                  8824,
                  8824,
                  8824
                ],
                "note": "(SHUNT-TRIP BREAKER)"
              },
              {
                "circuits": [
                  8,
                  10,
                  12
                ],
                "description": "ELEVATOR #2",
                "loadType": "EQUIP",
                "breaker": "125/3",
                "wire": 1,
                "voltAmps": [
                  8824,
                  8824,
                  8824
                ],
                "note": "(SHUNT-TRIP BREAKER)"
              },
              {
                "circuits": [
                  14,
                  16,
                  18,
                  20,
                  22,
                  24,
                  26,
                  28,
                  30,
                  32,
                  34,
                  36,
                  38,
                  40,
                  42
                ],
                "description": "SPACE ONLY",
                "loadType": null,
                "breaker": null,
                "wire": null,
                "voltAmps": [
                  0,
                  0,
                  0,
                  0,
                  0,
                  0,
                  0,
                  0,
                  0,
                  0,
                  0,
                  0,
                  0,
                  0,
                  0
                ],
                "note": null
              }
            ],
            "loadTotals": {
              "LTG": {
                "connected": 200,
                "demand": 250
              },
              "REC": {
                "connected": 720,
                "demand": 720
              },
              "EQUIP": {
                "connected": 28853,
                "demand": 28853
              },
              "AC": {
                "connected": 0,
                "demand": 0
              },
              "HTG": {
                "connected": 0,
                "demand": 0
              },
              "LGR": {
                "connected": 26471,
                "demand": 33088
              },
              "KIT": {
                "connected": 0,
                "demand": 0
              },
              "SUB": {
                "connected": 0,
                "demand": 0
              },
              "GLTG": {
                "connected": 0,
                "demand": 0
              },
              "EVCS": {
                "connected": 0,
                "demand": 0
              },
              "VA": {
                "connected": 56244,
                "demand": 62911
              },
              "AMPS": {
                "connected": 156,
                "demand": 175
              }
            },
            "phase": {
              "connectedKVA": {
                "A": 17.85,
                "B": 19.87,
                "C": 18.53
              },
              "connectedAmps": {
                "A": 148.73,
                "B": 165.56,
                "C": 154.41
              },
              "demandKVA": {
                "A": 20.1,
                "B": 22.07,
                "C": 20.74
              },
              "demandAmps": {
                "A": 167.52,
                "B": 183.94,
                "C": 172.79
              }
            },
            "panelNotes": [
              "PROVIDE FIRE ALARM CIRCUIT BREAKER WITH RED MARKING PER NEC REQUIREMENTS.",
              "VERIFY HPs, BREAKER SIZES, ETC FOR ELEVATOR WITH ELEVATOR MANUFACTURER & CODE REQUIREMENTS PRIOR TO PLACING ORDERS/ INSTALLATION.",
              "THE BREAKER WILL BE SHUT OFF WHEN A FIRE OCCURS VIA THE SIGNAL FROM FACP."
            ]
          },
          {
            "kind": "panel schedule",
            "panel": "PP",
            "feed": "MDP",
            "project": "HOME 2 SUITES, BRADENTON, FL",
            "projectNumber": "#210729",
            "voltage": "120/208V, 3PH, 4W",
            "aic": "30 KA",
            "bus": "150 AMP COPPER",
            "mains": "150 AMP M.L.O",
            "enclosure": "NEMA-3R",
            "location": "FOOD PREP. 1ST FLOOR",
            "mounting": "SURFACE MOUNTED",
            "rows": [
              {
                "circuits": [
                  1
                ],
                "description": "(01) - MOBILE REACH-IN FREEZER",
                "loadType": "EQUIP",
                "breaker": "20/1",
                "wire": 12,
                "voltAmps": [
                  1152
                ],
                "note": "(GFCI BREAKER)"
              },
              {
                "circuits": [
                  3
                ],
                "description": "(02) - MOBILE REACH-IN REF.",
                "loadType": "EQUIP",
                "breaker": "20/1",
                "wire": 12,
                "voltAmps": [
                  648
                ],
                "note": "(GFCI BREAKER)"
              },
              {
                "circuits": [
                  5
                ],
                "description": "(02) - MOBILE REACH-IN REF.",
                "loadType": "EQUIP",
                "breaker": "20/1",
                "wire": 12,
                "voltAmps": [
                  648
                ],
                "note": "(GFCI BREAKER)"
              },
              {
                "circuits": [
                  7,
                  9,
                  11
                ],
                "description": "(05) - UNDERCOUNTER DISHMACHINE",
                "loadType": "EQUIP",
                "breaker": "40/3",
                "wire": 8,
                "voltAmps": [
                  3483,
                  3483,
                  3483
                ],
                "note": "(GFCI BREAKER)"
              },
              {
                "circuits": [
                  13,
                  15
                ],
                "description": "(14) - COFFEE MAKER",
                "loadType": "EQUIP",
                "breaker": "30/2",
                "wire": 10,
                "voltAmps": [
                  2340,
                  2340
                ],
                "note": null
              },
              {
                "circuits": [
                  17,
                  19
                ],
                "description": "(16) - CONVECTION OVEN",
                "loadType": "EQUIP",
                "breaker": "35/2",
                "wire": 8,
                "voltAmps": [
                  2891,
                  2891
                ],
                "note": null
              },
              {
                "circuits": [
                  21
                ],
                "description": "(18) - MOBILE REACH-IN FREEZER",
                "loadType": "EQUIP",
                "breaker": "20/1",
                "wire": 12,
                "voltAmps": [
                  864
                ],
                "note": "(GFCI BREAKER)"
              },
              {
                "circuits": [
                  23,
                  25
                ],
                "description": "(20) - CONVECTION OVEN",
                "loadType": "EQUIP",
                "breaker": "35/2",
                "wire": 8,
                "voltAmps": [
                  2891,
                  2891
                ],
                "note": null
              },
              {
                "circuits": [
                  27
                ],
                "description": "(22) - MICROWAVE OVEN",
                "loadType": "EQUIP",
                "breaker": "20/1",
                "wire": 12,
                "voltAmps": [
                  2016
                ],
                "note": null
              },
              {
                "circuits": [
                  29
                ],
                "description": "(24) - WAFFLE MAKER",
                "loadType": "EQUIP",
                "breaker": "20/1",
                "wire": 12,
                "voltAmps": [
                  1560
                ],
                "note": null
              },
              {
                "circuits": [
                  31
                ],
                "description": "(25) - WAFFLE MAKER",
                "loadType": "EQUIP",
                "breaker": "20/1",
                "wire": 12,
                "voltAmps": [
                  1560
                ],
                "note": null
              },
              {
                "circuits": [
                  2
                ],
                "description": "(26) - CONVEYOR TOASTER",
                "loadType": "EQUIP",
                "breaker": "20/1",
                "wire": 12,
                "voltAmps": [
                  1728
                ],
                "note": null
              },
              {
                "circuits": [
                  4
                ],
                "description": "(27) - DISPLAY SHOWCASE",
                "loadType": "EQUIP",
                "breaker": "20/1",
                "wire": 12,
                "voltAmps": [
                  1800
                ],
                "note": null
              },
              {
                "circuits": [
                  6
                ],
                "description": "(28) - JUICE DISPENSER",
                "loadType": "EQUIP",
                "breaker": "20/1",
                "wire": 12,
                "voltAmps": [
                  720
                ],
                "note": null
              },
              {
                "circuits": [
                  8
                ],
                "description": "(29) - WARMING KETTLE",
                "loadType": "EQUIP",
                "breaker": "20/1",
                "wire": 12,
                "voltAmps": [
                  804
                ],
                "note": null
              },
              {
                "circuits": [
                  10
                ],
                "description": "(34) - YOGURT DISPENSER",
                "loadType": "EQUIP",
                "breaker": "20/1",
                "wire": 12,
                "voltAmps": [
                  168
                ],
                "note": null
              },
              {
                "circuits": [
                  12
                ],
                "description": "(E901) - CONVENIENCE",
                "loadType": "EQUIP",
                "breaker": "20/1",
                "wire": 12,
                "voltAmps": [
                  1500
                ],
                "note": null
              },
              {
                "circuits": [
                  14
                ],
                "description": "DISPOSER",
                "loadType": "EQUIP",
                "breaker": "20/1",
                "wire": 12,
                "voltAmps": [
                  375
                ],
                "note": null
              },
              {
                "circuits": [
                  16
                ],
                "description": "RCPTS - KITCHEN",
                "loadType": "REC",
                "breaker": "20/1",
                "wire": 12,
                "voltAmps": [
                  540
                ],
                "note": null
              },
              {
                "circuits": [
                  18,
                  20,
                  22,
                  24,
                  26,
                  28,
                  30
                ],
                "description": "SPARE",
                "loadType": null,
                "breaker": "20/1",
                "wire": null,
                "voltAmps": [
                  0,
                  0,
                  0,
                  0,
                  0,
                  0,
                  0
                ],
                "note": null
              },
              {
                "circuits": [
                  32,
                  34,
                  36,
                  38,
                  40,
                  42,
                  33,
                  35,
                  37,
                  39,
                  41
                ],
                "description": "SPACE ONLY",
                "loadType": null,
                "breaker": null,
                "wire": null,
                "voltAmps": [
                  0,
                  0,
                  0,
                  0,
                  0,
                  0,
                  0,
                  0,
                  0,
                  0,
                  0
                ],
                "note": null
              }
            ],
            "loadTotals": {
              "LTG": {
                "connected": 0,
                "demand": 0
              },
              "REC": {
                "connected": 540,
                "demand": 540
              },
              "EQUIP": {
                "connected": 42236,
                "demand": 42236
              },
              "AC": {
                "connected": 0,
                "demand": 0
              },
              "HTG": {
                "connected": 0,
                "demand": 0
              },
              "LGR": {
                "connected": 0,
                "demand": 0
              },
              "KIT": {
                "connected": 0,
                "demand": 0
              },
              "SUB": {
                "connected": 0,
                "demand": 0
              },
              "GLTG": {
                "connected": 0,
                "demand": 0
              },
              "EVCS": {
                "connected": 0,
                "demand": 0
              },
              "VA": {
                "connected": 42776,
                "demand": 42776
              },
              "AMPS": {
                "connected": 119,
                "demand": 119
              }
            },
            "phase": {
              "connectedKVA": {
                "A": 17.22,
                "B": 11.86,
                "C": 13.69
              },
              "connectedAmps": {
                "A": 143.53,
                "B": 98.82,
                "C": 114.11
              },
              "demandKVA": {
                "A": 17.22,
                "B": 11.86,
                "C": 13.69
              },
              "demandAmps": {
                "A": 143.53,
                "B": 98.82,
                "C": 114.11
              }
            },
            "panelNotes": [
              "FIELD VERIFICATION BREAKER SIZES, CABLE SIZES, ETC WITH KITCHEN SUPPLIER PRIOR TO INSTALLATION."
