E6.1 ELECTRICAL PANELS SCHEDULE Engineering PDF page 54 Issued November 22, 2024 COMPLETE SOURCE TEXT LAYER { "schemaVersion": "1.0", "sheet": "E6.1", "title": "ELECTRICAL PANELS SCHEDULE", "engineeringPdfPage": 54, "scale": "NTS", "measurements": { "drawnPathLF": null, "conductorLF": null, "conduitLF": null, "reason": "Panel-schedule sheet is not to scale and contains no plan routing geometry." }, "source": { "pdf": "/workspace/sites/ssx-cover-release/source-plans/engineering.pdf", "providedRender": "/workspace/sites/ssx-cover-release/tmp/pdfs/next3-e52-e61/source-54.png", "validatedRender": "/workspace/scratch/e9eeb133d6f5/e61-crops/e61-72.png", "fullSourcePixels": [ 10800, 7200 ], "pdfPoints": [ 2592, 1728 ], "reviewMethod": "full-sheet raster review plus high-resolution schedule crops; printed blanks/arrows retained" }, "coordinateSpace": { "width": 1920, "height": 1280, "origin": "top-left", "pdfPointToNormalized": 0.7407407407407407 }, "panelIndex": [ [ "L2.A", "L1.B" ], [ "L2.B", "L1.C" ], [ "L1.A", "L1.D" ] ], "markers": [ { "id": "S01", "category": "panel_schedule", "tag": "L2.A", "normalizedCenter": [ 461.11, 222.22 ], "normalizedRegion": [ 81.48, 74.07, 840.74, 370.37 ] }, { "id": "S02", "category": "panel_schedule", "tag": "L1.B", "normalizedCenter": [ 1225.92, 222.22 ], "normalizedRegion": [ 851.85, 74.07, 1600.0, 370.37 ] }, { "id": "S03", "category": "panel_schedule", "tag": "L2.B", "normalizedCenter": [ 461.11, 531.49 ], "normalizedRegion": [ 81.48, 377.78, 840.74, 685.19 ] }, { "id": "S04", "category": "panel_schedule", "tag": "L1.C", "normalizedCenter": [ 1225.92, 574.08 ], "normalizedRegion": [ 851.85, 377.78, 1600.0, 770.37 ] }, { "id": "S05", "category": "panel_schedule", "tag": "L1.A", "normalizedCenter": [ 461.11, 840.74 ], "normalizedRegion": [ 81.48, 688.89, 840.74, 992.59 ] }, { "id": "S06", "category": "panel_schedule", "tag": "L1.D", "normalizedCenter": [ 1225.92, 925.92 ], "normalizedRegion": [ 851.85, 770.37, 1600.0, 1081.48 ] }, { "id": "S07", "category": "panel_index", "tag": "PANEL INDEX", "normalizedCenter": [ 1674.07, 166.67 ], "normalizedRegion": [ 1600.0, 74.07, 1748.15, 333.33 ] }, { "id": "S08", "category": "general_notes", "tag": "NOTES 1-3", "normalizedCenter": [ 460.74, 1048.15 ], "normalizedRegion": [ 81.48, 977.78, 840.74, 1122.22 ] } ], "panels": [ { "name": "L2.A", "fedFrom": "MDP", "region": [ 81.48, 74.07, 840.74, 370.37 ], "header": { "projectName": "HOME 2 SUITES, BRADENTON, FL", "projectNumber": "#210729", "voltage": "120/208V, 3PH, 4W", "enclosure": "NEMA-1", "aicRating": "22 KA", "bus": "250 AMP", "busMaterial": "COPPER", "mains": "250 AMP M.L.O", "mounting": "SURFACE MOUNTED", "location": "STORAGE 2ND FLOOR" }, "rows": [ { "circuit": 1, "side": "odd", "loadType": "SUB", "description": "PANEL \"A\" / 201 - KING STUDIO", "notes": [], "poles": 2, "breaker": "80/2", "wire": 3, "voltAmps": 6694, "printedState": "explicit" }, { "circuit": 2, "side": "even", "loadType": "SUB", "description": "PANEL \"B\" / 207 - ACC KING ONE BEDROOM", "notes": [], "poles": 2, "breaker": "100/2", "wire": 2, "voltAmps": 8522, "printedState": "explicit" }, { "circuit": 3, "side": "odd", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 6694, "printedState": "continuation" }, { "circuit": 4, "side": "even", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 8522, "printedState": "continuation" }, { "circuit": 5, "side": "odd", "loadType": "SUB", "description": "PANEL \"B\" / 202 - KING ONE BEDROOM", "notes": [], "poles": 2, "breaker": "100/2", "wire": 2, "voltAmps": 8443, "printedState": "explicit" }, { "circuit": 6, "side": "even", "loadType": "SUB", "description": "PANEL \"A\" / 208 - KING STUDIO", "notes": [], "poles": 2, "breaker": "80/2", "wire": 3, "voltAmps": 6694, "printedState": "explicit" }, { "circuit": 7, "side": "odd", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 8443, "printedState": "continuation" }, { "circuit": 8, "side": "even", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 6694, "printedState": "continuation" }, { "circuit": 9, "side": "odd", "loadType": "SUB", "description": "PANEL \"A\" / 203 - KING STUDIO", "notes": [], "poles": 2, "breaker": "80/2", "wire": 3, "voltAmps": 6694, "printedState": "explicit" }, { "circuit": 10, "side": "even", "loadType": "SUB", "description": "PANEL \"A\" / 209 - KING STUDIO", "notes": [], "poles": 2, "breaker": "80/2", "wire": 3, "voltAmps": 6694, "printedState": "explicit" }, { "circuit": 11, "side": "odd", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 6694, "printedState": "continuation" }, { "circuit": 12, "side": "even", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 6694, "printedState": "continuation" }, { "circuit": 13, "side": "odd", "loadType": "SUB", "description": "PANEL \"A\" / 204 - KING STUDIO", "notes": [], "poles": 2, "breaker": "80/2", "wire": 3, "voltAmps": 6694, "printedState": "explicit" }, { "circuit": 14, "side": "even", "loadType": "SUB", "description": "PANEL \"A\" / 210 - KING STUDIO", "notes": [], "poles": 2, "breaker": "80/2", "wire": 3, "voltAmps": 6694, "printedState": "explicit" }, { "circuit": 15, "side": "odd", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 6694, "printedState": "continuation" }, { "circuit": 16, "side": "even", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 6694, "printedState": "continuation" }, { "circuit": 17, "side": "odd", "loadType": "SUB", "description": "PANEL \"A\" / 205 - KING STUDIO", "notes": [], "poles": 2, "breaker": "80/2", "wire": 3, "voltAmps": 6694, "printedState": "explicit" }, { "circuit": 18, "side": "even", "loadType": "SUB", "description": "PANEL \"A\" / 211 - KING STUDIO", "notes": [], "poles": 2, "breaker": "80/2", "wire": 3, "voltAmps": 6694, "printedState": "explicit" }, { "circuit": 19, "side": "odd", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 6694, "printedState": "continuation" }, { "circuit": 20, "side": "even", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 6694, "printedState": "continuation" }, { "circuit": 21, "side": "odd", "loadType": "SUB", "description": "PANEL \"A\" / 206 - KING STUDIO", "notes": [], "poles": 2, "breaker": "80/2", "wire": 3, "voltAmps": 6694, "printedState": "explicit" }, { "circuit": 22, "side": "even", "loadType": "SUB", "description": "PANEL \"A\" / 212 - KING STUDIO", "notes": [], "poles": 2, "breaker": "80/2", "wire": 3, "voltAmps": 6694, "printedState": "explicit" }, { "circuit": 23, "side": "odd", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 6694, "printedState": "continuation" }, { "circuit": 24, "side": "even", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 6694, "printedState": "continuation" }, { "circuit": 25, "side": "odd", "loadType": "SUB", "description": "SPARE", "notes": [], "poles": 2, "breaker": "80/2", "wire": null, "voltAmps": null, "printedState": "explicit" }, { "circuit": 26, "side": "even", "loadType": "REC", "description": "RCPTS - CORRIDOR", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 900, "printedState": "explicit" }, { "circuit": 27, "side": "odd", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": null, "printedState": "continuation" }, { "circuit": 28, "side": "even", "loadType": "REC", "description": "RCPTS - CORRIDOR/STORAGE", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 720, "printedState": "explicit" }, { "circuit": 29, "side": "odd", "loadType": null, "description": "SPACE ONLY", "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "space-only" }, { "circuit": 30, "side": "even", "loadType": "EQUIP", "description": "FIRE SMOKE DAMPER", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 500, "printedState": "explicit" }, { "circuit": 31, "side": "odd", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 32, "side": "even", "loadType": "EQUIP", "description": "ICE MACHINE", "notes": [ "(CLASS A GFCI BREAKER)" ], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 1500, "printedState": "explicit" }, { "circuit": 33, "side": "odd", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 34, "side": "even", "loadType": null, "description": "SPARE", "notes": [], "poles": 1, "breaker": "20/1", "wire": null, "voltAmps": null, "printedState": "explicit" }, { "circuit": 35, "side": "odd", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 36, "side": "even", "loadType": null, "description": null, "notes": [], "poles": 1, "breaker": "↓", "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 37, "side": "odd", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 38, "side": "even", "loadType": null, "description": null, "notes": [], "poles": 1, "breaker": "↓", "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 39, "side": "odd", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 40, "side": "even", "loadType": null, "description": null, "notes": [], "poles": 1, "breaker": "↓", "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 41, "side": "odd", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 42, "side": "even", "loadType": null, "description": "↓", "notes": [], "poles": 1, "breaker": "↓", "wire": null, "voltAmps": null, "printedState": "continuation" } ], "phasePairLoads": [ { "oddCircuit": 1, "evenCircuit": 2, "phase": "A", "printedVA": 15216 }, { "oddCircuit": 3, "evenCircuit": 4, "phase": "B", "printedVA": 15216 }, { "oddCircuit": 5, "evenCircuit": 6, "phase": "C", "printedVA": 15137 }, { "oddCircuit": 7, "evenCircuit": 8, "phase": "A", "printedVA": 15137 }, { "oddCircuit": 9, "evenCircuit": 10, "phase": "B", "printedVA": 13388 }, { "oddCircuit": 11, "evenCircuit": 12, "phase": "C", "printedVA": 13388 }, { "oddCircuit": 13, "evenCircuit": 14, "phase": "A", "printedVA": 13388 }, { "oddCircuit": 15, "evenCircuit": 16, "phase": "B", "printedVA": 13388 }, { "oddCircuit": 17, "evenCircuit": 18, "phase": "C", "printedVA": 13388 }, { "oddCircuit": 19, "evenCircuit": 20, "phase": "A", "printedVA": 13388 }, { "oddCircuit": 21, "evenCircuit": 22, "phase": "B", "printedVA": 13388 }, { "oddCircuit": 23, "evenCircuit": 24, "phase": "C", "printedVA": 13388 }, { "oddCircuit": 25, "evenCircuit": 26, "phase": "A", "printedVA": 900 }, { "oddCircuit": 27, "evenCircuit": 28, "phase": "B", "printedVA": 720 }, { "oddCircuit": 29, "evenCircuit": 30, "phase": "C", "printedVA": 500 }, { "oddCircuit": 31, "evenCircuit": 32, "phase": "A", "printedVA": 1500 }, { "oddCircuit": 33, "evenCircuit": 34, "phase": "B", "printedVA": 0 }, { "oddCircuit": 35, "evenCircuit": 36, "phase": "C", "printedVA": 0 }, { "oddCircuit": 37, "evenCircuit": 38, "phase": "A", "printedVA": 0 }, { "oddCircuit": 39, "evenCircuit": 40, "phase": "B", "printedVA": 0 }, { "oddCircuit": 41, "evenCircuit": 42, "phase": "C", "printedVA": 0 } ], "loadCodes": [ { "code": "LTG", "connected": 0, "description": "LTG =125% LIGHTING LOAD: (N/A)", "demand": 0 }, { "code": "REC", "connected": 1620, "description": "REC = RCPTS LOAD (100% FIRST 10KVA +50% REMAIN)", "demand": 1620 }, { "code": "EQUIP", "connected": 2000, "description": "EQUIP = EQUIPMENT LOAD", "demand": 2000 }, { "code": "AC", "connected": 0, "description": "AC = HVAC LOAD : (N/A)", "demand": 0 }, { "code": "HTG", "connected": 0, "description": "HTG = HEATING LOAD : (N/A)", "demand": 0 }, { "code": "LGR", "connected": 0, "description": "LGR = 125% LARGEST MOTOR : (N/A)", "demand": 0 }, { "code": "KIT", "connected": 0, "description": "KIT = KITCHEN LOAD : (N/A)", "demand": 0 }, { "code": "SUB", "connected": 167809, "description": "SUB = SUB PANEL x 41% PF(FOR 12 UNITS)", "demand": 68802 }, { "code": "GLTG", "connected": 0, "description": "GLTG = GUESTROOM LIGHTING LOAD: N/A", "demand": 0 }, { "code": "EVCS", "connected": 0, "description": "EVCS = 125% ELECTRIC VEHICLE CHARGING STATION : (N/A)", "demand": 0 } ], "totals": { "connectedVA": 171429, "connectedAmps": 476, "demandVA": 72422, "demandAmps": 201, "connectedPhaseKVA": [ 59.53, 56.1, 55.8 ], "connectedPhaseAmps": [ 496.07, 467.5, 465.0 ], "demandPhaseKVA": [ 25.82, 23.43, 23.17 ], "demandPhaseAmps": [ 215.19, 195.22, 193.11 ] }, "panelSpecificNotes": [] }, { "name": "L1.B", "fedFrom": "MDP", "region": [ 851.85, 74.07, 1600.0, 370.37 ], "header": { "projectName": "HOME 2 SUITES, BRADENTON, FL", "projectNumber": "#210729", "voltage": "120/208V, 3PH, 4W", "enclosure": "NEMA-1", "aicRating": "30 KA", "bus": "100 AMP", "busMaterial": "COPPER", "mains": "100 AMP M.L.O", "mounting": "SURFACE MOUNTED", "location": "ELEC. RM. 1ST FLOOR" }, "rows": [ { "circuit": 1, "side": "odd", "loadType": "LTG", "description": "LTS - ELEC / MECH. RM", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 378, "printedState": "explicit" }, { "circuit": 2, "side": "even", "loadType": "LTG", "description": "MONUMENT SIGN", "notes": [ "(NOTE 1)", "(NOTE 2)" ], "poles": 1, "breaker": "20/1", "wire": 10, "voltAmps": 1200, "printedState": "explicit" }, { "circuit": 3, "side": "odd", "loadType": "LTG", "description": "LTS - RESTROOM/SALES", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 150, "printedState": "explicit" }, { "circuit": 4, "side": "even", "loadType": "LTG", "description": "↓", "notes": [], "poles": 1, "breaker": "↓", "wire": "↓", "voltAmps": 1200, "printedState": "continuation" }, { "circuit": 5, "side": "odd", "loadType": "LTG", "description": "LTS - LAUNDRY", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 432, "printedState": "explicit" }, { "circuit": 