            ]
          },
          {
            "kind": "panel schedule",
            "panel": "SP",
            "feed": "MDP",
            "project": "HOME 2 SUITES, BRADENTON, FL",
            "projectNumber": "#210729",
            "voltage": "120/208V, 3PH, 4W",
            "aic": "10 KA",
            "bus": "100 AMP COPPER",
            "mains": "100 AMP M.L.O",
            "enclosure": "NEMA-4X",
            "location": "POOL EQUIP. RM",
            "mounting": "SURFACE MOUNTED",
            "rows": [
              {
                "circuits": [
                  1
                ],
                "description": "LTS - SWIMMING POOL",
                "loadType": "LTG",
                "breaker": "20/1",
                "wire": 12,
                "voltAmps": [
                  100
                ],
                "note": "(GFCI BREAKER),(NOTE 1)"
              },
              {
                "circuits": [
                  2
                ],
                "description": "LTS - POOL EQUIP RM",
                "loadType": "LTG",
                "breaker": "20/1",
                "wire": 12,
                "voltAmps": [
                  500
                ],
                "note": "(GFCI BREAKER)"
              },
              {
                "circuits": [
                  3,
                  5
                ],
                "description": "POOL PUMP #1",
                "loadType": "EQUIP",
                "breaker": "20/2",
                "wire": 12,
                "voltAmps": [
                  1500,
                  1500
                ],
                "note": "(GFCI BREAKER)"
              },
              {
                "circuits": [
                  4
                ],
                "description": "RCPTS - POOL EQUIP RM",
                "loadType": "REC",
                "breaker": "20/1",
                "wire": 12,
                "voltAmps": [
                  360
                ],
                "note": null
              },
              {
                "circuits": [
                  6
                ],
                "description": "RCPTS - POOL AREA",
                "loadType": "REC",
                "breaker": "20/1",
                "wire": 12,
                "voltAmps": [
                  1440
                ],
                "note": null
              },
              {
                "circuits": [
                  7,
                  9
                ],
                "description": "POOL PUMP #2",
                "loadType": "EQUIP",
                "breaker": "25/2",
                "wire": 10,
                "voltAmps": [
                  1800,
                  1800
                ],
                "note": "(GFCI BREAKER)"
              },
              {
                "circuits": [
                  8
                ],
                "description": "POOL LIFT STATION",
                "loadType": "EQUIP",
                "breaker": "20/1",
                "wire": 12,
                "voltAmps": [
                  1000
                ],
                "note": "(GFCI BREAKER)"
              },
              {
                "circuits": [
                  10
                ],
                "description": "SPARE",
                "loadType": null,
                "breaker": "20/1",
                "wire": null,
                "voltAmps": [
                  0
                ],
                "note": null
              },
              {
                "circuits": [
                  11
                ],
                "description": "LTS - SWIMMING POOL AREA",
                "loadType": "LTG",
                "breaker": "20/1",
                "wire": 12,
                "voltAmps": [
                  500
                ],
                "note": "(GFCI BREAKER),(NOTE 1)"
              },
              {
                "circuits": [
                  12
                ],
                "description": "DRINKING FOUNTAIN",
                "loadType": "EQUIP",
                "breaker": "20/1",
                "wire": 12,
                "voltAmps": [
                  1500
                ],
                "note": "(CLASS A GFCI BREAKER)"
              },
              {
                "circuits": [
                  13
                ],
                "description": "SPARE",
                "loadType": null,
                "breaker": "20/1",
                "wire": null,
                "voltAmps": [
                  0
                ],
                "note": "(GFCI BREAKER)"
              },
              {
                "circuits": [
                  15
                ],
                "description": "SPARE",
                "loadType": null,
                "breaker": "20/1",
                "wire": null,
                "voltAmps": [
                  0
                ],
                "note": "(GFCI BREAKER)"
              },
              {
                "circuits": [
                  14,
                  16,
                  18,
                  20,
                  22,
                  24,
                  17,
                  19,
                  21,
                  23
                ],
                "description": "SPACE ONLY",
                "loadType": null,
                "breaker": null,
                "wire": null,
                "voltAmps": [
                  0,
                  0,
                  0,
                  0,
                  0,
                  0,
                  0,
                  0,
                  0,
                  0
                ],
                "note": null
              }
            ],
            "loadTotals": {
              "LTG": {
                "connected": 1100,
                "demand": 1375
              },
              "REC": {
                "connected": 1800,
                "demand": 1800
              },
              "EQUIP": {
                "connected": 9100,
                "demand": 9100
              },
              "AC": {
                "connected": 0,
                "demand": 0
              },
              "HTG": {
                "connected": 0,
                "demand": 0
              },
              "LGR": {
                "connected": 0,
                "demand": 0
              },
              "KIT": {
                "connected": 0,
                "demand": 0
              },
              "SUB": {
                "connected": 0,
                "demand": 0
              },
              "GLTG": {
                "connected": 0,
                "demand": 0
              },
              "EVCS": {
                "connected": 0,
                "demand": 0
              },
              "VA": {
                "connected": 12000,
                "demand": 12275
              },
              "AMPS": {
                "connected": 33,
                "demand": 34
              }
            },
            "phase": {
              "connectedKVA": {
                "A": 3.4,
                "B": 3.66,
                "C": 4.94
              },
              "connectedAmps": {
                "A": 28.33,
                "B": 30.5,
                "C": 41.17
              },
              "demandKVA": {
                "A": 3.55,
                "B": 3.66,
                "C": 5.07
              },
              "demandAmps": {
                "A": 29.58,
                "B": 30.5,
                "C": 42.21
              }
            },
            "panelNotes": [
              "CONTROLLED BY A 20A, 1P, TIME CLOCK WITH 4 HR BATTERIES.",
              "FIELD VERIFICATION BREAKER SIZES, CABLE SIZES, ETC WITH POOL CONTRACTOR PRIOR TO INSTALLATION.",
              "BREAKERS AND BRANCH CIRCUITS WILL BE INSTALLED UNDER THE POOL PERMIT AND THIS PERMIT COVERS ONLY THE INSTALLATION OF THE PANEL AND GROUND."
            ]
          },
          {
            "kind": "switchboard schedule",
            "panel": "MDP",
            "feed": "SERVICE TRANSFORMER",
            "project": "HOME 2 SUITES, BRADENTON, FL",
            "projectNumber": "#210729",
            "voltage": "120/208V, 3PH, 4W",
            "aic": "65 KA",
            "bus": "2500 AMP COPPER",
            "mains": "2500 AMP M.C.B",
            "enclosure": "NEMA-1",
            "location": "ELECT. 1ST FLOOR",
            "mounting": "FLOOR MOUNTED",
            "rows": [
              {
                "circuits": [
                  1,
                  3,
                  5
                ],
                "description": "PANEL L5.A",
                "loadType": "SUB",
                "breaker": "250/3",
                "wire": 300,
                "voltAmps": [
                  22947,
                  22947,
                  22947
                ],
                "note": "(5TH FLOOR)"
              },
              {
                "circuits": [
                  2,
                  4,
                  6
                ],
                "description": "PANEL L1.A",
                "loadType": "SUB",
                "breaker": "225/3",
                "wire": "4/0",
                "voltAmps": [
                  19707,
                  19707,
                  19707
                ],
                "note": "(1ST FLOOR)"
              },
              {
                "circuits": [
                  7,
                  9,
                  11
                ],
                "description": "PANEL L5.B",
                "loadType": "SUB",
                "breaker": "250/3",
                "wire": 300,
                "voltAmps": [
                  21603,
                  21603,
                  21603
                ],
                "note": "(5TH FLOOR)"
              },
              {
                "circuits": [
                  8,
                  10,
                  12
                ],
                "description": "PANEL L1.B",
                "loadType": "SUB",
                "breaker": "100/3",
                "wire": 1,
                "voltAmps": [
                  4828,
                  6593,
                  4757
                ],
                "note": "(1ST FLOOR)"
              },
              {
                "circuits": [
                  13,
                  15,
                  17
                ],
                "description": "PANEL L4.A",
                "loadType": "SUB",
                "breaker": "250/3",
                "wire": 300,
                "voltAmps": [
                  22750,
                  22750,
                  22750
                ],
                "note": "(4TH FLOOR)"
              },
              {
                "circuits": [
                  14,
                  16,
                  18
                ],
                "description": "PANEL L1.C",
                "loadType": "SUB",
                "breaker": "200/3",
                "wire": "4/0",
                "voltAmps": [
                  16717,
                  18001,
                  17837
                ],
                "note": "(1ST FLOOR)"
              },
              {
                "circuits": [
                  19,
                  21,
                  23
                ],
                "description": "PANEL L4.B",
                "loadType": "SUB",
                "breaker": "250/3",
                "wire": 300,
                "voltAmps": [
                  21603,
                  21603,
                  21603
                ],
                "note": "(4TH FLOOR)"
              },
              {
                "circuits": [
                  20,
                  22,
                  24
                ],
                "description": "PANEL L1.D",
                "loadType": "SUB",
                "breaker": "200/3",
                "wire": "4/0",
                "voltAmps": [
                  17178,
                  16695,
                  15766
                ],
                "note": "(1ST FLOOR)"
              },
              {
                "circuits": [
                  25,
                  27,
                  29
                ],
                "description": "PANEL L3.A",
                "loadType": "SUB",
                "breaker": "250/3",
                "wire": 300,
                "voltAmps": [
                  22897,
                  22897,
                  22897
                ],
                "note": "(3RD FLOOR)"
              },
              {
                "circuits": [
                  26,
                  28,
                  30
                ],
                "description": "PANEL L1.E",
                "loadType": "SUB",