6, "side": "even", "loadType": "LTG", "description": "↓", "notes": [], "poles": 1, "breaker": "↓", "wire": "↓", "voltAmps": 1200, "printedState": "continuation" }, { "circuit": 7, "side": "odd", "loadType": "LTG", "description": "LTS - FITNESS/GUEST LAUNDRY", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 255, "printedState": "explicit" }, { "circuit": 8, "side": "even", "loadType": "LTG", "description": "LTS - SITE LIGHTING", "notes": [ "(NOTE 1)" ], "poles": 2, "breaker": "20/2", "wire": 10, "voltAmps": 140, "printedState": "explicit" }, { "circuit": 9, "side": "odd", "loadType": "LTG", "description": "LTS - LOBBY", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 400, "printedState": "explicit" }, { "circuit": 10, "side": "even", "loadType": "LTG", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 140, "printedState": "continuation" }, { "circuit": 11, "side": "odd", "loadType": "LTG", "description": "LTS - LOBBY", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 400, "printedState": "explicit" }, { "circuit": 12, "side": "even", "loadType": "LTG", "description": "LTS - SITE LIGHTING", "notes": [ "(NOTE 1)" ], "poles": 2, "breaker": "20/2", "wire": 10, "voltAmps": 112, "printedState": "explicit" }, { "circuit": 13, "side": "odd", "loadType": "LTG", "description": "LTS - CORRIDOR 1ST FL", "notes": [], "poles": 1, "breaker": "20/1", "wire": 10, "voltAmps": 340, "printedState": "explicit" }, { "circuit": 14, "side": "even", "loadType": "LTG", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 112, "printedState": "continuation" }, { "circuit": 15, "side": "odd", "loadType": "LTG", "description": "LTS - CORRIDOR 2ND FL", "notes": [], "poles": 1, "breaker": "20/1", "wire": 10, "voltAmps": 340, "printedState": "explicit" }, { "circuit": 16, "side": "even", "loadType": "LTG", "description": "BUILDING SIGN", "notes": [ "(NOTE 1)" ], "poles": 1, "breaker": "20/1", "wire": 10, "voltAmps": 1200, "printedState": "explicit" }, { "circuit": 17, "side": "odd", "loadType": "LTG", "description": "LTS - CORRIDOR 2ND FL", "notes": [], "poles": 1, "breaker": "20/1", "wire": 10, "voltAmps": 413, "printedState": "explicit" }, { "circuit": 18, "side": "even", "loadType": "LTG", "description": "LTS - EXTERIOR", "notes": [ "(NOTE 1)" ], "poles": 1, "breaker": "20/1", "wire": 10, "voltAmps": 324, "printedState": "explicit" }, { "circuit": 19, "side": "odd", "loadType": "LTG", "description": "LTS - CORRIDOR 3RD FL", "notes": [], "poles": 1, "breaker": "20/1", "wire": 10, "voltAmps": 413, "printedState": "explicit" }, { "circuit": 20, "side": "even", "loadType": "LTG", "description": "LTS - FLAG POLE", "notes": [ "(NOTE 1)" ], "poles": 1, "breaker": "20/1", "wire": 10, "voltAmps": 200, "printedState": "explicit" }, { "circuit": 21, "side": "odd", "loadType": "LTG", "description": "LTS - CORRIDOR 3RD FL", "notes": [], "poles": 1, "breaker": "20/1", "wire": 10, "voltAmps": 413, "printedState": "explicit" }, { "circuit": 22, "side": "even", "loadType": "LTG", "description": "LTS - EXTERIOR", "notes": [ "(NOTE 1)" ], "poles": 1, "breaker": "20/1", "wire": 10, "voltAmps": 300, "printedState": "explicit" }, { "circuit": 23, "side": "odd", "loadType": "LTG", "description": "LTS - CORRIDOR 3RD FL", "notes": [], "poles": 1, "breaker": "20/1", "wire": 10, "voltAmps": 413, "printedState": "explicit" }, { "circuit": 24, "side": "even", "loadType": "LTG", "description": "LTS - EXTERIOR", "notes": [ "(NOTE 1)" ], "poles": 1, "breaker": "20/1", "wire": 10, "voltAmps": 100, "printedState": "explicit" }, { "circuit": 25, "side": "odd", "loadType": "LTG", "description": "LTS - CORRIDOR 4TH FL", "notes": [], "poles": 1, "breaker": "20/1", "wire": 10, "voltAmps": 413, "printedState": "explicit" }, { "circuit": 26, "side": "even", "loadType": null, "description": "SPARE", "notes": [], "poles": 1, "breaker": "20/1", "wire": null, "voltAmps": null, "printedState": "explicit" }, { "circuit": 27, "side": "odd", "loadType": "LTG", "description": "LTS - CORRIDOR 4TH FL", "notes": [], "poles": 1, "breaker": "20/1", "wire": 10, "voltAmps": 413, "printedState": "explicit" }, { "circuit": 28, "side": "even", "loadType": null, "description": null, "notes": [], "poles": 1, "breaker": "↓", "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 29, "side": "odd", "loadType": "LTG", "description": "LTS - CORRIDOR 5TH FL", "notes": [], "poles": 1, "breaker": "20/1", "wire": 10, "voltAmps": 413, "printedState": "explicit" }, { "circuit": 30, "side": "even", "loadType": null, "description": null, "notes": [], "poles": 1, "breaker": "↓", "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 31, "side": "odd", "loadType": "LTG", "description": "LTS - CORRIDOR 5TH FL", "notes": [], "poles": 1, "breaker": "20/1", "wire": 10, "voltAmps": 413, "printedState": "explicit" }, { "circuit": 32, "side": "even", "loadType": null, "description": null, "notes": [], "poles": 1, "breaker": "↓", "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 33, "side": "odd", "loadType": "LTG", "description": "LTS - STAIRS", "notes": [], "poles": 1, "breaker": "20/1", "wire": 10, "voltAmps": 720, "printedState": "explicit" }, { "circuit": 34, "side": "even", "loadType": null, "description": "↓", "notes": [], "poles": 1, "breaker": "↓", "wire": null, "voltAmps": null, "printedState": "continuation" }, { "circuit": 35, "side": "odd", "loadType": null, "description": "SPACE ONLY", "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "space-only" }, { "circuit": 36, "side": "even", "loadType": null, "description": "SPACE ONLY", "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "space-only" }, { "circuit": 37, "side": "odd", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 38, "side": "even", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 39, "side": "odd", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 40, "side": "even", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 41, "side": "odd", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 42, "side": "even", "loadType": null, "description": "↓", "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "continuation" } ], "phasePairLoads": [ { "oddCircuit": 1, "evenCircuit": 2, "phase": "A", "printedVA": 1578 }, { "oddCircuit": 3, "evenCircuit": 4, "phase": "B", "printedVA": 1350 }, { "oddCircuit": 5, "evenCircuit": 6, "phase": "C", "printedVA": 1632 }, { "oddCircuit": 7, "evenCircuit": 8, "phase": "A", "printedVA": 395 }, { "oddCircuit": 9, "evenCircuit": 10, "phase": "B", "printedVA": 540 }, { "oddCircuit": 11, "evenCircuit": 12, "phase": "C", "printedVA": 512 }, { "oddCircuit": 13, "evenCircuit": 14, "phase": "A", "printedVA": 452 }, { "oddCircuit": 15, "evenCircuit": 16, "phase": "B", "printedVA": 1540 }, { "oddCircuit": 17, "evenCircuit": 18, "phase": "C", "printedVA": 737 }, { "oddCircuit": 19, "evenCircuit": 20, "phase": "A", "printedVA": 613 }, { "oddCircuit": 21, "evenCircuit": 22, "phase": "B", "printedVA": 713 }, { "oddCircuit": 23, "evenCircuit": 24, "phase": "C", "printedVA": 513 }, { "oddCircuit": 25, "evenCircuit": 26, "phase": "A", "printedVA": 413 }, { "oddCircuit": 27, "evenCircuit": 28, "phase": "B", "printedVA": 413 }, { "oddCircuit": 29, "evenCircuit": 30, "phase": "C", "printedVA": 413 }, { "oddCircuit": 31, "evenCircuit": 32, "phase": "A", "printedVA": 413 }, { "oddCircuit": 33, "evenCircuit": 34, "phase": "B", "printedVA": 720 }, { "oddCircuit": 35, "evenCircuit": 36, "phase": "C", "printedVA": 0 }, { "oddCircuit": 37, "evenCircuit": 38, "phase": "A", "printedVA": 0 }, { "oddCircuit": 39, "evenCircuit": 40, "phase": "B", "printedVA": 0 }, { "oddCircuit": 41, "evenCircuit": 42, "phase": "C", "printedVA": 0 } ], "loadCodes": [ { "code": "LTG", "connected": 12943, "description": "LTG =125% LIGHTING LOAD:", "demand": 16178 }, { "code": "REC", "connected": 0, "description": "REC = RCPTS LOAD : (N/A)", "demand": 0 }, { "code": "EQUIP", "connected": 0, "description": "EQUIP = EQUIPMENT LOAD : (N/A)", "demand": 0 }, { "code": "AC", "connected": 0, "description": "AC = HVAC LOAD : (N/A)", "demand": 0 }, { "code": "HTG", "connected": 0, "description": "HTG = HEATING LOAD : (N/A)", "demand": 0 }, { "code": "LGR", "connected": 0, "description": "LGR = 125% LARGEST MOTOR : (N/A)", "demand": 0 }, { "code": "KIT", "connected": 0, "description": "KIT = KITCHEN LOAD : (N/A)", "demand": 0 }, { "code": "SUB", "connected": 0, "description": "SUB = SUB PANEL x PF : (N/A)", "demand": 0 }, { "code": "GLTG", "connected": 0, "description": "GLTG = GUESTROOM LIGHTING LOAD: N/A", "demand": 0 }, { "code": "EVCS", "connected": 0, "description": "EVCS = 125% ELECTRIC VEHICLE CHARGING STATION : (N/A)", "demand": 0 } ], "totals": { "connectedVA": 12943, "connectedAmps": 36, "demandVA": 16178, "demandAmps": 45, "connectedPhaseKVA": [ 3.86, 5.27, 3.81 ], "connectedPhaseAmps": [ 32.19, 43.96, 31.71 ], "demandPhaseKVA": [ 4.83, 6.59, 4.76 ], "demandPhaseAmps": [ 40.23, 54.95, 39.64 ] }, "panelSpecificNotes": [ { "number": 1, "text": "CONTROLLED BY A 20A. MECH. HELD LIGHTING CONTACTORS WHICH IS CONTROLLED BY A 7-DAY, N-1 TIME CLOCK WITH 4 HRS BATTERIES IN PANEL L1.B." }, { "number": 2, "text": "PROVIDE HANDLE TIES FOR CIRCUIT BREAKERS TO DISCONNECT ALL UNGROUNDED CONDUCTORS SIMULTANEOUSLY ON MULTI-WIRE BRANCH CIRCUITS." } ] }, { "name": "L2.B", "fedFrom": "MDP", "region": [ 81.48, 377.78, 840.74, 685.19 ], "header": { "projectName": "HOME 2 SUITES, BRADENTON, FL", "projectNumber": "#210729", "voltage": "120/208V, 3PH, 4W", "enclosure": "NEMA-1", "aicRating": "22 KA", "bus": "250 AMP", "busMaterial": "COPPER", "mains": "250 AMP M.L.O", "mounting": "SURFACE MOUNTED", "location": "STORAGE 2ND FLOOR" }, "rows": [ { "circuit": 1, "side": "odd", "loadType": "SUB", "description": "PANEL \"A\" / 213 - KING STUDIO", "notes": [], "poles": 2, "breaker": "80/2", "wire": 3, "voltAmps": 6694, "printedState": "explicit" }, { "circuit": 2, "side": "even", "loadType": "SUB", "description": "PANEL \"A\" / 219 - KING STUDIO", "notes": [], "poles": 2, "breaker": "100/2", "wire": 2, "voltAmps": 8522, "printedState": "explicit" }, { "circuit": 3, "side": "odd", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 6694, "printedState": "continuation" }, { "circuit": 4, "side": "even", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 8522, "printedState": "continuation" }, { "circuit": 5, "side": "odd", "loadType": "SUB", "description": "PANEL \"A\" / 214 - KING STUDIO", "notes": [], "poles": 2, "breaker": "80/2", "wire": 3, "voltAmps": 6694, "printedState": "explicit" }, { "circuit": 6, "side": "even", "loadType": "SUB", "description": "PANEL \"A\" / 220 - DOUBLE QUEEN", "notes": [], "poles": 2, "breaker": "80/2", "wire": 3, "voltAmps": 6694, "printedState": "explicit" }, { "circuit": 7, "side": "odd", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 6694, "printedState": "continuation" }, { "circuit": 8, "side": "even", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 6694, "printedState": "continuation" }, { "circuit": 9, "side": "odd", "loadType": "SUB", "description": "PANEL \"A\" / 215 - KING STUDIO", "notes": [], "poles": 2, "breaker": "80/2", "wire": 3, "voltAmps": 6694, "printedState": "explicit" }, { "circuit": 10, "side": "even", "loadType": "SUB", "description": "PANEL \"A\" / 221 - KING STUDIO", "notes": [], "poles": 2, "breaker": "80/2", "wire": 3, "voltAmps": 6694, "printedState": "explicit" }, { "circuit": 11, "side": "odd", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 6694, "printedState": "continuation" }, { "circuit": 12, "side": "even", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 6694, "printedState": "continuation" }, { "circuit": 13, "side": "odd", "loadType": "SUB", "description": "PANEL \"A\" / 216 - DOUBLE QUEEN", "notes": [], "poles": 2, "breaker": "80/2", "wire": 3, "voltAmps": 6817, "printedState": "explicit" }, { "circuit": 14, "side": "even", "loadType": "SUB", "description": "PANEL \"A\" / 222 - DOUBLE QUEEN", "notes": [], "poles": 2, "breaker": "80/2", "wire": 3, "voltAmps": 6694, "printedState": "explicit" }, { "circuit": 15, "side": "odd", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 6817, "printedState": "continuation" }, { "circuit": 16, "side": "even", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 6694, "printedState": "continuation" }, { "circuit": 17, "side": "odd", "loadType": "SUB", "description": "PANEL \"A\" / 217 - KING STUDIO", "notes": [], "poles": 2, "breaker": "80/2", "wire": 3, "voltAmps": 6694, "printedState": "explicit" }, { "circuit": 18, "side": "even", "loadType": "SUB", "description": "PANEL \"A\" / 224 - DOUBLE QUEEN", "notes": [], "poles": 2, "breaker": "80/2", "wire": 3, "voltAmps": 6694, "printedState": "explicit" }, { "circuit": 19, "side": "odd", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 6694, "printedState": "continuation" }, { "circuit": 20, "side": "even", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 6694, "printedState": "continuation" }, { "circuit": 21, "side": "odd", "loadType": "SUB", "description": "PANEL \"A\" / 218 - DOUBLE QUEEN", "notes": [], "poles": 2, "breaker": "80/2", "wire": 3, "voltAmps": 6817, "printedState": "explicit" }, { "circuit": 22, "side": "even", "loadType": "SUB", "description": "PANEL \"A\" / 226 - KING ACC", "notes": [], "poles": 2, "breaker": "80/2", "wire": 3, "voltAmps": 6694, "printedState": "explicit" }, { "circuit": 23, "side": "odd", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 6817, "printedState": "continuation" }, { "circuit": 24, "side": "even", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 6694, "printedState": "continuation" }, { "circuit": 25, "side": "odd", "loadType": "SUB", "description": "SPARE", "notes": [], "poles": 2, "breaker": "80/2", "wire": null, "voltAmps": null, "printedState": "explicit" }, { "circuit": 26, "side": "even", "loadType": "HTG", "description": "EUH", "notes": [], "poles": 2, "breaker": "30/2", "wire": 10, "voltAmps": 2500, "printedState": "explicit" }, { "circuit": 27, "side": "odd", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": null, "printedState": "continuation" }, { "circuit": 28, "side": "even", "loadType": "HTG", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 2500, "printedState": "continuation" }, { "circuit": 29, "side": "odd", "loadType": null, "description": "SPACE ONLY", "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "space-only" }, { "circuit": 30, "side": "even", "loadType": "HTG", "description": "EUH", "notes": [], "poles": 2, "breaker": "30/2", "wire": 10, "voltAmps": 2500, "printedState": "explicit" }, { "circuit": 31, "side": "odd", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 32, "side": "even", "loadType": "HTG", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 2500, "printedState": "continuation" }, { "circuit": 33, "side": "odd", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 34, "side": "even", "loadType": null, "description": "SPARE", "notes": [], "poles": 1, "breaker": "20/1", "wire": null, "voltAmps": null, "printedState": "explicit" }, { "circuit": 35, "side": "odd", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 36, "side": "even", "loadType": null, "description": null, "notes": [], "poles": 1, "breaker": "↓", "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 37, "side": "odd", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 38, "side": "even", "loadType": null, "description": "↓", "notes": [], "poles": 1, "breaker": "↓", "wire": null, "voltAmps": null, "printedState": "continuation" }, { "circuit": 39, "side": "odd", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 40, "side": "even", "loadType": null, "description": "SPACE ONLY", "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "space-only" }, { "circuit": 41, "side": "odd", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 42, "side": "even", "loadType": null, "description": "↓", "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "continuation" } ], "phasePairLoads": [ { "oddCircuit": 1, "evenCircuit": 2, "phase": "A", "printedVA": 15216 }, { "oddCircuit": 3, "evenCircuit": 4, "phase": "B", "printedVA": 15216 }, { "oddCircuit": 5, "evenCircuit": 6, "phase": "C", "printedVA": 13388 }, { "oddCircuit": 7, "evenCircuit": 8, "phase": "A", "printedVA": 13388 }, { "oddCircuit": 9, "evenCircuit": 10, "phase": "B", "printedVA": 13388 }, { "oddCircuit": 11, "evenCircuit": 12, "phase": "C", "printedVA": 13388 }, { "oddCircuit": 13, "evenCircuit": 14, "phase": "A", "printedVA": 13511 }, { "oddCircuit": 15, "evenCircuit": 16, "phase": "B", "printedVA": 13511 }, { "oddCircuit": 17, "evenCircuit": 18, "phase": "C", "printedVA": 13388 }, { "oddCircuit": 19, "evenCircuit": 20, "phase": "A", "printedVA": 13388 }, { "oddCircuit": 21, "evenCircuit": 22, "phase": "B", "printedVA": 13511 }, { "oddCircuit": 23, "evenCircuit": 24, "phase": "C", "printedVA": 13511 }, { "oddCircuit": 25, "evenCircuit": 26, "phase": "A", "printedVA": 2500 }, { "oddCircuit": 27, "evenCircuit": 28, "phase": "B", "printedVA": 2500 }, { "oddCircuit": 29, "evenCircuit": 30, "phase": "C", "printedVA": 2500 }, { "oddCircuit": 31, "evenCircuit": 32, "phase": "A", "printedVA": 2500 }, { "oddCircuit": 33, "evenCircuit": 34, "phase": "B", "printedVA": 0 }, { "oddCircuit": 35, "evenCircuit": 36, "phase": "C", "printedVA": 0 }, { "oddCircuit": 37, "evenCircuit": 38, "phase": "A", "printedVA": 0 }, { "oddCircuit": 39, "evenCircuit": 40, "phase": "B", "printedVA": 0 }, { "oddCircuit": 41, "evenCircuit": 42, "phase": "C", "printedVA": 0 } ], "loadCodes": [ { "code": "LTG", "connected": 0, "description": "LTG =125% LIGHTING LOAD: (N/A)", "demand": 0 }, { "code": "REC", "connected": 0, "description": "REC = RCPTS LOAD : (N/A)", "demand": 0 }, { "code": "EQUIP", "connected": 0, "description": "EQUIP = EQUIPMENT LOAD : (N/A)", "demand": 0 }, { "code": "AC", "connected": 0, "description": "AC = HVAC LOAD : (N/A)", "demand": 0 }, { "code": "HTG", "connected": 10000, "description": "HTG = HEATING LOAD", "demand": 10000 }, { "code": "LGR", "connected": 0, "description": "LGR = 125% LARGEST MOTOR : (N/A)", "demand": 0 }, { "code": "KIT", "connected": 0, "description": "KIT = KITCHEN LOAD : (N/A)", "demand": 0 }, { "code": "SUB", "connected": 164804, "description": "SUB = SUB PANEL x 41% PF(FOR 12 UNITS)", "demand": 67570 }, { "code": "GLTG", "connected": 0, "description": "GLTG = GUESTROOM LIGHTING LOAD: N/A", "demand": 0 }, { "code": "EVCS", "connected": 0, "description": "EVCS = 125% ELECTRIC VEHICLE CHARGING STATION : (N/A)", "demand": 0 } ], "totals": { "connectedVA": 174804, "connectedAmps": 486, "demandVA": 77570, "demandAmps": 215, "connectedPhaseKVA": [ 60.5, 58.13, 56.18 ], "connectedPhaseAmps": [ 504.19, 484.38, 468.13 ], "demandPhaseKVA": [ 27.76, 25.31, 24.51 ], "demandPhaseAmps": [ 231.3, 210.89, 204.22 ] }, "panelSpecificNotes": [] }, { "name": "L1.C", "fedFrom": "MDP", "region": [ 851.85, 377.78, 1600.0, 770.37 ], "header": { "projectName": "HOME 2 SUITES, BRADENTON, FL", "projectNumber": "#210729", "voltage": "120/208V, 3PH, 4W", "enclosure": "NEMA-1", "aicRating": "42 KA", "bus": "200 AMP", "busMaterial": "COPPER", "mains": "200 AMP M.L.O", "mounting": "SURFACE MOUNTED", "location": "ELEC. RM. 1ST FLOOR" }, "rows": [ { "circuit": 1, "side": "odd", "loadType": "EQUIP", "description": "DOOR MOTOR", "notes": [], "poles": 1, "breaker": "20/1", "wire": 10, "voltAmps": 1500, "printedState": "explicit" }, { "circuit": 2, "side": "even", "loadType": "REC", "description": "RCPTS - FITNESS/GUEST LAUNDRY", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 1440, "printedState": "explicit" }, { "circuit": 3, "side": "odd", "loadType": "EQUIP", "description": "DOOR MOTOR", "notes": [], "poles": 1, "breaker": "20/1", "wire": 10, "voltAmps": 1500, "printedState": "explicit" }, { "circuit": 4, "side": "even", "loadType": "EQUIP", "description": "RCPTS - FITNESS EQUIPMENT", "notes": [], "poles": 1, "breaker": "30/1", "wire": 10, "voltAmps": 2000, "printedState": "explicit" }, { "circuit": 5, "side": "odd", "loadType": "REC", "description": "RCPTS - CORRIDOR/ENGINEER", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 1080, "printedState": "explicit" }, { "circuit": 6, "side": "even", "loadType": "EQUIP", "description": "RCPTS - FITNESS EQUIPMENT", "notes": [], "poles": 1, "breaker": "30/1", "wire": 10, "voltAmps": 2000, "printedState": "explicit" }, { "circuit": 7, "side": "odd", "loadType": "REC", "description": "IG RCPTS - ENGINEER", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 360, "printedState": "explicit" }, { "circuit": 8, "side": "even", "loadType": "EQUIP", "description": "RCPTS - FITNESS EQUIPMENT", "notes": [], "poles": 1, "breaker": "30/1", "wire": 10, "voltAmps": 2000, "printedState": "explicit" }, { "circuit": 9, "side": "odd", "loadType": "REC", "description": "RCPTS - ELECT/MECHANICAL", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 720, "printedState": "explicit" }, { "circuit": 10, "side": "even", "loadType": "EQUIP", "description": "RCPTS - FITNESS EQUIPMENT", "notes": [], "poles": 1, "breaker": "30/1", "wire": 10, "voltAmps": 2000, "printedState": "explicit" }, { "circuit": 11, "side": "odd", "loadType": "REC", "description": "RCPTS - PBX", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 720, "printedState": "explicit" }, { "circuit": 12, "side": "even", "loadType": "EQUIP", "description": "RCPTS - FITNESS EQUIPMENT", "notes": [], "poles": 1, "breaker": "30/1", "wire": 10, "voltAmps": 2000, "printedState": "explicit" }, { "circuit": 13, "side": "odd", "loadType": "REC", "description": "RCPTS - STORAGE/BREAKROOM", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 720, "printedState": "explicit" }, { "circuit": 14, "side": "even", "loadType": "REC", "description": "RCPTS - TV LOUNGE", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 1260, "printedState": "explicit" }, { "circuit": 15, "side": "odd", "loadType": "EQUIP", "description": "RCPTS - BREAKROOM REF.", "notes": [ "(GFCI BREAKER)" ], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 500, "printedState": "explicit" }, { "circuit": 16, "side": "even", "loadType": "REC", "description": "RCPTS - LOBBY", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 540, "printedState": "explicit" }, { "circuit": 17, "side": "odd", "loadType": "EQUIP", "description": "RCPTS - BREAKROOM", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 1500, "printedState": "explicit" }, { "circuit": 18, "side": "even", "loadType": "REC", "description": "RCPTS - OUTDOOR", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 360, "printedState": "explicit" }, { "circuit": 19, "side": "odd", "loadType": "EQUIP", "description": "RCPTS - BREAKROOM", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 1500, "printedState": "explicit" }, { "circuit": 20, "side": "even", "loadType": "REC", "description": "IG RCPTS - SALES", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 360, "printedState": "explicit" }, { "circuit": 21, "side": "odd", "loadType": "REC", "description": "RCPTS - LAUNDRY", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 1260, "printedState": "explicit" }, { "circuit": 22, "side": "even", "loadType": "REC", "description": "RCPTS - SALES/CORRIDOR", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 1440, "printedState": "explicit" }, { "circuit": 23, "side": "odd", "loadType": "REC", "description": "RCPTS - LAUNDRY/OUTDOOR", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 720, "printedState": "explicit" }, { "circuit": 24, "side": "even", "loadType": null, "description": "SPARE", "notes": [], "poles": 1, "breaker": "20/1", "wire": null, "voltAmps": null, "printedState": "explicit" }, { "circuit": 25, "side": "odd", "loadType": "REC", "description": "RCPTS - OFFICES", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 1080, "printedState": "explicit" }, { "circuit": 26, "side": "even", "loadType": null, "description": "SPARE", "notes": [], "poles": 1, "breaker": "20/1", "wire": null, "voltAmps": null, "printedState": "explicit" }, { "circuit": 27, "side": "odd", "loadType": "REC", "description": "IG RCPTS - OFFICES", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 360, "printedState": "explicit" }, { "circuit": 28, "side": "even", "loadType": "REC", "description": "RCPTS - OUTDOOR", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 360, "printedState": "explicit" }, { "circuit": 29, "side": "odd", "loadType": "REC", "description": "IG RCPTS - OFFICES", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 720, "printedState": "explicit" }, { "circuit": 30, "side": "even", "loadType": "EQUIP", "description": "ICE MACHINE", "notes": [ "(CLASS A GFCI BREAKER)" ], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 1500, "printedState": "explicit" }, { "circuit": 31, "side": "odd", "loadType": "REC", "description": "IG RCPTS - OFFICES", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 360, "printedState": "explicit" }, { "circuit": 32, "side": "even", "loadType": "EQUIP", "description": "MARKET", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 1500, "printedState": "explicit" }, { "circuit": 33, "side": "odd", "loadType": "REC", "description": "RCPTS - FRONT DESK", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 1260, "printedState": "explicit" }, { "circuit": 34, "side": "even", "loadType": "EQUIP", "description": "(E35) - FREEZER", "notes": [ "(GFCI BREAKER)" ], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 744, "printedState": "explicit" }, { "circuit": 35, "side": "odd", "loadType": "REC", "description": "RCPTS - FRONT DESK", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 1260, "printedState": "explicit" }, { "circuit": 36, "side": "even", "loadType": "EQUIP", "description": "(E36) - REFRIGERATOR", "notes": [ "(GFCI BREAKER)" ], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 1020, "printedState": "explicit" }, { "circuit": 37, "side": "odd", "loadType": "REC", "description": "RCPTS - MARKET", "notes": [ "(GFCI BREAKER)" ], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 360, "printedState": "explicit" }, { "circuit": 38, "side": "even", "loadType": "EQUIP", "description": "(E37) - WATER DISPENSER", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 180, "printedState": "explicit" }, { "circuit": 39, "side": "odd", "loadType": "REC", "description": "RCPTS - LOBBY", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 720, "printedState": "explicit" }, { "circuit": 40, "side": "even", "loadType": "EQUIP", "description": "(E37) - WATER DISPENSER", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 1400, "printedState": "explicit" }, { "circuit": 41, "side": "odd", "loadType": "REC", "description": "RCPTS - LOBBY", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 720, "printedState": "explicit" }, { "circuit": 42, "side": "even", "loadType": "EQUIP", "description": "(E901) - CONVENIENCE", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 1500, "printedState": "explicit" }, { "circuit": 43, "side": "odd", "loadType": "REC", "description": "RCPTS - LOBBY", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 1440, "printedState": "explicit" }, { "circuit": 44, "side": "even", "loadType": "EQUIP", "description": "(E901) - CONVENIENCE", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 1500, "printedState": "explicit" }, { "circuit": 45, "side": "odd", "loadType": "REC", "description": "RCPTS - LOBBY", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 720, "printedState": "explicit" }, { "circuit": 46, "side": "even", "loadType": "EQUIP", "description": "(E901) - CONVENIENCE", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 1500, "printedState": "explicit" }, { "circuit": 47, "side": "odd", "loadType": "REC", "description": "IG RCPTS - PRINTER", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 720, "printedState": "explicit" }, { "circuit": 48, "side": "even", "loadType": "EQUIP", "description": "MOTORIZED SHADE", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 500, "printedState": "explicit" }, { "circuit": 49, "side": "odd", "loadType": "REC", "description": "IG RCPTS - OUTDOOR", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 360, "printedState": "explicit" }, { "circuit": 50, "side": "even", "loadType": "EQUIP", "description": "IG RCPTS - TEL BOARD", "notes": [], "poles": 1, "breaker": "20/1", "wire": 10, "voltAmps": 1500, "printedState": "explicit" }, { "circuit": 51, "side": "odd", "loadType": "REC", "description": "SPARE", "notes": [], "poles": 1, "breaker": "20/1", "wire": null, "voltAmps": null, "printedState": "explicit" }, { "circuit": 52, "side": "even", "loadType": "EQUIP", "description": "↓", "notes": [], "poles": 1, "breaker": "20/1", "wire": 10, "voltAmps": 1500, "printedState": "continuation" }, { "circuit": 53, "side": "odd", "loadType": null, "description": "↓", "notes": [], "poles": 1, "breaker": "↓", "wire": null, "voltAmps": null, "printedState": "continuation" }, { "circuit": 54, "side": "even", "loadType": "EQUIP", "description": "IG RCPTS - SECURITY BOARD", "notes": [], "poles": 1, "breaker": "20/1", "wire": 10, "voltAmps": 1500, "printedState": "explicit" }, { "circuit": 55, "side": "odd", "loadType": null, "description": null, "notes": [], "poles": 1, "breaker": "↓", "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 56, "side": "even", "loadType": "EQUIP", "description": "↓", "notes": [], "poles": 1, "breaker": "20/1", "wire": 10, "voltAmps": 1500, "printedState": "continuation" }, { "circuit": 57, "side": "odd", "loadType": null, "description": null, "notes": [], "poles": 1, "breaker": "↓", "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 58, "side": "even", "loadType": "EQUIP", "description": "IG RCPTS - CABLE TV BOARD", "notes": [], "poles": 1, "breaker": "20/1", "wire": 10, "voltAmps": 1500, "printedState": "explicit" }, { "circuit": 59, "side": "odd", "loadType": null, "description": null, "notes": [], "poles": 1, "breaker": "↓", "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 60, "side": "even", "loadType": "EQUIP", "description": "↓", "notes": [], "poles": 1, "breaker": "20/1", "wire": 10, "voltAmps": 1500, "printedState": "continuation" }, { "circuit": 61, "side": "odd", "loadType": null, "description": null, "notes": [], "poles": 1, "breaker": "↓", "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 62, "side": "even", "loadType": "EQUIP", "description": "SPACE ONLY", "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "space-only" }, { "circuit": 63, "side": "odd", "loadType": null, "description": null, "notes": [], "poles": 1, "breaker": "↓", "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 64, "side": "even", "loadType": "EQUIP", "description": "↓", "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "continuation" }, { "circuit": 65, "side": "odd", "loadType": null, "description": "↓", "notes": [], "poles": 1, "breaker": "↓", "wire": null, "voltAmps": null, "printedState": "continuation" }, { "circuit": 66, "side": "even", "loadType": "EQUIP", "description": "↓", "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "continuation" } ], "phasePairLoads": [ { "oddCircuit": 1, "evenCircuit": 2, "phase": "A", "printedVA": 2940 }, { "oddCircuit": 3, "evenCircuit": 4, "phase": "B", "printedVA": 3500 }, { "oddCircuit": 5, "evenCircuit": 6, "phase": "C", "printedVA": 3080 }, { "oddCircuit": 7, "evenCircuit": 8, "phase": "A", "printedVA": 2360 }, { "oddCircuit": 9, "evenCircuit": 10, "phase": "B", "printedVA": 2720 }, { "oddCircuit": 11, "evenCircuit": 12, "phase": "C", "printedVA": 2720 }, { "oddCircuit": 13, "evenCircuit": 14, "phase": "A", "printedVA": 1980 }, { "oddCircuit": 15, "evenCircuit": 16, "phase": "B", "printedVA": 1040 }, { "oddCircuit": 17, "evenCircuit": 18, "phase": "C", "printedVA": 1860 }, { "oddCircuit": 19, "evenCircuit": 20, "phase": "A", "printedVA": 1860 }, { "oddCircuit": 21, "evenCircuit": 22, "phase": "B", "printedVA": 2700 }, { "oddCircuit": 23, "evenCircuit": 24, "phase": "C", "printedVA": 720 }, { "oddCircuit": 25, "evenCircuit": 26, "phase": "A", "printedVA": 1080 }, { "oddCircuit": 27, "evenCircuit": 28, "phase": "B", "printedVA": 720 }, { "oddCircuit": 29, "evenCircuit": 30, "phase": "C", "printedVA": 2220 }, { "oddCircuit": 31, "evenCircuit": 32, "phase": "A", "printedVA": 1860 }, { "oddCircuit": 33, "evenCircuit": 34, "phase": "B", "printedVA": 2004 }, { "oddCircuit": 35, "evenCircuit": 36, "phase": "C", "printedVA": 2280 }, { "oddCircuit": 37, "evenCircuit": 38, "phase": "A", "printedVA": 540 }, { "oddCircuit": 39, "evenCircuit": 40, "phase": "B", "printedVA": 2120 }, { "oddCircuit": 41, "evenCircuit": 42, "phase": "C", "printedVA": 2220 }, { "oddCircuit": 43, "evenCircuit": 44, "phase": "A", "printedVA": 2940 }, { "oddCircuit": 45, "evenCircuit": 46, "phase": "B", "printedVA": 2220 }, { "oddCircuit": 47, "evenCircuit": 48, "phase": "C", "printedVA": 1220 }, { "oddCircuit": 49, "evenCircuit": 50, "phase": "A", "printedVA": 1860 }, { "oddCircuit": 51, "evenCircuit": 52, "phase": "B", "printedVA": 1500 }, { "oddCircuit": 53, "evenCircuit": 54, "phase": "C", "printedVA": 1500 }, { "oddCircuit": 55, "evenCircuit": 56, "phase": "A", "printedVA": 1500 }, { "oddCircuit": 57, "evenCircuit": 58, "phase": "B", "printedVA": 1500 }, { "oddCircuit": 59, "evenCircuit": 60, "phase": "C", "printedVA": 1500 }, { "oddCircuit": 61, "evenCircuit": 62, "phase": "A", "printedVA": 0 }, { "oddCircuit": 63, "evenCircuit": 64, "phase": "B", "printedVA": 0 }, { "oddCircuit": 65, "evenCircuit": 66, "phase": "C", "printedVA": 0 } ], "loadCodes": [ { "code": "LTG", "connected": 0, "description": "LTG =125% LIGHTING LOAD: (N/A)", "demand": 0 }, { "code": "REC", "connected": 21420, "description": "REC = RCPTS LOAD (100% FIRST 10KVA +50% REMAIN)", "demand": 15710 }, { "code": "EQUIP", "connected": 36844, "description": "EQUIP = EQUIPMENT LOAD", "demand": 36844 }, { "code": "AC", "connected": 0, "description": "AC = HVAC LOAD : (N/A)", "demand": 0 }, { "code": "HTG", "connected": 0, "description": "HTG = HEATING LOAD : (N/A)", "demand": 0 }, { "code": "LGR", "connected": 0, "description": "LGR = 125% LARGEST MOTOR : (N/A)", "demand": 0 }, { "code": "KIT", "connected": 0, "description": "KIT = KITCHEN LOAD : (N/A)", "demand": 0 }, { "code": "SUB", "connected": 0, "description": "SUB = SUB PANEL x PF : (N/A)", "demand": 0 }, { "code": "GLTG", "connected": 0, "description": "GLTG = GUESTROOM LIGHTING LOAD: N/A", "demand": 0 }, { "code": "EVCS", "connected": 0, "description": "EVCS = 125% ELECTRIC VEHICLE CHARGING STATION : (N/A)", "demand": 0 } ], "totals": { "connectedVA": 58264, "connectedAmps": 162, "demandVA": 52554, "demandAmps": 146, "connectedPhaseKVA": [ 18.92, 20.02, 19.32 ], "connectedPhaseAmps": [ 157.67, 166.87, 161.0 ], "demandPhaseKVA": [ 16.72, 18.0, 17.84 ], "demandPhaseAmps": [ 139.3, 150.0, 148.64 ] }, "panelSpecificNotes": [ { "number": 1, "text": "CONTRACTOR MUST PROVIDE ISOLATED GROUNDS IN THE PANEL." } ] }, { "name": "L1.A", "fedFrom": "MDP", "region": [ 81.48, 688.89, 840.74, 992.59 ], "header": { "projectName": "HOME 2 SUITES, BRADENTON, FL", "projectNumber": "#210729", "voltage": "120/208V, 3PH, 4W", "enclosure": "NEMA-1", "aicRating": "42 KA", "bus": "225 AMP", "busMaterial": "COPPER", "mains": "225 AMP M.L.O", "mounting": "SURFACE MOUNTED", "location": "ELEC. RM. 1ST FLOOR" }, "rows": [ { "circuit": 1, "side": "odd", "loadType": "SUB", "description": "PANEL \"A\" / 101 - KING STUDIO", "notes": [], "poles": 2, "breaker": "80/2", "wire": 3, "voltAmps": 6694, "printedState": "explicit" }, { "circuit": 2, "side": "even", "loadType": "SUB", "description": "PANEL \"B\" / 107 - ACC KING ONE BEDROOM", "notes": [], "poles": 2, "breaker": "100/2", "wire": 2, "voltAmps": 8522, "printedState": "explicit" }, { "circuit": 3, "side": "odd", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 6694, "printedState": "continuation" }, { "circuit": 4, "side": "even", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 8522, "printedState": "continuation" }, { "circuit": 5, "side": "odd", "loadType": "SUB", "description": "PANEL \"B\" / 102 - KING ONE BEDROOM", "notes": [], "poles": 2, "breaker": "100/2", "wire": 2, "voltAmps": 8443, "printedState": "explicit" }, { "circuit": 6, "side": "even", "loadType": "SUB", "description": "PANEL \"A\" / 108 - KING STUDIO", "notes": [], "poles": 2, "breaker": "80/2", "wire": 3, "voltAmps": 6694, "printedState": "explicit" }, { "circuit": 7, "side": "odd", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 8443, "printedState": "continuation" }, { "circuit": 8, "side": "even", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 6694, "printedState": "continuation" }, { "circuit": 9, "side": "odd", "loadType": "SUB", "description": "PANEL \"A\" / 103 - KING STUDIO", "notes": [], "poles": 2, "breaker": "80/2", "wire": 3, "voltAmps": 6694, "printedState": "explicit" }, { "circuit": 10, "side": "even", "loadType": "SUB", "description": "PANEL \"A\" / 110 - KING STUDIO", "notes": [], "poles": 2, "breaker": "80/2", "wire": 3, "voltAmps": 6694, "printedState": "explicit" }, { "circuit": 11, "side": "odd", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 6694, "printedState": "continuation" }, { "circuit": 12, "side": "even", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 6694, "printedState": "continuation" }, { "circuit": 13, "side": "odd", "loadType": "SUB", "description": "PANEL \"A\" / 104 - KING STUDIO", "notes": [], "poles": 2, "breaker": "80/2", "wire": 3, "voltAmps": 6694, "printedState": "explicit" }, { "circuit": 14, "side": "even", "loadType": "SUB", "description": "PANEL \"A\" / 111 - KING STUDIO", "notes": [], "poles": 2, "breaker": "80/2", "wire": 3, "voltAmps": 6694, "printedState": "explicit" }, { "circuit": 15, "side": "odd", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 6694, "printedState": "continuation" }, { "circuit": 16, "side": "even", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 6694, "printedState": "continuation" }, { "circuit": 17, "side": "odd", "loadType": "SUB", "description": "PANEL \"A\" / 105 - KING STUDIO", "notes": [], "poles": 2, "breaker": "80/2", "wire": 3, "voltAmps": 6694, "printedState": "explicit" }, { "circuit": 18, "side": "even", "loadType": "SUB", "description": "PANEL \"A\" / 112 - KING STUDIO", "notes": [], "poles": 2, "breaker": "80/2", "wire": 3, "voltAmps": 6694, "printedState": "explicit" }, { "circuit": 19, "side": "odd", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 6694, "printedState": "continuation" }, { "circuit": 20, "side": "even", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 6694, "printedState": "continuation" }, { "circuit": 21, "side": "odd", "loadType": "SUB", "description": "PANEL \"A\" / 106 - KING STUDIO", "notes": [], "poles": 2, "breaker": "80/2", "wire": 3, "voltAmps": 6694, "printedState": "explicit" }, { "circuit": 22, "side": "even", "loadType": null, "description": "SPACE ONLY", "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "space-only" }, { "circuit": 23, "side": "odd", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 6694, "printedState": "continuation" }, { "circuit": 24, "side": "even", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 25, "side": "odd", "loadType": "SUB", "description": "SPARE", "notes": [], "poles": 2, "breaker": "80/2", "wire": null, "voltAmps": null, "printedState": "explicit" }, { "circuit": 26, "side": "even", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 27, "side": "odd", "loadType": "SUB", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": null, "printedState": "continuation" }, { "circuit": 28, "side": "even", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 29, "side": "odd", "loadType": null, "description": "SPACE ONLY", "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "space-only" }, { "circuit": 30, "side": "even", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 31, "side": "odd", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 32, "side": "even", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 