                "breaker": "400/3",
                "wire": 600,
                "voltAmps": [
                  33837,
                  32636,
                  30086
                ],
                "note": "(1ST FLOOR)"
              },
              {
                "circuits": [
                  31,
                  33,
                  35
                ],
                "description": "PANEL L3.B",
                "loadType": "SUB",
                "breaker": "250/3",
                "wire": 300,
                "voltAmps": [
                  21603,
                  21603,
                  21603
                ],
                "note": "(3RD FLOOR)"
              },
              {
                "circuits": [
                  32,
                  34,
                  36
                ],
                "description": "PANEL PP",
                "loadType": "SUB",
                "breaker": "150/3",
                "wire": "2/0",
                "voltAmps": [
                  17224,
                  11859,
                  13693
                ],
                "note": "(1ST FLOOR)"
              },
              {
                "circuits": [
                  37,
                  39,
                  41
                ],
                "description": "PANEL L2.A",
                "loadType": "SUB",
                "breaker": "250/3",
                "wire": 300,
                "voltAmps": [
                  22750,
                  22750,
                  22750
                ],
                "note": "(3RD FLOOR)"
              },
              {
                "circuits": [
                  38,
                  40,
                  42
                ],
                "description": "PANEL SP",
                "loadType": "SUB",
                "breaker": "100/3",
                "wire": 1,
                "voltAmps": [
                  3550,
                  3660,
                  5065
                ],
                "note": "(1ST FLOOR)"
              },
              {
                "circuits": [
                  43,
                  45,
                  47
                ],
                "description": "PANEL L2.B",
                "loadType": "SUB",
                "breaker": "250/3",
                "wire": 300,
                "voltAmps": [
                  21603,
                  21603,
                  21603
                ],
                "note": "(3RD FLOOR)"
              },
              {
                "circuits": [
                  44,
                  46,
                  48
                ],
                "description": "DOAS-1",
                "loadType": "LGR",
                "breaker": "150/3",
                "wire": "2/0",
                "voltAmps": [
                  15011,
                  15011,
                  15011
                ],
                "note": "(ROOF)"
              },
              {
                "circuits": [
                  49,
                  51,
                  53
                ],
                "description": "SURGE PROTECTIVE DEVICE IN 'MDP'",
                "loadType": "EQUIP",
                "breaker": "60/3",
                "wire": 6,
                "voltAmps": [
                  0,
                  0,
                  0
                ],
                "note": null
              },
              {
                "circuits": [
                  50,
                  52,
                  54
                ],
                "description": "DOAS-2",
                "loadType": "AC",
                "breaker": "150/3",
                "wire": "2/0",
                "voltAmps": [
                  15011,
                  15011,
                  15011
                ],
                "note": "(ROOF)"
              },
              {
                "circuits": [
                  55,
                  57,
                  59
                ],
                "description": "SPACE ONLY",
                "loadType": null,
                "breaker": null,
                "wire": null,
                "voltAmps": [
                  0,
                  0,
                  0
                ],
                "note": null
              },
              {
                "circuits": [
                  56,
                  58,
                  60
                ],
                "description": "PANEL EP",
                "loadType": "SUB",
                "breaker": "250/3",
                "wire": 300,
                "voltAmps": [
                  20103,
                  22073,
                  20735
                ],
                "note": null
              },
              {
                "circuits": [
                  61,
                  63,
                  65,
                  62,
                  64,
                  66
                ],
                "description": "SPACE ONLY",
                "loadType": null,
                "breaker": null,
                "wire": null,
                "voltAmps": [
                  0,
                  0,
                  0,
                  0,
                  0,
                  0
                ],
                "note": null
              }
            ],
            "nec220": [
              {
                "category": "GENERAL LIGHTING",
                "connectedKVA": 23,
                "factor": 1.25,
                "sizingKVA": 28.8
              },
              {
                "category": "KITCHENETTE GUEST ROOMS UNIT LOADS",
                "connectedKVA": 1475.9,
                "factor": 0.23,
                "sizingKVA": 339.5
              },
              {
                "category": "DRYER 2@1.5KVA & 2@5KVA",
                "connectedKVA": 13,
                "factor": 1,
                "sizingKVA": 13
              },
              {
                "category": "WASHER 2@7.1KVA & 1@2.1KVA",
                "connectedKVA": 18.4,
                "factor": 1,
                "sizingKVA": 18.4
              },
              {
                "category": "VENDING/ICE MACHINES 5@1.5KVA",
                "connectedKVA": 7.5,
                "factor": 1,
                "sizingKVA": 7.5
              },
              {
                "category": "SERVICE EQUIPMENT",
                "connectedKVA": 82,
                "factor": 0.65,
                "sizingKVA": 53.3
              },
              {
                "category": "ELECTRIC CHARGING STATION: 2 @ 7.2KVA @125%",
                "connectedKVA": 14.4,
                "factor": 1.25,
                "sizingKVA": 18
              },
              {
                "category": "MISCELLANEOUS (FIRE ALARM, DOOR MOTOR, ELV, ETC.)",
                "connectedKVA": 15,
                "factor": 1,
                "sizingKVA": 15
              },
              {
                "category": "RECEPTACLES",
                "connectedKVA": 29.7,
                "factor": "first 10KVA +50%",
                "sizingKVA": 19.9
              },
              {
                "category": "AHU'S / HEATING /COOLING EUHS",
                "connectedKVA": 137.9,
                "factor": 1,
                "sizingKVA": 137.9
              },
              {
                "category": "ELEVATOR: 1 @ 30HP (26.4KVA) @100%",
                "connectedKVA": 52.8,
                "factor": 1,
                "sizingKVA": 52.8
              },
              {
                "category": "PUMPS",
                "connectedKVA": 18.3,
                "factor": 1,
                "sizingKVA": 18.3
              },
              {
                "category": "LARGEST MOTOR ELEVATOR: 1 @30HP (26.4KVA) @125%",
                "connectedKVA": 45,
                "factor": 1.25,
                "sizingKVA": 56.3
              }
            ],
            "feederSizing": {
              "kVA": 779,
              "amps": 2161
            },
            "panelNotes": [
              "SWITCHBOARD IS 'FULLY' RATED TO INCLUDE 65K AIC BREAKER.",
              "SEE ONE-LINE DIAGRAM FOR COMPLETE FEEDER SIZES.",
              "FIELD VERIFICATION HP PRIOR TO INSTALLING BRKR, CONDUIT, WIRE, ETC.",
              "PANELS WITH BREAKERS 1200A AND OVER REQUIRE ARC FLASH REDUCTION PER NEC 240.87.",
              "CONTRACTOR WILL PROVIDE PANEL WITH ENERGY REDUCING MAINTENANCE SWITCH.",
              "THE CONTRACTOR HAS TO CHECK THE SIZE OF THE ELECTRICAL ROOM TO PROVIDE THE MAIN SWITCHGEAR WITH SUITABLE DIMENSIONS AND COMPLIANT WITH CODES FOR THE CLEARANCE REQUIREMENTS."
            ]
          }
        ],
        "generatorBuiltIn": {
          "kind": "built-in generator panel and NEC Article 220 sizing block",
          "panel": "GENSET PANEL (BUILT-IN)",
          "feed": "generator internal",
          "project": "HOME 2 SUITES, BRADENTON, FL",
          "projectNumber": "#210729",
          "voltage": "120/208V, 3PH, 4W",
          "aic": "42 KA",
          "bus": "500 AMP COPPER",
          "mains": "500 AMP M.C.B",
          "enclosure": "NEMA-3R",
          "location": "OUTDOOR",
          "mounting": "SURFACE MOUNTED",
          "rows": [
            {
              "circuits": [
                1,
                3,
                5
              ],
              "description": "FIRE PUMP CONTROL PANEL",
              "loadType": "EQUIP",
              "breaker": "300/3",
              "wire": 400,
              "voltAmps": [
                22059,
                22059,
                22059
              ],
              "note": "(NOTE 2)"
            },
            {
              "circuits": [
                2,
                4,
                6
              ],
              "description": "PANEL EP",
              "loadType": "SUB",
              "breaker": "250/3",
              "wire": 300,
              "voltAmps": [
                20103,
                22073,
                20735
              ],
              "note": null
            }
          ],
          "connectedPhaseVA": {
            "A": 42162,
            "B": 44132,
            "C": 42794
          },
          "fireMode": [
            [
              "LARGEST MOTOR (FP) 75HP (66.2KVA) @125%",
              66.2,
              1.25,
              82.7
            ],
            [
              "MISC. (FIRE ALARM, ETC.) @100%",
              1.5,
              1,
              1.5
            ],
            [
              "ELEVATOR 2@30HP (26.4KVA) @100%",
              52.8,
              1,
              52.8
            ],
            [
              "LIGHTING (ELEV PIT #1,2) @125%",
              0.2,
              1.25,
              0.3
            ],
            [
              "RECEPTACLES (ELEV. #1,2) @100%",
              0.7,
              1,
              0.7
            ],
            [
              "SUMP PUMP @100%",
              0.9,
              1,
              0.9
            ]
          ],
          "fireModeTotalKVA": 138.9,
          "operationalMode": [
            [
              "MISC. (FIRE ALARM, ETC.) @100%",
              1.5,
              1,
              1.5
            ],
            [
              "ELEVATOR 1@30HP (26.4KVA) @100% & 1@30HP (26.4KVA) @125%",
              52.8,
              "1 & 1.25",
              59.4
            ],
            [
              "LIGHTING (ELEV. PIT #1,2) @125%",
              0.2,
              1.25,
              0.3
            ],
            [
              "RECEPTACLES (ELEV. #1,2) @100%",
              0.7,
              1,
              0.7
            ],
            [
              "SUMP PUMP @100%",
              0.9,
              1,
              0.9
            ]
          ],
          "operationalModeTotalKVA": 62.8,
          "selectedMode": "FIRE MODE, because operational total is less than fire demand load",
          "generatorSelectionKVA": 163,
          "panelNotes": [
            "ELECTRICAL CONTRACTOR SHALL VERIFY HPs, CABLE SIZES, BREAKER LUGS, DS, ETC OF FIRE PUMPS WITH FIRE CONTRACTOR PRIOR TO INSTALLATION."
          ]
        },
        "generalNotes": [
          "CONTRACTOR SHALL PROVIDE A PERMANENTLY AFFIXED LABEL WITH THE MAXIMUM FAULT CURRENT PER ARTICLE 110.24. THE LABEL SHALL INCLUDE THE DATE THE FAULT-CURRENT CALCULATION WAS PERFORMED AND BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. THE LABEL SHALL BE 2”X3” IN SIZE AND SHALL BE BLUE LETTERING ON A CONTRASTING BACKGROUND.",
          "CONTRACTOR TO VERIFY FINAL CURRENT VALUES FROM ELECTRICAL UTILITY COMPANY AND PROVIDE AIC PROTECTION ACCORDINGLY.",
          "AIC RATINGS OF ALL THE PANELS & BRANCH BREAKERS SHALL MATCH THE FAULT CURRENT OF THE TRANSFORMER."
        ],
        "arithmeticChecks": [
          {
            "item": "L1.E connected load codes",
            "calculation": "30098+40818+6115+14400=91431 VA",
            "printed": 91430,
            "result": "1 VA discrepancy; preserve printed"
          },
          {
            "item": "L1.E demand load codes",
            "calculation": "30098+40818+7644+18000=96560 VA",
            "printed": 96559,
            "result": "1 VA discrepancy; preserve printed"
          },
          {
            "item": "EP totals",
            "calculation": "200+720+28853+26471=56244; 250+720+28853+33088=62911",
            "result": "pass"
          },
          {
            "item": "PP totals",
            "calculation": "540+42236=42776 connected/demand",
            "result": "pass"
          },
          {
            "item": "SP totals",
            "calculation": "1100+1800+9100=12000; 1375+1800+9100=12275",
            "result": "pass"
          },
          {
            "item": "GENSET fire mode",
            "calculation": "82.7+1.5+52.8+0.3+0.7+0.9=138.9 kVA",
            "result": "pass"
          },
          {
            "item": "GENSET operational mode",
            "calculation": "1.5+59.4+0.3+0.7+0.9=62.8 kVA",
            "result": "pass"
          },
          {
            "item": "MDP feeder sizing",
            "calculation": "displayed category sizing values sum to 778.7 kVA, rounded to printed 779 kVA",
            "result": "pass with displayed rounding"
          },
          {
            "item": "MDP current",
            "calculation": "779 kVA at 120/208V 3-phase is approximately 2162 A using rounded kVA; printed 2161 A depends on unrounded inputs",
            "result": "rounding qualification"
          }
        ],
        "crossSheetChecks": [
          {
            "chain": "MDP -> L3.A/L3.B/L4.A/L4.B/L5.A/L5.B",
            "finding": "E6.2 shows 250A/3P feeders; E6.0 headers show 250A bus, 250A MLO, 22kA panels. Electrically consistent."
          },
          {
            "chain": "MDP -> L1.E",
            "finding": "E6.2 MDP breaker 400/3, 600 wire; L1.E header 400A bus/400A MLO, 42kA. Consistent."
          },
          {
            "chain": "MDP/GENSET -> ATS -> EP",
            "finding": "EP header explicitly names dual source via ATS; MDP and built-in genset tables each show a 250/3 feeder to EP. Consistent, ATS details remain off-table."
          },
          {
            "chain": "E5.0 generator",
            "finding": "163kVA gas genset label matches E6.2 generator selection 163kVA."
          },
          {
            "chain": "E5.0 EV requirement",
            "finding": "MDP calculation includes 2 EV charging stations at 7.2kVA each and L1.E schedules two 40/2 EV charging circuits; this supports capacity for two but does not resolve E5.0 location/install ambiguity."
          },
          {
            "chain": "E1.0 upper-floor feeders",
            "finding": "E1.0 identifies L2.A/B through L5.A/B as 250A MLO upper-floor panels on the MDP; E6.2 feeder breaker and conductor pattern is consistent same. E1.0 feeder ampacity narrative should control where exact one-line sizes differ."
          }
        ],
        "issues": [
          "1 HIGH: MDP schedule labels PANEL L2.A and PANEL L2.B as (3RD FLOOR); E6.1 and room numbering place L2 panels on the 2nd floor. Preserve the printed E6.2 note as a cross-sheet floor-label conflict.",
          "2 HIGH: GENSET PANEL FIRE PUMP CONTROL PANEL row cites (NOTE 2), but its block prints only NOTE 1. The note chain is broken unless an external note is intended.",
          "3 MEDIUM: Printed panel index lists L1.E, MDP, PP and SP but omits EP and the GENSET PANEL (BUILT-IN) table present on the sheet.",
          "4 MEDIUM: L1.E printed load-code components exceed connected and demand totals by 1 VA each. This is likely rounding, but no correction was inferred.",
          "5 MEDIUM: MDP NEC 220 elevator row text prints one 30HP/26.4kVA elevator at 100% while the connected column is 52.8kVA; the generator operational block explicitly describes two elevators for 52.8kVA. Text-to-value conflict requires designer clarification.",
          "6 MEDIUM: MDP largest-motor elevator row identifies 26.4kVA but prints connected load 45.0kVA and 56.3kVA after 125%; internal basis is not traceable from the row.",
          "7 MEDIUM: All AIC values remain conditional on utility fault current and transformer fault current per general notes; 65kA MDP, 42kA L1.E/EP/genset, 30kA PP and 10kA SP are printed, not independently fault-current certified here.",
          "8 LOW: ACCU-1.5 rows are printed under LGR rather than AC, producing the 6115VA largest-motor code and 125% demand. Preserved as printed.",
          "9 LOW: ACCU-1.3 wire size cell is visually blank/ambiguous; breaker 30/2 and 1997VA per pole are legible. No wire size inferred.",
          "10 MEDIUM: Panel-specific field-verification notes defer HVAC, elevator, kitchen, pool and fire-pump breaker/conductor/equipment sizing to suppliers/contractors.",
          "11 LOW: MDP displayed sizing values total 778.7kVA and round to 779kVA; current recomputation from rounded 779kVA gives approximately 2162A versus printed2161A, consistent only with unrounded inputs.",
          "12 MEDIUM: The E6.2 MDP schedule is a feeder table, not proof of downstream branch-circuit installation; unlisted ATS and service-transformer details remain dependent on E1.0."
        ],
        "validation": {
          "fivePanelOrSwitchboardSchedules": [
            "L1.E",
            "EP",
            "PP",
            "SP",
            "MDP"
          ],
          "supplementalBuiltInGeneratorPanelReviewed": true,
          "allCircuitRowsRead": true,
          "allPhaseAndLoadTotalsRead": true,
          "generalNoteCount": 3,
          "panelSpecificNoteCount": {
            "L1E": 2,
            "EP": 3,
            "PP": 1,
            "SP": 3,
            "MDP": 6,
            "GENSET": 1
          },
          "panelIndexRead": true,
          "arithmeticChecked": true,
          "crossSheetChecked": [
            "E1.0",
            "E6.0",
            "E6.1",
            "E5.0"
          ],
          "ocrUse": "no numerical certification from OCR; embedded high-resolution schedule images and full-sheet raster inspected",
          "status": "validated with printed discrepancies preserved"
        }
      },
      "independentCrossCheck": {
        "schemaVersion": "1.0",
        "documentType": "independent_cross_sheet_reconciliation",
        "batch": {
          "sheets": [
            "E6.2",
            "E7.0",
            "E8.0"
          ],
          "engineeringPdfPages": [
            55,
            56,
            57
          ],
          "sourcePdf": "/workspace/sites/ssx-cover-release/source-plans/engineering.pdf",
          "sourceImages": [
            "/workspace/sites/ssx-cover-release/tmp/pdfs/final3-e62-e80/thumb-55.png",
            "/workspace/sites/ssx-cover-release/tmp/pdfs/final3-e62-e80/thumb-56.png",
            "/workspace/sites/ssx-cover-release/tmp/pdfs/final3-e62-e80/thumb-57.png",
            "/workspace/sites/ssx-cover-release/tmp/pdfs/final3-e62-e80/embedded/img-013.png"
          ],
          "currentBatchAudits": [
            {
              "path": "/workspace/scratch/e9eeb133d6f5/delegated-final3/e62-secondary.json",
              "role": "independent full-sheet secondary audit",
              "availabilityAtValidation": "present"
            },
            {
              "path": "/workspace/scratch/e9eeb133d6f5/delegated-final3/e62.json",
              "role": "primary sheet audit",
              "availabilityAtValidation": "present"
            },
            {
              "path": "/workspace/scratch/e9eeb133d6f5/delegated-final3/e70.json",
              "role": "primary sheet audit",
              "availabilityAtValidation": "present"
            },
            {
              "path": "/workspace/scratch/e9eeb133d6f5/delegated-final3/e70-secondary.json",
              "role": "independent secondary audit",
              "availabilityAtValidation": "present"
            },
            {
              "path": "/workspace/scratch/e9eeb133d6f5/delegated-final3/e80.json",
              "role": "primary sheet audit",
              "availabilityAtValidation": "present"
            }
          ],
          "priorEvidence": [
            "/workspace/scratch/e9eeb133d6f5/delegated-next5/e10.json",
            "/workspace/scratch/e9eeb133d6f5/delegated-next5/crosscheck.json",
            "/workspace/scratch/e9eeb133d6f5/delegated-e12-e24/crosscheck.json",
            "/workspace/scratch/e9eeb133d6f5/delegated-e30-e34/crosscheck.json",
            "/workspace/scratch/e9eeb133d6f5/delegated-e35-e51/crosscheck.json",
            "/workspace/scratch/e9eeb133d6f5/delegated-e52-e61/crosscheck.json",
            "/workspace/sites/ssx-cover-release/dist/e35-full-audit.json",
            "/workspace/sites/ssx-cover-release/dist/e60-full-audit.json",
            "/workspace/sites/ssx-cover-release/dist/e61-full-audit.json"
          ],
          "method": "Read-only cross-sheet comparison of source PDF pages 55-57, full-page renders, the higher-resolution E8.0 embedded image, current-batch audits and established E1.0-E6.1 evidence. Printed panel rows, one-line feeders, plan occurrences, schedule definitions, COMcheck compliance aggregates and NTS reference graphics were kept as distinct evidence classes. No illegible value, hidden precision, unprinted mapping or correction was inferred.",
          "scopeExclusions": [
            "No physical-length takeoff was performed. E6.2 is tabular, all eight E7.0 details are NTS, and E8.0 is a compliance report.",
            "Primary per-sheet audits were not duplicated.",
            "A panel row, COMcheck aggregate, typical detail, manufacturer/system example or photometric schedule row does not create an additional installed occurrence."
          ]
        },
        "summary": {
          "overallStatus": "HOLD",
          "crossSheetTakeoffCompleteness": "PASS",
          "coordinationProcurementRelease": "HOLD",
          "takeoffCompletenessReason": "The six E6.2 schedule blocks, all eight E7.0 NTS details and all four embedded E8.0 COMcheck certificate pages were reconciled. The schedule chain now contains all 15 branch panelboards named on E1.0, and the exact current-batch totals are preserved without converting references or compliance aggregates into installed quantities.",
          "releaseReason": "Release remains on HOLD because E6.2's own index omits EP and the built-in generator panel; the MDP labels L2.A/L2.B as third-floor panels and contains conflicting elevator load statements; the generator fire-pump row cites a missing Note 2; utility fault current and several supplier verifications remain open; the interior COMcheck contains tag/count and displayed-watt discrepancies; the exterior COMcheck models only 9 of the 23 scheduled site-lighting heads and omits SB1; the certificate code/project identity is not coordinated; and E7.0 lacks project-specific firestop listings and an unambiguous roof-raceway/detail applicability map.",
          "findingCounts": {
            "PASS": 12,
            "HOLD": 22
          }
        },
        "sheetRegister": [
          {
            "sheet": "E6.2",
            "title": "ELECTRICAL PANELS SCHEDULE",
            "page": 55,
            "content": "Five titled panel/switchboard schedules plus one built-in generator-panel block: L1.E, EP, PP, SP, MDP and GENSET PANEL (BUILT-IN).",
            "printedIndex": [
              "L1.E",
              "MDP",
              "PP",
              "SP"
            ],
            "scaleRule": "Tabular schedules; graphic scale is not applicable."