33, "side": "odd", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 34, "side": "even", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 35, "side": "odd", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 36, "side": "even", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 37, "side": "odd", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 38, "side": "even", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 39, "side": "odd", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 40, "side": "even", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 41, "side": "odd", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 42, "side": "even", "loadType": null, "description": "↓", "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "continuation" } ], "phasePairLoads": [ { "oddCircuit": 1, "evenCircuit": 2, "phase": "A", "printedVA": 15216 }, { "oddCircuit": 3, "evenCircuit": 4, "phase": "B", "printedVA": 15216 }, { "oddCircuit": 5, "evenCircuit": 6, "phase": "C", "printedVA": 15137 }, { "oddCircuit": 7, "evenCircuit": 8, "phase": "A", "printedVA": 15137 }, { "oddCircuit": 9, "evenCircuit": 10, "phase": "B", "printedVA": 13388 }, { "oddCircuit": 11, "evenCircuit": 12, "phase": "C", "printedVA": 13388 }, { "oddCircuit": 13, "evenCircuit": 14, "phase": "A", "printedVA": 13388 }, { "oddCircuit": 15, "evenCircuit": 16, "phase": "B", "printedVA": 13388 }, { "oddCircuit": 17, "evenCircuit": 18, "phase": "C", "printedVA": 13388 }, { "oddCircuit": 19, "evenCircuit": 20, "phase": "A", "printedVA": 13388 }, { "oddCircuit": 21, "evenCircuit": 22, "phase": "B", "printedVA": 6694 }, { "oddCircuit": 23, "evenCircuit": 24, "phase": "C", "printedVA": 6694 }, { "oddCircuit": 25, "evenCircuit": 26, "phase": "A", "printedVA": 0 }, { "oddCircuit": 27, "evenCircuit": 28, "phase": "B", "printedVA": 0 }, { "oddCircuit": 29, "evenCircuit": 30, "phase": "C", "printedVA": 0 }, { "oddCircuit": 31, "evenCircuit": 32, "phase": "A", "printedVA": 0 }, { "oddCircuit": 33, "evenCircuit": 34, "phase": "B", "printedVA": 0 }, { "oddCircuit": 35, "evenCircuit": 36, "phase": "C", "printedVA": 0 }, { "oddCircuit": 37, "evenCircuit": 38, "phase": "A", "printedVA": 0 }, { "oddCircuit": 39, "evenCircuit": 40, "phase": "B", "printedVA": 0 }, { "oddCircuit": 41, "evenCircuit": 42, "phase": "C", "printedVA": 0 } ], "loadCodes": [ { "code": "LTG", "connected": 0, "description": "LTG =125% LIGHTING LOAD: (N/A)", "demand": 0 }, { "code": "REC", "connected": 0, "description": "REC = RCPTS LOAD : (N/A)", "demand": 0 }, { "code": "EQUIP", "connected": 0, "description": "EQUIP = EQUIPMENT LOAD : (N/A)", "demand": 0 }, { "code": "AC", "connected": 0, "description": "AC = HVAC LOAD : (N/A)", "demand": 0 }, { "code": "HTG", "connected": 0, "description": "HTG = HEATING LOAD : (N/A)", "demand": 0 }, { "code": "LGR", "connected": 0, "description": "LGR = 125% LARGEST MOTOR : (N/A)", "demand": 0 }, { "code": "KIT", "connected": 0, "description": "KIT = KITCHEN LOAD : (N/A)", "demand": 0 }, { "code": "SUB", "connected": 154421, "description": "SUB = SUB PANEL x 42% PF(FOR 11 UNITS)", "demand": 64857 }, { "code": "GLTG", "connected": 0, "description": "GLTG = GUESTROOM LIGHTING LOAD: N/A", "demand": 0 }, { "code": "EVCS", "connected": 0, "description": "EVCS = 125% ELECTRIC VEHICLE CHARGING STATION : (N/A)", "demand": 0 } ], "totals": { "connectedVA": 154421, "connectedAmps": 429, "demandVA": 64857, "demandAmps": 180, "connectedPhaseKVA": [ 57.13, 48.69, 48.61 ], "connectedPhaseAmps": [ 476.07, 405.72, 405.05 ], "demandPhaseKVA": [ 23.99, 20.45, 20.41 ], "demandPhaseAmps": [ 199.95, 170.4, 170.12 ] }, "panelSpecificNotes": [] }, { "name": "L1.D", "fedFrom": "MDP", "region": [ 851.85, 770.37, 1600.0, 1081.48 ], "header": { "projectName": "HOME 2 SUITES, BRADENTON, FL", "projectNumber": "#210729", "voltage": "120/208V, 3PH, 4W", "enclosure": "NEMA-1", "aicRating": "42 KA", "bus": "200 AMP", "busMaterial": "COPPER", "mains": "200 AMP M.L.O", "mounting": "SURFACE MOUNTED", "location": "ELEC. RM. 1ST FLOOR" }, "rows": [ { "circuit": 1, "side": "odd", "loadType": "EQUIP", "description": "WASHER", "notes": [ "(GFCI BREAKER)" ], "poles": 3, "breaker": "30/3", "wire": 10, "voltAmps": 2000, "printedState": "explicit" }, { "circuit": 2, "side": "even", "loadType": "EQUIP", "description": "BOOSTER PUMP CONTROL PANEL (B.P)", "notes": [], "poles": 3, "breaker": "60/3", "wire": 6, "voltAmps": 3309, "printedState": "explicit" }, { "circuit": 3, "side": "odd", "loadType": "EQUIP", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 2000, "printedState": "continuation" }, { "circuit": 4, "side": "even", "loadType": "EQUIP", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 3309, "printedState": "continuation" }, { "circuit": 5, "side": "odd", "loadType": "EQUIP", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 2000, "printedState": "continuation" }, { "circuit": 6, "side": "even", "loadType": "EQUIP", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 3309, "printedState": "continuation" }, { "circuit": 7, "side": "odd", "loadType": "EQUIP", "description": "WASHER", "notes": [ "(GFCI BREAKER)" ], "poles": 3, "breaker": "30/3", "wire": 10, "voltAmps": 2000, "printedState": "explicit" }, { "circuit": 8, "side": "even", "loadType": "EQUIP", "description": "CIRCULATE PUMP CONTROL PANEL (C.P)", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 441, "printedState": "explicit" }, { "circuit": 9, "side": "odd", "loadType": "EQUIP", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 2000, "printedState": "continuation" }, { "circuit": 10, "side": "even", "loadType": "EQUIP", "description": "CIRCULATE PUMP CONTROL PANEL (C.P)", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 441, "printedState": "explicit" }, { "circuit": 11, "side": "odd", "loadType": "EQUIP", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 2000, "printedState": "continuation" }, { "circuit": 12, "side": "even", "loadType": "EQUIP", "description": "GAS WATER HEATER", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 1440, "printedState": "explicit" }, { "circuit": 13, "side": "odd", "loadType": "EQUIP", "description": "DRYER (GAS HEAT)", "notes": [ "(GFCI BREAKER)" ], "poles": 2, "breaker": "20/2", "wire": 12, "voltAmps": 750, "printedState": "explicit" }, { "circuit": 14, "side": "even", "loadType": "EQUIP", "description": "GAS WATER HEATER", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 960, "printedState": "explicit" }, { "circuit": 15, "side": "odd", "loadType": "EQUIP", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 750, "printedState": "continuation" }, { "circuit": 16, "side": "even", "loadType": "EQUIP", "description": "GAS WATER HEATER", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 960, "printedState": "explicit" }, { "circuit": 17, "side": "odd", "loadType": "EQUIP", "description": "DRYER (GAS HEAT)", "notes": [ "(GFCI BREAKER)" ], "poles": 2, "breaker": "20/2", "wire": 12, "voltAmps": 750, "printedState": "explicit" }, { "circuit": 18, "side": "even", "loadType": "EQUIP", "description": "MOTORIZED DAMPER", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 500, "printedState": "explicit" }, { "circuit": 19, "side": "odd", "loadType": "EQUIP", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 750, "printedState": "continuation" }, { "circuit": 20, "side": "even", "loadType": "EQUIP", "description": "FIRE SMOKE DAMPER", "notes": [], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 500, "printedState": "explicit" }, { "circuit": 21, "side": "odd", "loadType": "EQUIP", "description": "WASHER ( GUEST LAUNDRY)", "notes": [ "(GFCI BREAKER)" ], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 1800, "printedState": "explicit" }, { "circuit": 22, "side": "even", "loadType": null, "description": "SPARE", "notes": [], "poles": 1, "breaker": "20/1", "wire": null, "voltAmps": null, "printedState": "explicit" }, { "circuit": 23, "side": "odd", "loadType": "EQUIP", "description": "WASHER ( GUEST LAUNDRY)", "notes": [ "(GFCI BREAKER)" ], "poles": 1, "breaker": "20/1", "wire": 12, "voltAmps": 1800, "printedState": "explicit" }, { "circuit": 24, "side": "even", "loadType": null, "description": null, "notes": [], "poles": 1, "breaker": "↓", "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 25, "side": "odd", "loadType": "EQUIP", "description": "DRYER ( GUEST LAUNDRY)", "notes": [ "(GFCI BREAKER)" ], "poles": 2, "breaker": "30/2", "wire": 10, "voltAmps": 2500, "printedState": "explicit" }, { "circuit": 26, "side": "even", "loadType": null, "description": null, "notes": [], "poles": 1, "breaker": "↓", "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 27, "side": "odd", "loadType": "EQUIP", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 2500, "printedState": "continuation" }, { "circuit": 28, "side": "even", "loadType": null, "description": null, "notes": [], "poles": 1, "breaker": "↓", "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 29, "side": "odd", "loadType": "EQUIP", "description": "DRYER ( GUEST LAUNDRY)", "notes": [ "(GFCI BREAKER)" ], "poles": 2, "breaker": "30/2", "wire": 10, "voltAmps": 2500, "printedState": "explicit" }, { "circuit": 30, "side": "even", "loadType": null, "description": null, "notes": [], "poles": 1, "breaker": "↓", "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 31, "side": "odd", "loadType": "EQUIP", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 2500, "printedState": "continuation" }, { "circuit": 32, "side": "even", "loadType": null, "description": null, "notes": [], "poles": 1, "breaker": "↓", "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 33, "side": "odd", "loadType": "EQUIP", "description": "RCPTS - MAINTENANCE FOR PTAC", "notes": [], "poles": 2, "breaker": "20/2", "wire": 12, "voltAmps": 1468, "printedState": "explicit" }, { "circuit": 34, "side": "even", "loadType": null, "description": null, "notes": [], "poles": 1, "breaker": "↓", "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 35, "side": "odd", "loadType": "EQUIP", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 1468, "printedState": "continuation" }, { "circuit": 36, "side": "even", "loadType": null, "description": "↓", "notes": [], "poles": 1, "breaker": "↓", "wire": null, "voltAmps": null, "printedState": "continuation" }, { "circuit": 37, "side": "odd", "loadType": "EQUIP", "description": "RCPTS - MAINTENANCE FOR PTAC", "notes": [], "poles": 2, "breaker": "20/2", "wire": 12, "voltAmps": 1468, "printedState": "explicit" }, { "circuit": 38, "side": "even", "loadType": null, "description": "SPACE ONLY", "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "space-only" }, { "circuit": 39, "side": "odd", "loadType": "EQUIP", "description": "↓", "notes": [], "poles": "-", "breaker": "↓", "wire": "↓", "voltAmps": 1468, "printedState": "continuation" }, { "circuit": 40, "side": "even", "loadType": null, "description": null, "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "blank" }, { "circuit": 41, "side": "odd", "loadType": null, "description": "SPACE ONLY", "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "space-only" }, { "circuit": 42, "side": "even", "loadType": null, "description": "↓", "notes": [], "poles": null, "breaker": null, "wire": null, "voltAmps": null, "printedState": "continuation" } ], "phasePairLoads": [ { "oddCircuit": 1, "evenCircuit": 2, "phase": "A", "printedVA": 5309 }, { "oddCircuit": 3, "evenCircuit": 4, "phase": "B", "printedVA": 5309 }, { "oddCircuit": 5, "evenCircuit": 6, "phase": "C", "printedVA": 5309 }, { "oddCircuit": 7, "evenCircuit": 8, "phase": "A", "printedVA": 2441 }, { "oddCircuit": 9, "evenCircuit": 10, "phase": "B", "printedVA": 2441 }, { "oddCircuit": 11, "evenCircuit": 12, "phase": "C", "printedVA": 3440 }, { "oddCircuit": 13, "evenCircuit": 14, "phase": "A", "printedVA": 1710 }, { "oddCircuit": 15, "evenCircuit": 16, "phase": "B", "printedVA": 1710 }, { "oddCircuit": 17, "evenCircuit": 18, "phase": "C", "printedVA": 1250 }, { "oddCircuit": 19, "evenCircuit": 20, "phase": "A", "printedVA": 1250 }, { "oddCircuit": 21, "evenCircuit": 22, "phase": "B", "printedVA": 1800 }, { "oddCircuit": 23, "evenCircuit": 24, "phase": "C", "printedVA": 1800 }, { "oddCircuit": 25, "evenCircuit": 26, "phase": "A", "printedVA": 2500 }, { "oddCircuit": 27, "evenCircuit": 28, "phase": "B", "printedVA": 2500 }, { "oddCircuit": 29, "evenCircuit": 30, "phase": "C", "printedVA": 2500 }, { "oddCircuit": 31, "evenCircuit": 32, "phase": "A", "printedVA": 2500 }, { "oddCircuit": 33, "evenCircuit": 34, "phase": "B", "printedVA": 1468 }, { "oddCircuit": 35, "evenCircuit": 36, "phase": "C", "printedVA": 1468 }, { "oddCircuit": 37, "evenCircuit": 38, "phase": "A", "printedVA": 1468 }, { "oddCircuit": 39, "evenCircuit": 40, "phase": "B", "printedVA": 1468 }, { "oddCircuit": 41, "evenCircuit": 42, "phase": "C", "printedVA": 0 } ], "loadCodes": [ { "code": "LTG", "connected": 0, "description": "LTG =125% LIGHTING LOAD: (N/A)", "demand": 0 }, { "code": "REC", "connected": 0, "description": "REC = RCPTS LOAD : (N/A)", "demand": 0 }, { "code": "EQUIP", "connected": 49639, "description": "EQUIP = EQUIPMENT LOAD", "demand": 49639 }, { "code": "AC", "connected": 0, "description": "AC = HVAC LOAD : (N/A)", "demand": 0 }, { "code": "HTG", "connected": 0, "description": "HTG = HEATING LOAD : (N/A)", "demand": 0 }, { "code": "LGR", "connected": 0, "description": "LGR = 125% LARGEST MOTOR : (N/A)", "demand": 0 }, { "code": "KIT", "connected": 0, "description": "KIT = KITCHEN LOAD : (N/A)", "demand": 0 }, { "code": "SUB", "connected": 0, "description": "SUB = SUB PANEL x PF : (N/A)", "demand": 0 }, { "code": "GLTG", "connected": 0, "description": "GLTG = GUESTROOM LIGHTING LOAD: N/A", "demand": 0 }, { "code": "EVCS", "connected": 0, "description": "EVCS = 125% ELECTRIC VEHICLE CHARGING STATION : (N/A)", "demand": 0 } ], "totals": { "connectedVA": 49639, "connectedAmps": 138, "demandVA": 49639, "demandAmps": 138, "connectedPhaseKVA": [ 17.18, 16.7, 15.77 ], "connectedPhaseAmps": [ 143.15, 139.13, 131.39 ], "demandPhaseKVA": [ 17.18, 16.7, 15.77 ], "demandPhaseAmps": [ 143.15, 139.13, 131.39 ] }, "panelSpecificNotes": [ { "number": 1, "text": "FIELD VERIFICATION BREAKER SIZES, BREAKER TYPE, ETC WITH LAUNDRY MANUFACTURER AND CODES REQUIREMENTS PRIOR TO INSTALLATION." }, { "number": 2, "text": "FIELD VERIFICATION HPs, BREAKER SIZES, CABLES SIZES FOR BOOSTER PUMPS WITH THE PLUMBING EQUIPMENT SCHEDULE PRIOR TO INSTALLATION." } ] } ], "generalNotes": [ { "number": 1, "text": "CONTRACTOR SHALL PROVIDE A PERMANENTLY AFFIXED LABEL WITH THE MAXIMUM FAULT CURRENT PER ARTICLE 110.24. THE LABEL SHALL INCLUDE THE DATE THE FAULT-CURRENT CALCULATION WAS PERFORMED AND BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. THE LABEL SHALL BE 2”X3” IN SIZE AND SHALL BE BLUE LETTERING ON A CONTRASTING BACKGROUND." }, { "number": 2, "text": "CONTRACTOR TO VERIFY FINAL CURRENT VALUES FROM ELECTRICAL UTILITY COMPANY AND PROVIDE AIC PROTECTION ACCORDINGLY." }, { "number": 3, "text": "AIC RATINGS OF ALL THE PANELS & BRANCH BREAKERS SHALL MATCH THE FAULT CURRENT OF THE TRANSFORMER." } ], "reconciliation": { "guestroomSubpanels": [ { "sourcePanel": "L1.A", "circuits": "1-20 odd/even plus 21/23", "rooms": [ "101", "102", "103", "104", "105", "106", "107", "108", "110", "111", "112" ], "connectedSUBVA": 154421, "demandSUBVA": 64857, "crossSheetRoomRegisterConflict": { "severity": "critical", "scheduleEvidence": "The independently reviewed E6.1/L1.A schedule is reported as printing 12 guest feeder rows identified 101-112, while its SUB demand formula itself prints FOR 11 UNITS.", "E3.0RoomRegisterEvidence": { "guestrooms": [ "101", "102", "103", "104", "105", "106", "107", "108", "110", "112", "114" ], "nonGuestSpaces": { "109": "Mechanical", "111": "Engineer" } }, "specificConflict": "L1.A assigns a guest feeder to room 111, but E3.0 identifies 111 as Engineer; E3.0 guestroom 114 is omitted from L1.A. Room 109 is Mechanical on E3.0 and is not a guestroom.", "resolution": null, "rule": "No room-number substitution, feeder reassignment, or load correction is inferred." } }, { "sourcePanel": "L2.A", "circuits": "1-24", "rooms": [ "201", "202", "203", "204", "205", "206", "207", "208", "209", "210", "211", "212" ], "connectedSUBVA": 167809, "demandSUBVA": 68802 }, { "sourcePanel": "L2.B", "circuits": "1-24", "rooms": [ "213", "214", "215", "216", "217", "218", "219", "220", "221", "222", "224", "226" ], "connectedSUBVA": 164804, "demandSUBVA": 67570 } ], "lightingAndSite": { "panel": "L1.B", "items": [ "electrical/mechanical-room lighting", "restroom/sales", "laundry", "fitness/guest laundry", "lobby", "corridors floors 1-5", "stairs", "monument sign", "site lighting", "building sign", "exterior lighting", "flag pole" ], "connectedLTGVA": 12943, "demandLTGVA": 16178 }, "mechanicalAndHVAC": [ { "panel": "L2.A", "circuits": [ 30 ], "item": "FIRE SMOKE DAMPER", "VA": 500 }, { "panel": "L2.B", "circuits": [ 26, 28, 30, 32 ], "item": "EUH", "connectedHTGVA": 10000 }, { "panel": "L1.C", "circuits": [ 9 ], "item": "RCPTS - ELECT/MECHANICAL", "VA": 720 }, { "panel": "L1.D", "circuits": [ 12, 14, 16 ], "item": "GAS WATER HEATER", "VA": [ 1440, 960, 960 ] }, { "panel": "L1.D", "circuits": [ 18 ], "item": "MOTORIZED DAMPER", "VA": 500 }, { "panel": "L1.D", "circuits": [ 20 ], "item": "FIRE SMOKE DAMPER", "VA": 500 }, { "panel": "L1.D", "circuits": [ 33, 35, 37, 39 ], "item": "RCPTS - MAINTENANCE FOR PTAC", "VAperTwoPoleCircuit": 1468 } ], "equipmentAndSpecial": [ { "panel": "L2.A", "circuits": [ 32 ], "item": "ICE MACHINE", "VA": 1500, "note": "CLASS A GFCI BREAKER" }, { "panel": "L1.C", "circuits": [ 30 ], "item": "ICE MACHINE", "VA": 1500, "note": "CLASS A GFCI BREAKER" }, { "panel": "L1.C", "circuits": [ 34, 36, 38, 40, 42, 44, 46 ], "items": [ "FREEZER", "REFRIGERATOR", "WATER DISPENSER", "CONVENIENCE" ] }, { "panel": "L1.C", "circuits": [ 48 ], "item": "MOTORIZED SHADE", "VA": 500 } ], "washerDryer": { "panel": "L1.D", "circuits": [ 1, 3, 5, 7, 9, 11, 13, 15, 17, 19, 21, 23, 25, 27, 29, 31 ], "notes": [ "GFCI BREAKER tags printed", "panel note requires field verification with laundry manufacturer and codes" ] }, "boosterAndCirculationPumps": { "panel": "L1.D", "boosterPumpCircuits": [ 2, 4, 6 ], "boosterPumpVAperPole": 3309, "circulationPumpCircuits": [ 8, 10 ], "circulationPumpVA": 441, "note": "HPs, breaker sizes, and cable sizes require field verification against plumbing equipment schedule" }, "electricVehicle": { "circuitOccurrences": 0, "allPanelLoadCodeRows": "EVCS = 125% ELECTRIC VEHICLE CHARGING STATION : (N/A)", "connectedVA": 0, "demandVA": 0 }, "largestMotor": { "allPanels": "LGR rows print N/A and zero; no largest-motor adder is scheduled" }, "roomMappingStatus": "Panel schedules identify guestroom numbers and room types, but this audit does not multiply or infer downstream branch-device quantities." }, "validation": { "panelCount": 6, "circuitRowCount": 276, "expectedCircuitRowCount": 276, "panelIndexMatchesSchedules": true, "allCircuitNumbersPresent": true, "crossSheetRoomConflictRecorded": true, "printedBlanksPreserved": true, "printedContinuationArrowsPreserved": true, "arithmeticChecks": [ { "panel": "L2.A", "sumOfPrintedCircuitVoltAmps": 171430, "sumOfPrintedPhasePairVA": 171430, "sumOfConnectedLoadCodeVA": 171429, "printedConnectedVA": 171429, "circuitVsPrintedDeltaVA": 1, "phaseVsPrintedDeltaVA": 1, "loadCodeVsPrintedDeltaVA": 0 }, { "panel": "L1.B", "sumOfPrintedCircuitVoltAmps": 12947, "sumOfPrintedPhasePairVA": 12947, "sumOfConnectedLoadCodeVA": 12943, "printedConnectedVA": 12943, "circuitVsPrintedDeltaVA": 4, "phaseVsPrintedDeltaVA": 4, "loadCodeVsPrintedDeltaVA": 0 }, { "panel": "L2.B", "sumOfPrintedCircuitVoltAmps": 174804, "sumOfPrintedPhasePairVA": 174804, "sumOfConnectedLoadCodeVA": 174804, "printedConnectedVA": 174804, "circuitVsPrintedDeltaVA": 0, "phaseVsPrintedDeltaVA": 0, "loadCodeVsPrintedDeltaVA": 0 }, { "panel": "L1.C", "sumOfPrintedCircuitVoltAmps": 58264, "sumOfPrintedPhasePairVA": 58264, "sumOfConnectedLoadCodeVA": 58264, "printedConnectedVA": 58264, "circuitVsPrintedDeltaVA": 0, "phaseVsPrintedDeltaVA": 0, "loadCodeVsPrintedDeltaVA": 0 }, { "panel": "L1.A", "sumOfPrintedCircuitVoltAmps": 154422, "sumOfPrintedPhasePairVA": 154422, "sumOfConnectedLoadCodeVA": 154421, "printedConnectedVA": 154421, "circuitVsPrintedDeltaVA": 1, "phaseVsPrintedDeltaVA": 1, "loadCodeVsPrintedDeltaVA": 0 }, { "panel": "L1.D", "sumOfPrintedCircuitVoltAmps": 49641, "sumOfPrintedPhasePairVA": 49641, "sumOfConnectedLoadCodeVA": 49639, "printedConnectedVA": 49639, "circuitVsPrintedDeltaVA": 2, "phaseVsPrintedDeltaVA": 2, "loadCodeVsPrintedDeltaVA": 0 } ] }, "issues": [ { "number": 1, "severity": "arithmetic", "text": "L1.A printed guestroom row values sum to 154,422 VA, while the connected SUB and total VA rows print 154,421 VA: 1 VA difference." }, { "number": 2, "severity": "arithmetic", "text": "L2.A printed guestroom row values sum to 167,810 VA, while the connected SUB row prints 167,809 VA; with REC 1,620 VA and EQUIP 2,000 VA, the component sum is 171,430 VA versus the printed total 171,429 VA: 1 VA difference." }, { "number": 3, "severity": "description-load mismatch", "text": "L2.B circuit 2 is labeled PANEL “A” / 219 - KING STUDIO but prints 8,522 VA on each pole, unlike the 6,694 VA used for other King Studio feeds; no correction was inferred." }, { "number": 4, "severity": "description-load mismatch", "text": "L2.B panels /220, /222, and /224 are labeled DOUBLE QUEEN but print 6,694 VA on each pole, while /216 and /218 DOUBLE QUEEN print 6,817 VA; no correction was inferred." }, { "number": 5, "severity": "coordination", "text": "General Notes 2-3 require utility-current verification and coordination of panel/branch-breaker AIC ratings with transformer fault current." }, { "number": 6, "severity": "coordination", "text": "L1.D laundry and booster-pump breaker/cable data are explicitly subject to field verification; scheduled values must not be treated as finally coordinated." }, { "number": 7, "severity": "reference-chain", "text": "The plumbing equipment schedule needed for L1.D booster-pump verification is not identified by sheet number on E6.1." }, { "number": 8, "severity": "reference-chain", "text": "Guestroom subpanel labels provide room numbers and types but not a cross-sheet branch-device reconciliation; downstream device quantities cannot be inferred from this schedule." }, { "number": 9, "severity": "arithmetic", "text": "L1.B printed circuit/phase-pair values sum to 12,947 VA, while the connected LTG and total VA rows print 12,943 VA: 4 VA difference. The printed demand value of 16,178 VA is preserved without correction." }, { "number": 10, "severity": "arithmetic", "text": "L1.D printed circuit/phase-pair values sum to 49,641 VA, while the connected EQUIP and total VA rows print 49,639 VA: 2 VA difference. Connected and demand totals are preserved as printed." }, { "number": 11, "severity": "ev", "text": "EVCS appears only as zero/N/A load-code rows on all six schedules; no EV circuit is scheduled on E6.1." }, { "number": 12, "severity": "critical cross-sheet conflict", "text": "L1.A is independently reported as printing 12 guest feeder rows 101-112, while E3.0 registers 11 guestrooms 101-108, 110, 112, and 114. E3.0 identifies 109 as Mechanical and 111 as Engineer; L1.A assigns a guest feeder to 111 and omits guestroom 114. L1.A's own SUB demand formula says FOR 11 UNITS. No correction or feeder reassignment is inferred." } ], "secondaryAudit": { "schema": "electrical-panel-schedule-secondary-verification-v1", "sheet": { "number": "E6.1", "title": "ELECTRICAL PANELS SCHEDULE", "engineeringPdfPage": 54, "project": "HOME 2 SUITES, BRADENTON, FL", "projectNumber": "#210729", "date": "NOV. 22, 2024", "sourceImage": "/workspace/sites/ssx-cover-release/tmp/pdfs/next3-e52-e61/source-54.png", "sourcePixels": [ 10800, 7200 ], "panelIndex": [ "L2.A", "L2.B", "L1.A", "L1.B", "L1.C", "L1.D" ], "panelScheduleCount": 6 }, "method": { "status": "independent visual recomputation", "basis": [ "Full-resolution 10800x7200 raster reviewed by schedule region.", "Circuit descriptions, breaker/pole fields, displayed VA, load-code totals, phase totals and note blocks were transcribed independently.", "Repeated vertical arrows were treated as continuation of the printed description and breaker specification only where the P column contains an occupied pole entry.", "SPACE ONLY positions were excluded from installed-breaker counts; printed SPARE positions with pole and breaker data were retained as installed spare breaker positions.", "Displayed integer circuit VA was summed separately from printed schedule totals to expose rounding or formula discrepancies." ], "reviewRegionsSourcePixels": { "L2.A": [ 430, 450, 4730, 2100 ], "L2.B": [ 430, 2150, 4730, 3800 ], "L1.A": [ 430, 3900, 4730, 5550 ], "L1.B": [ 4770, 450, 9070, 2100 ], "L1.C": [ 4770, 2100, 9070, 4000 ], "L1.D": [ 4770, 4400, 9070, 6000 ], "generalNotes": [ 400, 5550, 4800, 6200 ] } }, "panels": [ { "id": "L2.A", "header": { "fedFrom": "MDP", "voltage": "120/208V, 3PH, 4W", "enclosure": "NEMA-1", "aicRatingKA": 22, "busA": 250, "busMaterial": "COPPER", "mainsA": 250, "mainType": "M.L.O", "mounting": "SURFACE MOUNTED", "location": "STORAGE 2ND FLOOR", "positions": 42 }, "occupied": { "activePolePositions": 28, "spareBreakerPolePositions": 7, "installedBreakerPolePositions": 35, "spaceOnlyPositions": 7, "activeCircuits": [ 1, 3, 5, 7, 9, 11, 13, 15, 17, 19, 21, 23, 2, 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24, 26, 28, 30, 32 ], "spareCircuits": [ 25, 27, 34, 36, 38, 40, 42 ], "spaceOnlyCircuits": [ 29, 31, 33, 35, 37, 39, 41 ] }, "breakerPatterns": [ { "rating": "80/2", "activeBreakers": 10, "spareBreakers": 1, "totalBreakers": 11 }, { "rating": "100/2", "activeBreakers": 2, "spareBreakers": 0, "totalBreakers": 2 }, { "rating": "20/1", "activeBreakers": 4, "spareBreakers": 5, "totalBreakers": 9 } ], "circuitGroups": [ { "circuits": [ 1, 3 ], "description": "PANEL \"A\" / 201 - KING STUDIO", "loadType": "SUB", "breaker": "80/2", "displayedVAEachPole": 6694 }, { "circuits": [ 5, 7 ], "description": "PANEL \"B\" / 202 - KING ONE BEDROOM", "loadType": "SUB", "breaker": "100/2", "displayedVAEachPole": 8443 }, { "circuits": [ 9, 11 ], "description": "PANEL \"A\" / 203 - KING STUDIO", "loadType": "SUB", "breaker": "80/2", "displayedVAEachPole": 6694 }, { "circuits": [ 13, 15 ], "description": "PANEL \"A\" / 204 - KING STUDIO", "loadType": "SUB", "breaker": "80/2", "displayedVAEachPole": 6694 }, { "circuits": [ 17, 19 ], "description": "PANEL \"A\" / 