          },
          {
            "sheet": "E7.0",
            "title": "ELECTRICAL DETAILS",
            "page": 56,
            "content": "Eight numbered reference details covering mounting heights, GFI mounting, roof HVAC/maintenance receptacles, rated-wall boxes and firestop assemblies.",
            "scaleRule": "All eight details state SCALE: NTS. No graphic length or installed count may be derived from their geometry."
          },
          {
            "sheet": "E8.0",
            "title": "ELECTRICAL COMCHECK REPORT",
            "page": 57,
            "content": "Four embedded certificate pages: Interior Lighting Compliance Certificate pages 1-2 of 4 and Exterior Lighting Compliance Certificate pages 3-4 of 4.",
            "scaleRule": "Compliance-report tables; scale is not applicable. Quantities are modeled report aggregates, not plan-installed takeoff counts."
          }
        ],
        "panelAndSourceReconciliation": {
          "branchPanelScheduleCompleteness": {
            "e10Panelboards": [
              "L1.A",
              "L1.B",
              "L1.C",
              "L1.D",
              "L1.E",
              "PP",
              "SP",
              "L2.A",
              "L2.B",
              "L3.A",
              "L3.B",
              "L4.A",
              "L4.B",
              "L5.A",
              "L5.B"
            ],
            "scheduledOnE60E61": [
              "L1.A",
              "L1.B",
              "L1.C",
              "L1.D",
              "L2.A",
              "L2.B",
              "L3.A",
              "L3.B",
              "L4.A",
              "L4.B",
              "L5.A",
              "L5.B"
            ],
            "scheduledOnE62": [
              "L1.E",
              "PP",
              "SP"
            ],
            "projectTotalBranchPanelboards": 15,
            "scheduledBranchPanelboards": 15,
            "conclusion": "Content completeness passes across E6.0-E6.2. E6.2's printed on-sheet index is separately incomplete because it omits EP and the generator block that are visibly present."
          },
          "e62ScheduleHeaders": [
            {
              "name": "L1.E",
              "fedFrom": "MDP",
              "system": "120/208V, 3PH, 4W",
              "busA": 400,
              "main": "400A MLO",
              "aic": "42kA",
              "enclosure": "NEMA-1"
            },
            {
              "name": "EP",
              "fedFrom": "MDP/GENSET VIA ATS",
              "busA": 250,
              "main": "250A MCB",
              "aic": "42kA",
              "enclosure": "NEMA-1"
            },
            {
              "name": "PP",
              "fedFrom": "MDP",
              "busA": 150,
              "main": "150A MLO",
              "aic": "30kA",
              "enclosure": "NEMA-3R"
            },
            {
              "name": "SP",
              "fedFrom": "MDP",
              "busA": 100,
              "main": "100A MLO",
              "aic": "10kA",
              "enclosure": "NEMA-4X"
            },
            {
              "name": "GENSET PANEL (BUILT-IN)",
              "fedFrom": "generator",
              "busA": 500,
              "main": "500A MCB",
              "aic": "42kA",
              "enclosure": "NEMA-3R"
            },
            {
              "name": "MDP",
              "fedFrom": "SERVICE TRANSFORMER",
              "busA": 2500,
              "main": "2500A MCB",
              "aic": "65kA",
              "enclosure": "NEMA-1"
            }
          ],
          "mdpFeederChecks": [
            {
              "destinations": "L2.A/L2.B through L5.A/L5.B",
              "breaker": "250A/3P",
              "wire": "#300",
              "status": "PASS",
              "qualification": "Electrical rating chain agrees with the 250A upper-floor panel headers; E6.2 floor labels for L2.A/L2.B remain a separate HOLD."
            },
            {
              "destination": "L1.A",
              "breaker": "225A/3P",
              "wire": "#4/0",
              "status": "PASS"
            },
            {
              "destination": "L1.B",
              "breaker": "100A/3P",
              "wire": "#1",
              "status": "PASS"
            },
            {
              "destinations": "L1.C/L1.D",
              "breaker": "200A/3P",
              "wire": "#4/0",
              "status": "PASS"
            },
            {
              "destination": "L1.E",
              "breaker": "400A/3P",
              "wire": "#600",
              "status": "PASS"
            },
            {
              "destination": "PP",
              "breaker": "150A/3P",
              "wire": "#2/0",
              "status": "PASS"
            },
            {
              "destination": "SP",
              "breaker": "100A/3P",
              "wire": "#1",
              "status": "PASS"
            },
            {
              "destinations": "DOAS-1/DOAS-2",
              "breaker": "150A/3P each",
              "wire": "#2/0 each",
              "status": "PASS",
              "qualification": "The 150A branch protection agrees with M1.2's 150A maximum fuse. E1.0's #2/0 feeder ampacity and E1.0A's DOAS-2 3.26% voltage drop remain separate design checks."
            },
            {
              "destination": "EP",
              "breaker": "250A/3P",
              "wire": "#300",
              "status": "PASS"
            },
            {
              "destination": "SPD",
              "breaker": "60A/3P",
              "wire": "#6",
              "status": "PASS"
            }
          ],
          "l1eMechanicalAndSiteLoads": {
            "scheduledEquipmentCounts": {
              "AHU": 6,
              "ACCU": 6,
              "CU": 2,
              "EUH": 1,
              "EVChargingStations": 2
            },
            "mechanicalScheduleComparison": "Six AHUs, six ACCUs and two CUs match M1.1. The AHU 30A, ACCU 50/50/30/20/50/30A, CU-1 30A and CU-2 15A two-pole breakers match the printed M1.1 MOCP values. The 5kW, 30A/2P EUH row is unnumbered, so its exact EUH identity is not certified.",
            "evCapacity": "Two 40A/2P branches at 7.2kVA each equal 14.4kVA connected and 18.0kVA demand at 125%, matching the E1.0 service-load basis for two charging stations. Capacity does not by itself resolve E5.0's future-rough-in versus installed-station scope.",
            "printedArithmetic": [
              {
                "item": "connected load-code sum",
                "calculatedFromDisplayedValuesVA": 91431,
                "printedVA": 91430,
                "differenceVA": 1
              },
              {
                "item": "demand load-code sum",
                "calculatedFromDisplayedValuesVA": 96560,
                "printedVA": 96559,
                "differenceVA": 1
              }
            ],
            "unresolvedCell": "ACCU-1.3 has a legible 30A/2P breaker and load but a visually blank/ambiguous wire-size cell; no wire size is inferred."
          },
          "emergencyAndGenerator": {
            "epSource": "MDP/GENSET VIA ATS",
            "epElevatorBranches": [
              {
                "load": "Elevator 1",
                "breaker": "125A/3P",
                "wire": "#1",
                "feature": "shunt trip"
              },
              {
                "load": "Elevator 2",
                "breaker": "125A/3P",
                "wire": "#1",
                "feature": "shunt trip"
              }
            ],
            "generatorModes": {
              "fireModeKVA": 138.9,
              "operationalModeKVA": 62.8,
              "selectedGeneratorKVA": 163,
              "crossSheet": "The selected 163kVA generator matches E1.0/E5.0."
            },
            "brokenReference": "The FIRE PUMP CONTROL PANEL row cites NOTE 2, but the generator block prints only NOTE 1."
          },
          "scopeBoundaries": [
            "SP Note 3 states pool breakers and branch circuits are installed under the pool permit; the current permit covers only the panel and ground. Do not roll downstream pool devices into this permit from SP schedule rows.",
            "PP food-equipment rows are electrical source/load allocations, not additional installed equipment occurrences.",
            "MDP feeder rows are source relationships, not duplicate downstream panel or equipment quantities."
          ]
        },
        "comcheckReconciliation": {
          "reportIdentity": {
            "certificateEnergyCode": "2021 IECC",
            "engineeringDetailCaption": "2023 FLORIDA - 8TH EDITION COMCHECK REPORT",
            "comcheckProject": "24-06-16",
            "engineeringTitleBlockProject": "210729",
            "ownerAgent": null,
            "designerContractor": null,
            "status": "HOLD until code applicability and project identity are confirmed and required parties complete the certificates."
          },
          "interior": {
            "allowedWatts": 24522,
            "proposedWatts": 16876,
            "printedResult": "PASS; design is 31% better than code",
            "exactComputedPercentBetter": 31.1802,
            "additionalEfficiencyCredits": {
              "required": 10,
              "proposed": 11,
              "cooling": 2,
              "dedicatedOutdoorAir": 3,
              "reducedLightingPower": 6
            },
            "fixtureRowCount": 27,
            "modeledFixtureQuantityTotal": 1089,
            "guestroomComparison": [
              {
                "comcheckTag": "G10",
                "comcheckQuantity": 341,
                "planScheduleTag": "GR10",
                "mappedExpectedQuantity": 341,
                "status": "HOLD",
                "reason": "Quantity maps numerically, but G10 is not the defined GR10 tag; no substitution is certified."
              },
              {
                "comcheckTag": "S21",
                "comcheckQuantity": 224,
                "mappedExpectedQuantity": 228,
                "difference": -4,
                "status": "HOLD"
              },
              {
                "comcheckTag": "GR-203",
                "comcheckQuantity": 107,
                "mappedExpectedQuantity": 107,
                "difference": 0,
                "status": "PASS"
              }
            ],
            "commonAreaExamples": [
              {
                "tag": "R11",
                "planTotal": 97,
                "comcheckTotal": 97,
                "status": "PASS"
              },
              {
                "tag": "PA-204",
                "planTotal": 111,
                "comcheckTotal": 111,
                "status": "PASS"
              },
              {
                "tag": "S02",
                "planTotal": 18,
                "comcheckTotal": 18,
                "status": "PASS"
              },
              {
                "tag": "R01",
                "planTotal": 59,
                "comcheckTotal": 62,
                "difference": 3,
                "status": "HOLD"
              },
              {
                "planTag": "S04",
                "planTotal": 1,
                "scheduleDefinition": "missing from E1.2",
                "comcheckTreatment": "No S04 row; COMcheck reports S01 total 13 while plans contain 12 S01 plus one unresolved S04.",
                "status": "HOLD",
                "reason": "Apparent substitution is not accepted without a design correction."
              }
            ],
            "wholeBuildingComparison": {
              "visibleCommonAreaPlanOccurrences": 414,
              "mappedGuestroomPrototypeOccurrences": 676,
              "combinedPlanBasis": 1090,
              "comcheckModeledFixtureQuantity": 1089,
              "netDifference": -1,
              "qualification": "The net difference masks independent tag/count problems: R01 is +3 in COMcheck, S21 is -4, and S01/S04 is an unresolved tag substitution. It is not a one-fixture correction instruction."
            },
            "displayedWattArithmetic": {
              "largestExplicitConflict": "G10 prints 341 fixtures at 12W and 4,262W proposed; 341 x 12 = 4,092W, a 170W difference.",
              "otherRowsWithDisplayedIntegerWattDifferences": [
                "S20 +1W",
                "S20 +3W",
                "R01 +24W",
                "R05 +3W",
                "R11 +40W",
                "R01 +4W",
                "R01 +4W",
                "R11 +8W"
              ],
              "rule": "Preserve printed proposed totals. Hidden fixture precision may exist, but none is inferred."
            }
          },
          "exterior": {
            "printedTradableAllowedWatts": 1344,
            "displayedAllowedRowsSumWatts": 1345,
            "supplementalAllowanceWatts": 500,
            "proposedWatts": 1198,
            "printedResult": "PASS; design is 35% better than code",
            "exactComputedPercentBetterUsing1844W": 35.0325,
            "siteLightingModel": {
              "arrangements": 6,
              "luminaireHeads": 9,
              "wattsPerHead": 56,
              "parkingAreaWatts": 504,
              "tagsRepresented": [
                "SA",
                "SA1",
                "SB",
                "SC1"
              ],
              "missingTag": "SB1"
            },
            "planAndPhotometricSchedule": {
              "arrangements": 16,
              "luminaireHeads": 23,
              "standardHeads": 12,
              "hssHeads": 11,
              "e51CalculationPoints": 526,
              "scheduleDecimalsExcludedFromPointCount": 13
            },
            "difference": {
              "missingModeledHeads": 14,
              "status": "HOLD",
              "sensitivityOnly": "If the 14 omitted heads were added at E5.2's 56W/head, proposed power would increase from 1,198W to 1,982W, 138W above the printed 1,844W combined allowance. This is an inference for risk screening only; it is not a corrected COMcheck result and a model rerun is required."
            },
            "otherPlanComparisons": [
              {
                "tag": "R02",
                "comcheckQuantity": 19,
                "visibleE20PlanQuantity": 1,
                "status": "HOLD",
                "reason": "E2.0 defers architectural/prototype quantity confirmation; the 19-count aggregate lacks an occurrence map."
              },
              {
                "tag": "S03",
                "comcheckQuantity": 14,
                "visibleE20PlanQuantity": 15,
                "difference": -1,
                "status": "HOLD"
              }
            ],
            "productBasisConflict": "The existing procurement/photometric conflict remains: E1.2/E5.2 define JPL-1 at 3000K and 56W with E5.2 mounting/finish unselected, while E5.1 uses 4000K NV-description rows at 19-foot mounting, 6,832 lumens standard and 4,252 lumens HSS."
          },
          "nonAdditiveClasses": [
            "COMcheck fixture quantities are compliance-model aggregates and add zero installed fixtures to plan counts.",
            "E5.1's 16 pole arrangements and 23 luminaire heads describe the same installed system at different grouping levels; never add 16 + 23.",
            "E5.1 rows QTY 12 and QTY 11 corroborate the same 23 heads and add zero more heads.",
            "The 526 E5.1 photometric calculation points are analysis readings, not fixtures. The 13 schedule decimal entries are excluded from that point count."
          ]
        },
        "detailAndOccurrenceReconciliation": {
          "e70ExactReferenceInventory": {
            "numberedDetails": 8,
            "ntsLabels": 8,
            "installedProjectQuantityFromGraphics": 0,
            "rule": "Every E7.0 graphic is a reference assembly. Project quantities come only from plan occurrences and schedules."
          },
          "closedChains": [
            {
              "chain": "E1.1 General Note 7 -> E7.0 Detail 1",
              "status": "PASS",
              "evidence": "Detail 1 supplies the referenced device-mounting heights; it remains a generalized standard subject to discipline-specific exceptions."
            },
            {
              "chain": "E3.5 roof plan -> E6.0 L5.A-34 -> E7.0 Details 3/6",
              "status": "PASS for count/source; HOLD for installation selection",
              "evidence": "E3.5 shows three WP GFI receptacles on one L5.A-34 branch adjacent to DOAS-1, DOAS-2 and EF-10; E6.0 schedules RCPTS - ROOF at 540VA, consistent with three 180VA receptacle loads. E7.0 supplies typical weatherproof GFI/raceway requirements but no occurrence multiplier."
            }
          ],
          "firestopRequirements": {
            "detail4PartyWall": "Steel boxes are limited to 16 square inches and require 3M MPP-4S or equal, resilient isolation, staggered placement and local inspector approval.",
            "detail5RatedWall": "UL300/UL400 series is cited; boxes are limited to 100 square inches per 100 square feet; putty pad is 1/8 inch for 1-hour and 1/4 inch for 2-hour construction; opposite boxes less than 24 inches apart may not be back-to-back.",
            "detail7Alternatives": "One of four named manufacturer systems is permitted; system-specific materials and rules may not be mixed without a listed/approved assembly.",
            "detail8Hilti": "FS657/FS-ONE multi-penetration example, maximum opening 2,496 square inches, F rating 4 hours and T rating 0 hours.",
            "releaseGap": "Details 5, 7 and 8 do not print a complete tested-system/design identifier or a project-location/penetration register. Substrate, penetrating-item mix, annular space, opening size and acceptance remain unverified."
          },
          "roofDetailAmbiguity": "Detail 3 depicts an EMT-to-Sealtight transition through a roof pitch pocket; Detail 6 routes 1/2-inch Sealtight inside the curb to a bar-joist J-box. The sheet does not state which condition governs each of the three plotted roof assemblies or how the two details combine. Physical mounting/routing remains a coordination HOLD.",
          "nonRoofMaintenanceScope": "E3.2/E3.4 above-ceiling maintenance receptacle notes and undefined C.P/HP tags are not roof-mounted HVAC occurrences and must not be multiplied from E7.0 Details 3/6. Their served equipment and source remain unresolved."
        },
        "findings": [
          {
            "id": "PASS-01",
            "status": "PASS",
            "topic": "Sheet and scale inventory",
            "evidence": [
              "Pages 55-57 progress E6.2, E7.0 and E8.0 without a gap.",
              "E7.0 has exactly eight details and all eight state NTS.",
              "E6.2 and E8.0 are schedules/reports with no measurable geometry."
            ],
            "conclusion": "The final three-sheet content and scale/NTS boundaries are fully reconciled."
          },
          {
            "id": "PASS-02",
            "status": "PASS",
            "topic": "Branch-panel schedule content completeness",
            "evidence": [
              "E1.0 names 15 branch panelboards.",
              "E6.0/E6.1 schedule 12.",
              "E6.2 schedules L1.E, PP and SP."
            ],
            "conclusion": "All 15 branch panelboards have schedule content across E6.0-E6.2."
          },
          {
            "id": "PASS-03",
            "status": "PASS",
            "topic": "MDP feeder and destination chain",
            "evidence": [
              "E6.2 prints feeder rows for every scheduled branch panel, both DOAS units, EP and SPD.",
              "Breaker sizes agree with destination panel headers and the E1.0 one-line relationships."
            ],
            "conclusion": "The visible MDP source chain is complete as a feeder inventory, subject to the separately listed design holds."
          },
          {
            "id": "PASS-04",
            "status": "PASS",
            "topic": "First-floor mechanical schedule relationship",
            "evidence": [
              "L1.E contains 6 AHU, 6 ACCU and 2 CU loads.",
              "Those counts and printed breaker sizes match M1.1's equipment register and MOCP values."
            ],
            "conclusion": "The L1.E first-floor HVAC equipment count/source chain reconciles."
          },
          {
            "id": "PASS-05",
            "status": "PASS",
            "topic": "DOAS branch protection",
            "evidence": [
              "E6.2 MDP provides one 150A/3P breaker to each DOAS.",
              "M1.2 prints 150A maximum fuse for each unit."
            ],
            "conclusion": "The 150A overcurrent-protection relationship matches M1.2. The separate E1.0 175A feeder basis and DOAS-2 voltage-drop conflict remain held."
          },
          {
            "id": "PASS-06",
            "status": "PASS",
            "topic": "Emergency and generator source chain",
            "evidence": [
              "EP is fed from MDP/GENSET via ATS.",
              "Both MDP and generator blocks feed EP at 250A/3P.",
              "The selected 163kVA generator matches E1.0/E5.0."
            ],
            "conclusion": "The normal/emergency source topology and generator size reconcile."
          },
          {
            "id": "PASS-07",
            "status": "PASS",
            "topic": "EV load-capacity arithmetic",
            "evidence": [
              "L1.E schedules two 40A/2P EV branches at 7.2kVA each.",
              "Connected load is 14.4kVA and 125% demand is 18.0kVA, matching E1.0's service-load basis."
            ],
            "conclusion": "Capacity for two stations is represented; installed-versus-future scope remains separately held."
          },
          {
            "id": "PASS-08",
            "status": "PASS",
            "topic": "COMcheck report capture",
            "evidence": [
              "E8.0 contains two interior and two exterior certificate pages.",
              "All allowed/proposed rows and fixture rows were captured by the primary audit."
            ],
            "conclusion": "The report inventory is complete even though its coordination and arithmetic require HOLD findings."
          },
          {
            "id": "PASS-09",
            "status": "PASS",
            "topic": "Interior printed totals",
            "evidence": [
              "Allowed rows total 24,522W.",
              "Proposed rows total 16,876W.",
              "The exact reduction is 31.1802%, consistent with the printed 31% PASS statement."
            ],
            "conclusion": "The interior top-level printed totals reconcile to the report rows."
          },
          {
            "id": "PASS-10",
            "status": "PASS",
            "topic": "Selected interior fixture aggregates",
            "evidence": [
              "R11 totals 97 on plans and COMcheck.",
              "PA-204 totals 111 on plans and COMcheck.",
              "S02 totals 18 on plans and COMcheck.",
              "GR-203 totals 107 on the mapped guestroom basis and COMcheck."
            ],
            "conclusion": "These four fixture aggregates reconcile without creating additional installed quantities."
          },
          {
            "id": "PASS-11",
            "status": "PASS",
            "topic": "Roof maintenance-receptacle count/source",
            "evidence": [
              "E3.5 has three WP GFI receptacles on L5.A-34 adjacent to the three roof equipment occurrences.",
              "E6.0 schedules RCPTS - ROOF at 540VA, consistent with three 180VA loads."
            ],
            "conclusion": "Three roof maintenance-receptacle plan occurrences are supported; E7.0 details add zero additional occurrences."
          },
          {
            "id": "PASS-12",
            "status": "PASS",
            "topic": "E7.0 reference destination and quantity policy",
            "evidence": [
              "E1.1 Note 7 resolves to E7.0 Detail 1.",
              "All eight E7.0 details are NTS.",
              "No plan occurrence count is printed in any detail."
            ],
            "conclusion": "The detail-reference chain is captured and reference graphics are correctly excluded from installed totals."
          },
          {
            "id": "HOLD-01",
            "status": "HOLD",
            "topic": "Incomplete E6.2 on-sheet index",
            "evidence": [
              "The printed index lists L1.E, MDP, PP and SP.",
              "EP and GENSET PANEL (BUILT-IN) blocks are visibly present but omitted."
            ],
            "requiredResolution": "Correct the panel index or explicitly state why the two blocks are excluded."
          },
          {
            "id": "HOLD-02",
            "status": "HOLD",
            "topic": "L2 floor-label conflict",
            "evidence": [
              "E6.2 labels L2.A and L2.B as 3RD FLOOR.",
              "E6.1 and E3.1 place those panels on the second floor."
            ],
            "requiredResolution": "Correct the MDP feeder descriptions or issue a controlling clarification."
          },
          {
            "id": "HOLD-03",
            "status": "HOLD",
            "topic": "Broken generator-panel note",
            "evidence": [
              "The fire-pump control-panel row cites NOTE 2.",
              "The generator block prints only NOTE 1."
            ],
            "requiredResolution": "Provide the intended Note 2 and reconcile fire-pump breaker/conductor requirements."
          },
          {
            "id": "HOLD-04",
            "status": "HOLD",
            "topic": "MDP elevator load-basis conflicts",
            "evidence": [
              "The NEC 220 row says one 30HP elevator at 26.4kVA but prints 52.8kVA connected.",
              "The generator block states two elevators for 52.8kVA.",
              "The largest-motor row identifies 26.4kVA but prints 45.0kVA connected and 56.3kVA demand."
            ],
            "requiredResolution": "Issue a traceable two-elevator and largest-motor calculation basis."
          },
          {
            "id": "HOLD-05",
            "status": "HOLD",
            "topic": "Fault-current and supplier verification",
            "evidence": [
              "E6.2 prints 65kA MDP, 42kA L1.E/EP/generator, 30kA PP and 10kA SP ratings.",
              "General notes make all AIC values conditional on utility/transformer fault current.",
              "HVAC, elevator, kitchen, pool and fire-pump sizes are field/vendor verification items."
            ],
            "requiredResolution": "Obtain utility fault current and final supplier data, then revalidate AIC, breakers, conductors and equipment ratings."
          },
          {
            "id": "HOLD-06",
            "status": "HOLD",
            "topic": "Unverified emergency/elevator calculation coverage",
            "evidence": [
              "EP schedules Elevator 1 and Elevator 2 at 125A/3P.",
              "Prior E1.0A evidence calculates Elevator 1 but does not provide an independently traceable Elevator 2 short-circuit/voltage-drop chain."
            ],
            "requiredResolution": "Provide the missing Elevator 2 calculation/source chain and verify ATS details."
          },
          {
            "id": "HOLD-07",
            "status": "HOLD",
            "topic": "L1.E unresolved schedule details",
            "evidence": [
              "ACCU-1.3's wire-size cell is blank/ambiguous.",
              "Displayed L1.E connected and demand code sums each differ from printed totals by 1VA."
            ],
            "requiredResolution": "Clarify the conductor and issue traceable unrounded load totals; do not infer either value."
          },
          {
            "id": "HOLD-08",
            "status": "HOLD",
            "topic": "EV installed-versus-future scope",
            "evidence": [
              "L1.E schedules two EV branches and E1.0 includes two-station capacity.",
              "E5.0 contains future rough-in language and an annotation requiring at least two stations."
            ],
            "requiredResolution": "State whether two chargers are installed now, future only, or split scope, and identify final locations."
          },
          {
            "id": "HOLD-09",
            "status": "HOLD",
            "topic": "Inherited DOAS feeder and voltage-drop conflict",
            "evidence": [
              "E6.2 confirms 150A/3P, #2/0 feeders for both DOAS units.",
              "M1.2 prints a 150A maximum fuse, while prior E1.0 reconciliation retains a 175A feeder basis.",
              "E1.0A prints DOAS-2 at 310ft, 6.78V and 3.26%."
            ],
            "requiredResolution": "Coordinate the 150A/175A bases and revise or formally accept the DOAS-2 branch so the governing voltage-drop criterion is satisfied."
          },
          {
            "id": "HOLD-10",
            "status": "HOLD",
            "topic": "Interior COMcheck guestroom mapping",
            "evidence": [
              "COMcheck uses G10 quantity 341 while E1.2/E4.0/E4.1 use GR10.",
              "COMcheck S21 is 224 while the 107-room prototype mapping produces 228.",
              "GR-203 reconciles at 107."
            ],
            "requiredResolution": "Correct the G10/GR10 designation and reconcile the four missing S21 fixtures in the COMcheck model."
          },
          {
            "id": "HOLD-11",
            "status": "HOLD",
            "topic": "Interior COMcheck common-area mismatches",
            "evidence": [
              "R01 is 62 in COMcheck versus 59 visible plan occurrences.",
              "E2.4 plots one S04 with no E1.2 definition.",
              "COMcheck has no S04 row and its S01 total of 13 appears to combine 12 S01 occurrences with the unresolved S04."
            ],
            "requiredResolution": "Map every modeled common-area fixture to a plan occurrence and issue the missing S04 definition or a written tag correction."
          },
          {
            "id": "HOLD-12",
            "status": "HOLD",
            "topic": "Interior COMcheck displayed-watt arithmetic",
            "evidence": [
              "G10 prints 341 x 12W but 4,262W proposed; the displayed product is 4,092W.",
              "Eight additional rows differ from quantity times displayed integer fixture watts."
            ],
            "requiredResolution": "Provide the actual unrounded fixture input wattages or rerun the report with traceable displayed values."
          },
          {
            "id": "HOLD-13",
            "status": "HOLD",
            "topic": "Exterior COMcheck site-lighting omission",
            "evidence": [
              "COMcheck models 6 pole arrangements and 9 heads and contains no SB1.",
              "E5.0/E5.1 contain 16 arrangements and 23 heads, including three SB1 arrangements/six heads.",
              "The model is short 14 heads."
            ],
            "requiredResolution": "Rerun exterior COMcheck using the coordinated 23-head arrangement and every tag/optic/shield condition."
          },
          {
            "id": "HOLD-14",
            "status": "HOLD",
            "topic": "Exterior COMcheck other fixture quantities",
            "evidence": [
              "R02 is 19 in COMcheck but only one E2.0 occurrence is visible and its quantity is deferred to architectural/prototype confirmation.",
              "S03 is 14 in COMcheck versus 15 visible E2.0 occurrences."
            ],
            "requiredResolution": "Supply a location-by-location exterior fixture map and reconcile R02 and S03."
          },
          {
            "id": "HOLD-15",
            "status": "HOLD",
            "topic": "COMcheck code and project identity",
            "evidence": [
              "Certificates state 2021 IECC while engineering captions state 2023 Florida - 8th Edition.",
              "COMcheck project ID is 24-06-16 while title-block project number is 210729.",
              "Owner/Agent and Designer/Contractor fields are blank."
            ],
            "requiredResolution": "Confirm governing code equivalence/applicability, identify the project-ID relationship and complete the responsible-party fields."
          },
          {
            "id": "HOLD-16",
            "status": "HOLD",
            "topic": "Exterior luminaire procurement/photometric basis",
            "evidence": [
              "E1.2/E5.2 indicate JPL-1, 3000K and 56W; E5.2 leaves mounting and finish unselected.",
              "E5.1 uses 4000K NV-description photometric rows at 19ft and differing standard/HSS lumen outputs."
            ],
            "requiredResolution": "Issue one coordinated catalog/optic/HSS/CCT/output/mounting/finish basis and rerun or confirm photometrics and COMcheck."
          },
          {
            "id": "HOLD-17",
            "status": "HOLD",
            "topic": "Firestop tested-system and occurrence chain",
            "evidence": [
              "E7.0 Details 5, 7 and 8 cite UL/manufacturer systems but do not print complete tested-system/design identifiers.",
              "No project penetration/location register is provided.",
              "Detail 8 is F=4hr and T=0hr."
            ],
            "requiredResolution": "Select listed assemblies for each actual substrate and penetrating-item condition, map every occurrence, and obtain required acceptance."
          },
          {
            "id": "HOLD-18",
            "status": "HOLD",
            "topic": "Maintenance-receptacle detail applicability",
            "evidence": [
              "E7.0 Detail 3 uses a pitch-pocket EMT/Sealtight transition while Detail 6 routes Sealtight inside the curb.",
              "The sheet does not assign one condition to each of the three roof occurrences.",
              "E3.2/E3.4 above-ceiling maintenance receptacles and C.P/HP tags are not roof assemblies and their served equipment remains undefined."
            ],
            "requiredResolution": "Provide a project-specific detail/location matrix and define the non-roof C.P/HP maintenance loads and circuits."
          },
          {
            "id": "HOLD-19",
            "status": "HOLD",
            "topic": "DOAS load-code classification conflict",
            "evidence": [
              "DOAS-1 is coded LGR on MDP-44/46/48.",
              "Otherwise-identical DOAS-2 is coded AC on MDP-50/52/54.",
              "Each prints 15,011VA per phase, 150A/3P and #2/0."
            ],
            "requiredResolution": "Confirm the intended demand/load-code classification and recalculate if necessary."
          },
          {
            "id": "HOLD-20",
            "status": "HOLD",
            "topic": "PP food-service scope and omissions",
            "evidence": [
              "E3.0 identifies optional/future qualifiers for items including 20, 25 and 29, but PP lists them as ordinary active loads.",
              "E3.0 food-service items 35, 36 and 37 have no PP row."
            ],
            "requiredResolution": "Preserve optional/future scope explicitly and assign or formally remove items 35, 36 and 37."
          },
          {
            "id": "HOLD-21",
            "status": "HOLD",
            "topic": "Unnumbered EUH identity",
            "evidence": [
              "L1.E circuits 26/28 print only EUH.",
              "Prior mechanical evidence contains more than one EUH designation."
            ],
            "requiredResolution": "Identify the exact EUH tag served by L1.E-26/28."
          },
          {
            "id": "HOLD-22",
            "status": "HOLD",
            "topic": "ATS identifier and rating absent",
            "evidence": [
              "EP header says MDP/GENSET VIA ATS.",
              "No ATS tag or rating is printed in the E6.2 schedule block."
            ],
            "requiredResolution": "Provide the ATS identifier, rating and coordinated source/feeder details."
          }
        ],
        "quantityAndDuplicateRules": [
          {
            "source": "E6.2 panel and feeder rows",
            "rule": "Use as source/load relationships. Do not add feeder-row destinations to the already counted downstream panels or equipment."
          },
          {
            "source": "E6.2 L1.E equipment rows",
            "rule": "Reconcile to M1.1 equipment identities; do not add schedule occurrences to mechanical plan occurrences."
          },
          {
            "source": "E6.2 PP and SP",
            "rule": "Schedule/load allocation only. SP downstream pool scope is by separate pool permit per Note 3."
          },
          {
            "source": "E7.0 details",
            "rule": "Eight NTS reference definitions, zero installed quantity. Apply only to independently plotted applicable occurrences."
          },
          {
            "source": "E8.0 interior fixture quantity 1,089",
            "rule": "Compliance-model aggregate only; do not add to E2.x installed plan totals."
          },
          {
            "source": "E8.0 exterior pole quantities",
            "rule": "Compliance-model arrangements/heads only; do not add to the certified E5.0/E5.1 16-arrangement/23-head plan and schedule quantities."
          },
          {
            "source": "E5.1 photometric data",
            "rule": "Use 526 unique plan-region readings for analysis coverage. The 13 schedule decimals and all readings add zero fixtures."
          },
          {
            "source": "Typical and schedule definitions",
            "rule": "Do not apply a multiplier unless a governing room/equipment/location matrix explicitly establishes it."
          }
        ],
        "releaseChecks": [
          {
            "status": "PASS",
            "item": "All 15 E1.0 branch panelboards have schedule content across E6.0-E6.2."
          },
          {
            "status": "PASS",
            "item": "MDP destinations, L1.E mechanical counts and both DOAS source/protection chains are captured."
          },
          {
            "status": "PASS",
            "item": "All eight E7.0 NTS details and all four E8.0 certificate pages are included without additive reference quantities."
          },
          {
            "status": "PASS",
            "item": "Three roof maintenance receptacles reconcile from E3.5 to E6.0 L5.A-34; details add zero occurrences."
          },
          {
            "status": "HOLD",
            "item": "Correct E6.2 index omissions and L2.A/L2.B floor labels."
          },
          {
            "status": "HOLD",
            "item": "Repair generator Note 2 and issue traceable elevator/largest-motor calculations."
          },
          {
            "status": "HOLD",
            "item": "Obtain utility fault-current and final supplier data; resolve ACCU-1.3 conductor, Elevator 2 calculation and DOAS-2 voltage drop."
          },
          {
            "status": "HOLD",
            "item": "Resolve EV installed-versus-future scope and retain SP downstream pool work outside the current permit total."
          },
          {
            "status": "HOLD",
            "item": "Correct COMcheck G10/GR10, S21, R01 and S04 relationships and make displayed fixture wattage inputs traceable."
          },
          {
            "status": "HOLD",
            "item": "Rerun exterior COMcheck for all 23 site-lighting heads, including SB1, and reconcile R02/S03."
          },
          {
            "status": "HOLD",
            "item": "Coordinate COMcheck code/project identity and exterior luminaire catalog/CCT/output/mounting/finish data."
          },
          {
            "status": "HOLD",
            "item": "Provide project-specific tested firestop systems, penetration locations and a roof/non-roof maintenance-detail applicability matrix."
          }
        ],
        "validation": {
          "jsonValidated": true,
          "readOnlyReview": true,
          "siteCheckoutEdited": false,
          "sitesToolsUsed": false,
          "published": false,
          "agentsSpawned": false,
          "sourceSheetsReviewed": [
            "E6.2",
            "E7.0",
            "E8.0"
          ],
          "primaryAuditsIncorporated": [
            "E6.2",
            "E7.0",
            "E8.0"
          ],
          "e62AuditBasis": "Primary and independent secondary audits reconciled.",
          "exactTotalsIncorporated": {
            "branchPanelboardsScheduled": 15,
            "e62ScheduleBlocks": 6,
            "e62CircuitPositions": 222,
            "e62PanelIndexEntries": 4,
            "e62GeneratorCalculationRows": 11,
            "e62MdpFeederCalculationRows": 15,
            "e70Details": 8,
            "e80InteriorFixtureRows": 27,
            "e80InteriorModeledQuantity": 1089,
            "e80ExteriorModeledSiteHeads": 9,
            "e51CertifiedSiteHeads": 23,
            "e51PhotometricPoints": 526
          },
          "status": "validated; takeoff completeness PASS and coordination/procurement release HOLD"
        }
      }
    }
  },
  "issues": [
    {
      "id": "1",
      "title": "High",
      "text": "{\"id\": 1, \"severity\": \"HIGH\", \"title\": \"GENSET fire-pump row references nonexistent note 2\", \"evidence\": \"GENSET circuits 1/3/5 print NOTE 2, but the GENSET block contains only note 1.\", \"status\": \"BROKEN_REFERENCE\"}"
    },
    {
      "id": "2",
      "title": "Medium",
      "text": "{\"id\": 2, \"severity\": \"MEDIUM\", \"title\": \"Panel index is incomplete\", \"evidence\": \"Local index lists only L1.E, MDP, PP and SP; EP and GENSET PANEL (BUILT-IN), both scheduled on this sheet, are omitted. Other MDP-fed floor panels are also absent.\", \"status\": \"INCOMPLETE_INDEX\"}"
    },
    {
      "id": "3",
      "title": "Medium",
      "text": "{\"id\": 3, \"severity\": \"MEDIUM\", \"title\": \"L2.A and L2.B are labeled 3RD FLOOR\", \"evidence\": \"MDP circuits 37-47 print PANEL L2.A and PANEL L2.B with note (3RD FLOOR), inconsistent with their L2 naming and the separate L3.A/L3.B third-floor feeders.\", \"status\": \"PRINTED_CONFLICT\"}"
    },
    {
      "id": "4",
      "title": "High",
      "text": "{\"id\": 4, \"severity\": \"HIGH\", \"title\": \"MDP elevator feeder-calculation row is internally inconsistent\", \"evidence\": \"Row 5.2 says one 30HP elevator at 26.4 kVA @100% but prints 52.8 kVA connected and sizing load; 52.8 corresponds to two such loads.\", \"status\": \"CALCULATION_AMBIGUITY\"}"
    },
    {
      "id": "5",
      "title": "Medium",
      "text": "{\"id\": 5, \"severity\": \"MEDIUM\", \"title\": \"DOAS load-code classification differs\", \"evidence\": \"DOAS-1 is coded LGR on circuits 44/46/48 while otherwise-identical DOAS-2 is coded AC on circuits 50/52/54; each prints 15,011 VA/phase, 150/3 breaker and 2/0 wire.\", \"status\": \"CLASSIFICATION_CONFLICT\"}"
    },
    {
      "id": "6",
      "title": "High",
      "text": "{\"id\": 6, \"severity\": \"HIGH\", \"title\": \"DOAS coordination conflict remains open\", \"evidence\": \"E6.2 confirms 150A/3P, 2/0 feeders; earlier E1.0A/E3.5 reconciliation records a 175A basis and DOAS-2 voltage drop of 3.26%, above the stated 3% limit, while M1.2 lists 150A maximum fuse.\", \"status\": \"CROSS_SHEET_CONFLICT\"}"
    },
    {
      "id": "7",
      "title": "Medium",
      "text": "{\"id\": 7, \"severity\": \"MEDIUM\", \"title\": \"PP does not preserve optional/future qualifiers\", \"evidence\": \"E3.0 food-service evidence identified optional/future basis for items including 20, 25 and 29; PP schedules them as ordinary active circuit loads without those qualifiers.\", \"status\": \"SCOPE_AMBIGUITY\"}"
    },
    {
      "id": "8",
      "title": "Medium",
      "text": "{\"id\": 8, \"severity\": \"MEDIUM\", \"title\": \"Food-service items 35, 36 and 37 have no PP row\", \"evidence\": \"They appear in prior E3.0 dry schedule evidence but are absent from all PP circuit descriptions.\", \"status\": \"CROSS_SHEET_OMISSION\"}"
    },
    {
      "id": "9",
      "title": "Low",
      "text": "{\"id\": 9, \"severity\": \"LOW\", \"title\": \"L1.E EUH tag is not uniquely numbered\", \"evidence\": \"Circuits 26/28 print only EUH; prior first-floor/mechanical evidence includes more than one EUH designation, so equipment identity cannot be certified from E6.2 alone.\", \"status\": \"AMBIGUOUS_TAG\"}"
    },
    {
      "id": "10",
      "title": "High",
      "text": "{\"id\": 10, \"severity\": \"HIGH\", \"title\": \"Fault-current basis remains field-dependent\", \"evidence\": \"General note 2 requires final current values from the utility; scheduled AIC values of 10, 30, 42 and 65 kA are not a substitute for the final verified available-fault-current calculation.\", \"status\": \"OPEN_COORDINATION\"}"
    },
    {
      "id": "11",
      "title": "Medium",
      "text": "{\"id\": 11, \"severity\": \"MEDIUM\", \"title\": \"Emergency source path lacks an ATS identifier\", \"evidence\": \"EP header says MDP/GENSET VIA ATS, but no ATS tag or rating is printed in the panel schedule block.\", \"status\": \"AMBIGUOUS_REFERENCE\"}"
    },
    {
      "id": "12",
      "title": "Low",
      "text": "{\"id\": 12, \"severity\": \"LOW\", \"title\": \"PP equipment basis requires supplier verification\", \"evidence\": \"PP note 1 directs field verification of breaker and cable sizes with the kitchen supplier; schedule values are not released fabrication values.\", \"status\": \"VERIFY\"}"
    },
    {
      "id": "13",
      "title": "Low",
      "text": "{\"id\": 13, \"severity\": \"LOW\", \"title\": \"SP branch scope is not installed by this permit\", \"evidence\": \"SP note 3 states breakers and branch circuits are installed under the pool permit; only panel and ground are covered here.\", \"status\": \"PERMIT_SCOPE\"}"
    }
  ]
}