205 - KING STUDIO", "loadType": "SUB", "breaker": "80/2", "displayedVAEachPole": 6694 }, { "circuits": [ 21, 23 ], "description": "PANEL \"A\" / 206 - KING STUDIO", "loadType": "SUB", "breaker": "80/2", "displayedVAEachPole": 6694 }, { "circuits": [ 2, 4 ], "description": "PANEL \"B\" / 207 - ACC KING ONE BEDROOM", "loadType": "SUB", "breaker": "100/2", "displayedVAEachPole": 8522 }, { "circuits": [ 6, 8 ], "description": "PANEL \"A\" / 208 - KING STUDIO", "loadType": "SUB", "breaker": "80/2", "displayedVAEachPole": 6694 }, { "circuits": [ 10, 12 ], "description": "PANEL \"A\" / 209 - KING STUDIO", "loadType": "SUB", "breaker": "80/2", "displayedVAEachPole": 6694 }, { "circuits": [ 14, 16 ], "description": "PANEL \"A\" / 210 - KING STUDIO", "loadType": "SUB", "breaker": "80/2", "displayedVAEachPole": 6694 }, { "circuits": [ 18, 20 ], "description": "PANEL \"A\" / 211 - KING STUDIO", "loadType": "SUB", "breaker": "80/2", "displayedVAEachPole": 6694 }, { "circuits": [ 22, 24 ], "description": "PANEL \"A\" / 212 - KING STUDIO", "loadType": "SUB", "breaker": "80/2", "displayedVAEachPole": 6694 }, { "circuits": [ 26 ], "description": "RCPTS - CORRIDOR", "loadType": "REC", "breaker": "20/1", "displayedVA": 900 }, { "circuits": [ 28 ], "description": "RCPTS - CORRIDOR/STORAGE", "loadType": "REC", "breaker": "20/1", "displayedVA": 720 }, { "circuits": [ 30 ], "description": "FIRE SMOKE DAMPER", "loadType": "EQUIP", "breaker": "20/1", "displayedVA": 500 }, { "circuits": [ 32 ], "description": "ICE MACHINE", "loadType": "EQUIP", "breaker": "20/1", "displayedVA": 1500, "note": "CLASS A GFCI BREAKER" }, { "circuits": [ 25, 27 ], "description": "SPARE", "kind": "spare", "breaker": "80/2" }, { "circuits": [ 34, 36, 38, 40, 42 ], "description": "SPARE", "kind": "spare", "breaker": "20/1" } ], "loadsVA": { "connectedByCode": { "LTG": 0, "REC": 1620, "EQUIP": 2000, "AC": 0, "HTG": 0, "LGR": 0, "KIT": 0, "SUB": 167809, "GLTG": 0, "EVCS": 0 }, "demandByCode": { "LTG": 0, "REC": 1620, "EQUIP": 2000, "AC": 0, "HTG": 0, "LGR": 0, "KIT": 0, "SUB": 68802, "GLTG": 0, "EVCS": 0 }, "connectedTotal": 171429, "demandTotal": 72422, "displayedCircuitVASum": 171430, "displayedRowsMinusPrintedTotal": 1 }, "phaseTotals": { "connectedKVA": { "A": 59.53, "B": 56.1, "C": 55.8 }, "connectedAmps": { "A": 496.07, "B": 467.5, "C": 465.0 }, "demandKVA": { "A": 25.82, "B": 23.43, "C": 23.17 }, "demandAmps": { "A": 215.19, "B": 195.22, "C": 193.11 }, "scheduleConnectedAmps": 476, "scheduleDemandAmps": 201 }, "panelSpecificNoteCount": 0 }, { "id": "L2.B", "header": { "fedFrom": "MDP", "voltage": "120/208V, 3PH, 4W", "enclosure": "NEMA-1", "aicRatingKA": 22, "busA": 250, "busMaterial": "COPPER", "mainsA": 250, "mainType": "M.L.O", "mounting": "SURFACE MOUNTED", "location": "STORAGE 2ND FLOOR", "positions": 42 }, "occupied": { "activePolePositions": 28, "spareBreakerPolePositions": 5, "installedBreakerPolePositions": 33, "spaceOnlyPositions": 9, "activeCircuits": [ 1, 3, 5, 7, 9, 11, 13, 15, 17, 19, 21, 23, 2, 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24, 26, 28, 30, 32 ], "spareCircuits": [ 25, 27, 34, 36, 38 ], "spaceOnlyCircuits": [ 29, 31, 33, 35, 37, 39, 41, 40, 42 ] }, "breakerPatterns": [ { "rating": "80/2", "activeBreakers": 11, "spareBreakers": 1, "totalBreakers": 12 }, { "rating": "100/2", "activeBreakers": 1, "spareBreakers": 0, "totalBreakers": 1 }, { "rating": "30/2", "activeBreakers": 2, "spareBreakers": 0, "totalBreakers": 2 }, { "rating": "20/1", "activeBreakers": 0, "spareBreakers": 3, "totalBreakers": 3 } ], "circuitGroups": [ { "circuits": [ 1, 3 ], "description": "PANEL \"A\" / 213 - KING STUDIO", "loadType": "SUB", "breaker": "80/2", "displayedVAEachPole": 6694 }, { "circuits": [ 5, 7 ], "description": "PANEL \"A\" / 214 - KING STUDIO", "loadType": "SUB", "breaker": "80/2", "displayedVAEachPole": 6694 }, { "circuits": [ 9, 11 ], "description": "PANEL \"A\" / 215 - KING STUDIO", "loadType": "SUB", "breaker": "80/2", "displayedVAEachPole": 6694 }, { "circuits": [ 13, 15 ], "description": "PANEL \"A\" / 216 - DOUBLE QUEEN", "loadType": "SUB", "breaker": "80/2", "displayedVAEachPole": 6817 }, { "circuits": [ 17, 19 ], "description": "PANEL \"A\" / 217 - KING STUDIO", "loadType": "SUB", "breaker": "80/2", "displayedVAEachPole": 6694 }, { "circuits": [ 21, 23 ], "description": "PANEL \"A\" / 218 - DOUBLE QUEEN", "loadType": "SUB", "breaker": "80/2", "displayedVAEachPole": 6817 }, { "circuits": [ 2, 4 ], "description": "PANEL \"A\" / 219 - KING STUDIO", "loadType": "SUB", "breaker": "100/2", "displayedVAEachPole": 8522 }, { "circuits": [ 6, 8 ], "description": "PANEL \"A\" / 220 - DOUBLE QUEEN", "loadType": "SUB", "breaker": "80/2", "displayedVAEachPole": 6694 }, { "circuits": [ 10, 12 ], "description": "PANEL \"A\" / 221 - KING STUDIO", "loadType": "SUB", "breaker": "80/2", "displayedVAEachPole": 6694 }, { "circuits": [ 14, 16 ], "description": "PANEL \"A\" / 222 - DOUBLE QUEEN", "loadType": "SUB", "breaker": "80/2", "displayedVAEachPole": 6694 }, { "circuits": [ 18, 20 ], "description": "PANEL \"A\" / 224 - DOUBLE QUEEN", "loadType": "SUB", "breaker": "80/2", "displayedVAEachPole": 6694 }, { "circuits": [ 22, 24 ], "description": "PANEL \"A\" / 226 - KING ACC", "loadType": "SUB", "breaker": "80/2", "displayedVAEachPole": 6694 }, { "circuits": [ 26, 28 ], "description": "EUH", "loadType": "HTG", "breaker": "30/2", "displayedVAEachPole": 2500 }, { "circuits": [ 30, 32 ], "description": "EUH", "loadType": "HTG", "breaker": "30/2", "displayedVAEachPole": 2500 }, { "circuits": [ 25, 27 ], "description": "SPARE", "kind": "spare", "breaker": "80/2" }, { "circuits": [ 34, 36, 38 ], "description": "SPARE", "kind": "spare", "breaker": "20/1" } ], "loadsVA": { "connectedByCode": { "LTG": 0, "REC": 0, "EQUIP": 0, "AC": 0, "HTG": 10000, "LGR": 0, "KIT": 0, "SUB": 164804, "GLTG": 0, "EVCS": 0 }, "demandByCode": { "LTG": 0, "REC": 0, "EQUIP": 0, "AC": 0, "HTG": 10000, "LGR": 0, "KIT": 0, "SUB": 67570, "GLTG": 0, "EVCS": 0 }, "connectedTotal": 174804, "demandTotal": 77570, "displayedCircuitVASum": 174804, "displayedRowsMinusPrintedTotal": 0 }, "phaseTotals": { "connectedKVA": { "A": 60.5, "B": 58.13, "C": 56.18 }, "connectedAmps": { "A": 504.19, "B": 484.38, "C": 468.13 }, "demandKVA": { "A": 27.76, "B": 25.31, "C": 24.51 }, "demandAmps": { "A": 231.3, "B": 210.89, "C": 204.22 }, "scheduleConnectedAmps": 486, "scheduleDemandAmps": 215 }, "panelSpecificNoteCount": 0 }, { "id": "L1.A", "header": { "fedFrom": "MDP", "voltage": "120/208V, 3PH, 4W", "enclosure": "NEMA-1", "aicRatingKA": 42, "busA": 225, "busMaterial": "COPPER", "mainsA": 225, "mainType": "M.L.O", "mounting": "SURFACE MOUNTED", "location": "ELEC. RM. 1ST FLOOR", "positions": 42 }, "occupied": { "activePolePositions": 22, "spareBreakerPolePositions": 2, "installedBreakerPolePositions": 24, "spaceOnlyPositions": 18, "activeCircuits": [ 1, 3, 5, 7, 9, 11, 13, 15, 17, 19, 21, 23, 2, 4, 6, 8, 10, 12, 14, 16, 18, 20 ], "spareCircuits": [ 25, 27 ], "spaceOnlyCircuits": [ 29, 31, 33, 35, 37, 39, 41, 22, 24, 26, 28, 30, 32, 34, 36, 38, 40, 42 ] }, "breakerPatterns": [ { "rating": "80/2", "activeBreakers": 9, "spareBreakers": 1, "totalBreakers": 10 }, { "rating": "100/2", "activeBreakers": 2, "spareBreakers": 0, "totalBreakers": 2 } ], "circuitGroups": [ { "circuits": [ 1, 3 ], "description": "PANEL \"A\" / 101 - KING STUDIO", "loadType": "SUB", "breaker": "80/2", "displayedVAEachPole": 6694 }, { "circuits": [ 5, 7 ], "description": "PANEL \"B\" / 102 - KING ONE BEDROOM", "loadType": "SUB", "breaker": "100/2", "displayedVAEachPole": 8443 }, { "circuits": [ 9, 11 ], "description": "PANEL \"A\" / 103 - KING STUDIO", "loadType": "SUB", "breaker": "80/2", "displayedVAEachPole": 6694 }, { "circuits": [ 13, 15 ], "description": "PANEL \"A\" / 104 - KING STUDIO", "loadType": "SUB", "breaker": "80/2", "displayedVAEachPole": 6694 }, { "circuits": [ 17, 19 ], "description": "PANEL \"A\" / 105 - KING STUDIO", "loadType": "SUB", "breaker": "80/2", "displayedVAEachPole": 6694 }, { "circuits": [ 21, 23 ], "description": "PANEL \"A\" / 106 - KING STUDIO", "loadType": "SUB", "breaker": "80/2", "displayedVAEachPole": 6694 }, { "circuits": [ 2, 4 ], "description": "PANEL \"B\" / 107 - ACC KING ONE BEDROOM", "loadType": "SUB", "breaker": "100/2", "displayedVAEachPole": 8522 }, { "circuits": [ 6, 8 ], "description": "PANEL \"A\" / 108 - KING STUDIO", "loadType": "SUB", "breaker": "80/2", "displayedVAEachPole": 6694 }, { "circuits": [ 10, 12 ], "description": "PANEL \"A\" / 110 - KING STUDIO", "loadType": "SUB", "breaker": "80/2", "displayedVAEachPole": 6694 }, { "circuits": [ 14, 16 ], "description": "PANEL \"A\" / 111 - KING STUDIO", "loadType": "SUB", "breaker": "80/2", "displayedVAEachPole": 6694 }, { "circuits": [ 18, 20 ], "description": "PANEL \"A\" / 112 - KING STUDIO", "loadType": "SUB", "breaker": "80/2", "displayedVAEachPole": 6694 }, { "circuits": [ 25, 27 ], "description": "SPARE", "kind": "spare", "breaker": "80/2" } ], "loadsVA": { "connectedByCode": { "LTG": 0, "REC": 0, "EQUIP": 0, "AC": 0, "HTG": 0, "LGR": 0, "KIT": 0, "SUB": 154421, "GLTG": 0, "EVCS": 0 }, "demandByCode": { "LTG": 0, "REC": 0, "EQUIP": 0, "AC": 0, "HTG": 0, "LGR": 0, "KIT": 0, "SUB": 64857, "GLTG": 0, "EVCS": 0 }, "connectedTotal": 154421, "demandTotal": 64857, "displayedCircuitVASum": 154422, "displayedRowsMinusPrintedTotal": 1 }, "phaseTotals": { "connectedKVA": { "A": 57.13, "B": 48.69, "C": 48.61 }, "connectedAmps": { "A": 476.07, "B": 405.72, "C": 405.05 }, "demandKVA": { "A": 23.99, "B": 20.45, "C": 20.41 }, "demandAmps": { "A": 199.95, "B": 170.4, "C": 170.12 }, "scheduleConnectedAmps": 429, "scheduleDemandAmps": 180 }, "panelSpecificNoteCount": 0 }, { "id": "L1.B", "header": { "fedFrom": "MDP", "voltage": "120/208V, 3PH, 4W", "enclosure": "NEMA-1", "aicRatingKA": 30, "busA": 100, "busMaterial": "COPPER", "mainsA": 100, "mainType": "M.L.O", "mounting": "SURFACE MOUNTED", "location": "ELEC. RM. 1ST FLOOR", "positions": 42 }, "occupied": { "activePolePositions": 29, "spareBreakerPolePositions": 5, "installedBreakerPolePositions": 34, "spaceOnlyPositions": 8, "activeCircuits": [ 1, 3, 5, 7, 9, 11, 13, 15, 17, 19, 21, 23, 25, 27, 29, 31, 33, 2, 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24 ], "spareCircuits": [ 26, 28, 30, 32, 34 ], "spaceOnlyCircuits": [ 35, 37, 39, 41, 36, 38, 40, 42 ] }, "breakerPatterns": [ { "rating": "20/1", "activeBreakers": 25, "spareBreakers": 5, "totalBreakers": 30 }, { "rating": "20/2", "activeBreakers": 2, "spareBreakers": 0, "totalBreakers": 2 } ], "circuitGroups": [ { "circuits": [ 1 ], "description": "LTS - ELEC / MECH. RM", "loadType": "LTG", "breaker": "20/1", "displayedVA": 378 }, { "circuits": [ 3 ], "description": "LTS - RESTROOM/SALES", "loadType": "LTG", "breaker": "20/1", "displayedVA": 150 }, { "circuits": [ 5 ], "description": "LTS - LAUNDRY", "loadType": "LTG", "breaker": "20/1", "displayedVA": 432 }, { "circuits": [ 7 ], "description": "LTS - FITNESS/GUEST LAUNDRY", "loadType": "LTG", "breaker": "20/1", "displayedVA": 255 }, { "circuits": [ 9, 11 ], "description": "LTS - LOBBY", "loadType": "LTG", "breaker": "20/1", "displayedVAEach": 400 }, { "circuits": [ 13, 15 ], "description": "LTS - CORRIDOR 1ST FL", "loadType": "LTG", "breaker": "20/1", "displayedVAEach": 340 }, { "circuits": [ 17, 19 ], "description": "LTS - CORRIDOR 2ND FL", "loadType": "LTG", "breaker": "20/1", "displayedVAEach": 413 }, { "circuits": [ 21, 23 ], "description": "LTS - CORRIDOR 3RD FL", "loadType": "LTG", "breaker": "20/1", "displayedVAEach": 413 }, { "circuits": [ 25, 27 ], "description": "LTS - CORRIDOR 4TH FL", "loadType": "LTG", "breaker": "20/1", "displayedVAEach": 413 }, { "circuits": [ 29, 31 ], "description": "LTS - CORRIDOR 5TH FL", "loadType": "LTG", "breaker": "20/1", "displayedVAEach": 413 }, { "circuits": [ 33 ], "description": "LTS - STAIRS", "loadType": "LTG", "breaker": "20/1", "displayedVA": 720 }, { "circuits": [ 2, 4, 6 ], "description": "MONUMENT SIGN", "loadType": "LTG", "breaker": "20/1", "displayedVAEach": 1200, "noteReferences": [ 1, 2 ] }, { "circuits": [ 8, 10 ], "description": "LTS - SITE LIGHTING", "loadType": "LTG", "breaker": "20/2", "displayedVAEachPole": 140, "noteReferences": [ 1 ] }, { "circuits": [ 12, 14 ], "description": "LTS - SITE LIGHTING", "loadType": "LTG", "breaker": "20/2", "displayedVAEachPole": 112, "noteReferences": [ 1 ] }, { "circuits": [ 16 ], "description": "BUILDING SIGN", "loadType": "LTG", "breaker": "20/1", "displayedVA": 1200, "noteReferences": [ 1 ] }, { "circuits": [ 18 ], "description": "LTS - EXTERIOR", "loadType": "LTG", "breaker": "20/1", "displayedVA": 324, "noteReferences": [ 1 ] }, { "circuits": [ 20 ], "description": "LTS - FLAG POLE", "loadType": "LTG", "breaker": "20/1", "displayedVA": 200, "noteReferences": [ 1 ] }, { "circuits": [ 22 ], "description": "LTS - EXTERIOR", "loadType": "LTG", "breaker": "20/1", "displayedVA": 300, "noteReferences": [ 1 ] }, { "circuits": [ 24 ], "description": "LTS - EXTERIOR", "loadType": "LTG", "breaker": "20/1", "displayedVA": 100, "noteReferences": [ 1 ] }, { "circuits": [ 26, 28, 30, 32, 34 ], "description": "SPARE", "kind": "spare", "breaker": "20/1" } ], "loadsVA": { "connectedByCode": { "LTG": 12943, "REC": 0, "EQUIP": 0, "AC": 0, "HTG": 0, "LGR": 0, "KIT": 0, "SUB": 0, "GLTG": 0, "EVCS": 0 }, "demandByCode": { "LTG": 16178, "REC": 0, "EQUIP": 0, "AC": 0, "HTG": 0, "LGR": 0, "KIT": 0, "SUB": 0, "GLTG": 0, "EVCS": 0 }, "connectedTotal": 12943, "demandTotal": 16178, "displayedCircuitVASum": 12947, "displayedRowsMinusPrintedTotal": 4, "nearestInteger125PercentOfPrintedConnected": 16179, "printedDemandMinusNearestInteger": -1 }, "phaseTotals": { "connectedKVA": { "A": 3.86, "B": 5.27, "C": 3.81 }, "connectedAmps": { "A": 32.19, "B": 43.96, "C": 31.71 }, "demandKVA": { "A": 4.83, "B": 6.59, "C": 4.76 }, "demandAmps": { "A": 40.23, "B": 54.95, "C": 39.64 }, "scheduleConnectedAmps": 36, "scheduleDemandAmps": 45 }, "panelSpecificNotes": [ "1 - CONTROLLED BY A 20A, MECH. HELD LIGHTING CONTACTORS WHICH IS CONTROLLED BY A 7-DAY, N-1 TIME CLOCK WITH 4 HRS BATTERIES IN PANEL L1.B.", "2 - PROVIDE HANDLE TIES FOR CIRCUIT BREAKERS TO DISCONNECT ALL UNGROUNDED CONDUCTORS SIMULTANEOUSLY ON MULTI-WIRE BRANCH CIRCUITS." ], "panelSpecificNoteCount": 2 }, { "id": "L1.C", "header": { "fedFrom": "MDP", "voltage": "120/208V, 3PH, 4W", "enclosure": "NEMA-1", "aicRatingKA": 42, "busA": 200, "busMaterial": "COPPER", "mainsA": 200, "mainType": "M.L.O", "mounting": "SURFACE MOUNTED", "location": "ELEC. RM. 1ST FLOOR", "positions": 66 }, "occupied": { "activePolePositions": 53, "spareBreakerPolePositions": 10, "installedBreakerPolePositions": 63, "spaceOnlyPositions": 3, "activeCircuits": [ 1, 3, 5, 7, 9, 11, 13, 15, 17, 19, 21, 23, 25, 27, 29, 31, 33, 35, 37, 39, 41, 43, 45, 47, 49, 2, 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 28, 30, 32, 34, 36, 38, 40, 42, 44, 46, 48, 50, 52, 54, 56, 58, 60 ], "spareCircuits": [ 51, 53, 55, 57, 59, 61, 63, 65, 24, 26 ], "spaceOnlyCircuits": [ 62, 64, 66 ] }, "breakerPatterns": [ { "rating": "20/1", "activeBreakers": 48, "spareBreakers": 10, "totalBreakers": 58 }, { "rating": "30/1", "activeBreakers": 5, "spareBreakers": 0, "totalBreakers": 5 } ], "circuitGroups": [ { "circuits": [ 1, 3 ], "description": "DOOR MOTOR", "loadType": "EQUIP", "breaker": "20/1", "displayedVAEach": 1500 }, { "circuits": [ 5 ], "description": "RCPTS - CORRIDOR/ENGINEER", "loadType": "REC", "breaker": "20/1", "displayedVA": 1080 }, { "circuits": [ 7 ], "description": "IG RCPTS - ENGINEER", "loadType": "REC", "breaker": "20/1", "displayedVA": 360 }, { "circuits": [ 9 ], "description": "RCPTS - ELECT/MECHANICAL", "loadType": "REC", "breaker": "20/1", "displayedVA": 720 }, { "circuits": [ 11 ], "description": "RCPTS - PBX", "loadType": "REC", "breaker": "20/1", "displayedVA": 720 }, { "circuits": [ 13 ], "description": "RCPTS - STORAGE/BREAKROOM", "loadType": "REC", "breaker": "20/1", "displayedVA": 720 }, { "circuits": [ 15 ], "description": "RCPTS - BREAKROOM REF.", "loadType": "EQUIP", "breaker": "20/1", "displayedVA": 500, "note": "GFCI BREAKER" }, { "circuits": [ 17, 19 ], "description": "RCPTS - BREAKROOM", "loadType": "EQUIP", "breaker": "20/1", "displayedVAEach": 1500 }, { "circuits": [ 21 ], "description": "RCPTS - LAUNDRY", "loadType": "REC", "breaker": "20/1", "displayedVA": 1260 }, { "circuits": [ 23 ], "description": "RCPTS - LAUNDRY/OUTDOOR", "loadType": "REC", "breaker": "20/1", "displayedVA": 720 }, { "circuits": [ 25 ], "description": "RCPTS - OFFICES", "loadType": "REC", "breaker": "20/1", "displayedVA": 1080 }, { "circuits": [ 27 ], "description": "IG RCPTS - OFFICES", "loadType": "REC", "breaker": "20/1", "displayedVA": 360 }, { "circuits": [ 29 ], "description": "IG RCPTS - OFFICES", "loadType": "REC", "breaker": "20/1", "displayedVA": 720 }, { "circuits": [ 31 ], "description": "IG RCPTS - OFFICES", "loadType": "REC", "breaker": "20/1", "displayedVA": 360 }, { "circuits": [ 33, 35 ], "description": "RCPTS - FRONT DESK", "loadType": "REC", "breaker": "20/1", "displayedVAEach": 1260 }, { "circuits": [ 37 ], "description": "RCPTS - MARKET", "loadType": "REC", "breaker": "20/1", "displayedVA": 360, "note": "GFCI BREAKER" }, { "circuits": [ 39, 41 ], "description": "RCPTS - LOBBY", "loadType": "REC", "breaker": "20/1", "displayedVAEach": 720 }, { "circuits": [ 43 ], "description": "RCPTS - LOBBY", "loadType": "REC", "breaker": "20/1", "displayedVA": 1440 }, { "circuits": [ 45 ], "description": "RCPTS - LOBBY", "loadType": "REC", "breaker": "20/1", "displayedVA": 720 }, { "circuits": [ 47 ], "description": "IG RCPTS - PRINTER", "loadType": "REC", "breaker": "20/1", "displayedVA": 720 }, { "circuits": [ 49 ], "description": "IG RCPTS - OUTDOOR", "loadType": "REC", "breaker": "20/1", "displayedVA": 360 }, { "circuits": [ 2 ], "description": "RCPTS - FITNESS/GUEST LAUNDRY", "loadType": "REC", "breaker": "20/1", "displayedVA": 1440 }, { "circuits": [ 4, 6, 8, 10, 12 ], "description": "RCPTS - FITNESS EQUIPMENT", "loadType": "EQUIP", "breaker": "30/1", "displayedVAEach": 2000 }, { "circuits": [ 14 ], "description": "RCPTS - TV LOUNGE", "loadType": "REC", "breaker": "20/1", "displayedVA": 1260 }, { "circuits": [ 16 ], "description": "RCPTS - LOBBY", "loadType": "REC", "breaker": "20/1", "displayedVA": 540 }, { "circuits": [ 18 ], "description": "RCPTS - OUTDOOR", "loadType": "REC", "breaker": "20/1", "displayedVA": 360 }, { "circuits": [ 20 ], "description": "IG RCPTS - SALES", "loadType": "REC", "breaker": "20/1", "displayedVA": 360 }, { "circuits": [ 22 ], "description": "RCPTS - SALES/CORRIDOR", "loadType": "REC", "breaker": "20/1", "displayedVA": 1440 }, { "circuits": [ 24, 26 ], "description": "SPARE", "kind": "spare", "breaker": "20/1" }, { "circuits": [ 28 ], "description": "RCPTS - OUTDOOR", "loadType": "REC", "breaker": "20/1", "displayedVA": 360 }, { "circuits": [ 30 ], "description": "ICE MACHINE", "loadType": "EQUIP", "breaker": "20/1", "displayedVA": 1500, "note": "CLASS A GFCI BREAKER" }, { "circuits": [ 32 ], "description": "MARKET", "loadType": "EQUIP", "breaker": "20/1", "displayedVA": 1500 }, { "circuits": [ 34 ], "description": "(E35) - FREEZER", "loadType": "EQUIP", "breaker": "20/1", "displayedVA": 744, "note": "GFCI BREAKER" }, { "circuits": [ 36 ], "description": "(E36) - REFRIGERATOR", "loadType": "EQUIP", "breaker": "20/1", "displayedVA": 1020, "note": "GFCI BREAKER" }, { "circuits": [ 38, 40 ], "description": "(E37) - WATER DISPENSER", "loadType": "EQUIP", "breaker": "20/1", "displayedVA": [ 180, 1400 ] }, { "circuits": [ 42, 44, 46 ], "description": "(E901) - CONVENIENCE", "loadType": "EQUIP", "breaker": "20/1", "displayedVAEach": 1500 }, { "circuits": [ 48 ], "description": "MOTORIZED SHADE", "loadType": "EQUIP", "breaker": "20/1", "displayedVA": 500 }, { "circuits": [ 50, 52 ], "description": "IG RCPTS - TEL BOARD", "loadType": "EQUIP", "breaker": "20/1", "displayedVAEach": 1500 }, { "circuits": [ 54, 56 ], "description": "IG RCPTS - SECURITY BOARD", "loadType": "EQUIP", "breaker": "20/1", "displayedVAEach": 1500 }, { "circuits": [ 58, 60 ], "description": "IG RCPTS - CABLE TV BOARD", "loadType": "EQUIP", "breaker": "20/1", "displayedVAEach": 1500 }, { "circuits": [ 51, 53, 55, 57, 59, 61, 63, 65 ], "description": "SPARE", "kind": "spare", "breaker": "20/1" } ], "loadsVA": { "connectedByCode": { "LTG": 0, "REC": 21420, "EQUIP": 36844, "AC": 0, "HTG": 0, "LGR": 0, "KIT": 0, "SUB": 0, "GLTG": 0, "EVCS": 0 }, "demandByCode": { "LTG": 0, "REC": 15710, "EQUIP": 36844, "AC": 0, "HTG": 0, "LGR": 0, "KIT": 0, "SUB": 0, "GLTG": 0, "EVCS": 0 }, "connectedTotal": 58264, "demandTotal": 52554, "displayedCircuitVASum": 58264, "displayedRowsMinusPrintedTotal": 0 }, "phaseTotals": { "connectedKVA": { "A": 18.92, "B": 20.02, "C": 19.32 }, "connectedAmps": { "A": 157.67, "B": 166.87, "C": 161.0 }, "demandKVA": { "A": 16.72, "B": 18.0, "C": 17.84 }, "demandAmps": { "A": 139.3, "B": 150.0, "C": 148.64 }, "scheduleConnectedAmps": 162, "scheduleDemandAmps": 146 }, "panelSpecificNotes": [ "1 - CONTRACTOR MUST PROVIDE ISOLATED GROUND BUS IN THE PANEL." ], "panelSpecificNoteCount": 1 }, { "id": "L1.D", "header": { "fedFrom": "MDP", "voltage": "120/208V, 3PH, 4W", "enclosure": "NEMA-1", "aicRatingKA": 42, "busA": 200, "busMaterial": "COPPER", "mainsA": 200, "mainType": "M.L.O", "mounting": "SURFACE MOUNTED", "location": "ELEC. RM. 1ST FLOOR", "positions": 42 }, "occupied": { "activePolePositions": 30, "spareBreakerPolePositions": 8, "installedBreakerPolePositions": 38, "spaceOnlyPositions": 4, "activeCircuits": [ 1, 3, 5, 7, 9, 11, 13, 15, 17, 19, 21, 23, 25, 27, 29, 31, 33, 35, 37, 39, 2, 4, 6, 8, 10, 12, 14, 16, 18, 20 ], "spareCircuits": [ 22, 24, 26, 28, 30, 32, 34, 36 ], "spaceOnlyCircuits": [ 41, 38, 40, 42 ] }, "breakerPatterns": [ { "rating": "20/1", "activeBreakers": 9, "spareBreakers": 8, "totalBreakers": 17 }, { "rating": "20/2", "activeBreakers": 4, "spareBreakers": 0, "totalBreakers": 4 }, { "rating": "30/2", "activeBreakers": 2, "spareBreakers": 0, "totalBreakers": 2 }, { "rating": "30/3", "activeBreakers": 2, "spareBreakers": 0, "totalBreakers": 2 }, { "rating": "60/3", "activeBreakers": 1, "spareBreakers": 0, "totalBreakers": 1 } ], "circuitGroups": [ { "circuits": [ 1, 3, 5 ], "description": "WASHER", "loadType": "EQUIP", "breaker": "30/3", "displayedVAEachPole": 2000, "note": "GFCI BREAKER" }, { "circuits": [ 7, 9, 11 ], "description": "WASHER", "loadType": "EQUIP", "breaker": "30/3", "displayedVAEachPole": 2000, "note": "GFCI BREAKER" }, { "circuits": [ 13, 15 ], "description": "DRYER (GAS HEAT)", "loadType": "EQUIP", "breaker": "20/2", "displayedVAEachPole": 750, "note": "GFCI BREAKER" }, { "circuits": [ 17, 19 ], "description": "DRYER (GAS HEAT)", "loadType": "EQUIP", "breaker": "20/2", "displayedVAEachPole": 750, "note": "GFCI BREAKER" }, { "circuits": [ 21 ], "description": "WASHER (GUEST LAUNDRY)", "loadType": "EQUIP", "breaker": "20/1", "displayedVA": 1800, "note": "GFCI BREAKER" }, { "circuits": [ 23 ], "description": "WASHER (GUEST LAUNDRY)", "loadType": "EQUIP", "breaker": "20/1", "displayedVA": 1800, "note": "GFCI BREAKER" }, { "circuits": [ 25, 27 ], "description": "DRYER (GUEST LAUNDRY)", "loadType": "EQUIP", "breaker": "30/2", "displayedVAEachPole": 2500, "note": "GFCI BREAKER" }, { "circuits": [ 29, 31 ], "description": "DRYER (GUEST LAUNDRY)", "loadType": "EQUIP", "breaker": "30/2", "displayedVAEachPole": 2500, "note": "GFCI BREAKER" }, { "circuits": [ 33, 35 ], "description": "RCPTS - MAINTENANCE FOR PTAC", "loadType": "EQUIP", "breaker": "20/2", "displayedVAEachPole": 1468 }, { "circuits": [ 37, 39 ], "description": "RCPTS - MAINTENANCE FOR PTAC", "loadType": "EQUIP", "breaker": "20/2", "displayedVAEachPole": 1468 }, { "circuits": [ 2, 4, 6 ], "description": "BOOSTER PUMP CONTROL PANEL (B.P)", "loadType": "EQUIP", "breaker": "60/3", "displayedVAEachPole": 3309 }, { "circuits": [ 8, 10 ], "description": "CIRCULATE PUMP CONTROL PANEL (C.P)", "loadType": "EQUIP", "breaker": "20/1", "displayedVAEach": 441 }, { "circuits": [ 12 ], "description": "GAS WATER HEATER", "loadType": "EQUIP", "breaker": "20/1", "displayedVA": 1440 }, { "circuits": [ 14, 16 ], "description": "GAS WATER HEATER", "loadType": "EQUIP", "breaker": "20/1", "displayedVAEach": 960 }, { "circuits": [ 18 ], "description": "MOTORIZED DAMPER", "loadType": "EQUIP", "breaker": "20/1", "displayedVA": 500 }, { "circuits": [ 20 ], "description": "FIRE SMOKE DAMPER", "loadType": "EQUIP", "breaker": "20/1", "displayedVA": 500 }, { "circuits": [ 22, 24, 26, 28, 30, 32, 34, 36 ], "description": "SPARE", "kind": "spare", "breaker": "20/1" } ], "loadsVA": { "connectedByCode": { "LTG": 0, "REC": 0, "EQUIP": 49639, "AC": 0, "HTG": 0, "LGR": 0, "KIT": 0, "SUB": 0, "GLTG": 0, "EVCS": 0 }, "demandByCode": { "LTG": 0, "REC": 0, "EQUIP": 49639, "AC": 0, "HTG": 0, "LGR": 0, "KIT": 0, "SUB": 0, "GLTG": 0, "EVCS": 0 }, "connectedTotal": 49639, "demandTotal": 49639, "displayedCircuitVASum": 49641, "displayedRowsMinusPrintedTotal": 2 }, "phaseTotals": { "connectedKVA": { "A": 17.18, "B": 16.7, "C": 15.77 }, "connectedAmps": { "A": 143.15, "B": 139.13, "C": 131.39 }, "demandKVA": { "A": 17.18, "B": 16.7, "C": 15.77 }, "demandAmps": { "A": 143.15, "B": 139.13, "C": 131.39 }, "scheduleConnectedAmps": 138, "scheduleDemandAmps": 138 }, "panelSpecificNotes": [ "1 - FIELD VERIFICATION BREAKER SIZES, BREAKER TYPE, ETC WITH LAUNDRY MANUFACTURER AND CODES REQUIREMENTS PRIOR TO INSTALLATION.", "2 - FIELD VERIFICATION HPs, BREAKER SIZES, CABLES SIZES FOR BOOSTER PUMPS WITH THE PLUMBING EQUIPMENT SCHEDULE PRIOR TO INSTALLATION." ], "panelSpecificNoteCount": 2 } ], "loadCodeDefinitions": { "LTG": "125% LIGHTING LOAD", "REC": "RCPTS LOAD (100% FIRST 10KVA +50% REMAIN)", "EQUIP": "EQUIPMENT LOAD", "AC": "HVAC LOAD", "HTG": "HEATING LOAD", "LGR": "125% LARGEST MOTOR", "KIT": "KITCHEN LOAD", "SUB": "SUB PANEL x demand factor shown per panel", "GLTG": "GUESTROOM LIGHTING LOAD", "EVCS": "125% ELECTRIC VEHICLE CHARGING STATION" }, "notes": { "general": [ "1. CONTRACTOR SHALL PROVIDE A PERMANENTLY AFFIXED LABEL WITH THE MAXIMUM FAULT CURRENT PER ARTICLE 110.24. THE LABEL SHALL INCLUDE THE DATE THE FAULT-CURRENT CALCULATION WAS PERFORMED AND BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. THE LABEL SHALL BE 2\"X3\" IN SIZE AND SHALL BE BLUE LETTERING ON A CONTRASTING BACKGROUND.", "2. CONTRACTOR TO VERIFY FINAL CURRENT VALUES FROM ELECTRICAL UTILITY COMPANY AND PROVIDE AIC PROTECTION ACCORDINGLY.", "3. AIC RATINGS OF ALL THE PANELS & BRANCH BREAKERS SHALL MATCH THE FAULT CURRENT OF THE TRANSFORMER." ], "generalNoteCount": 3, "panelSpecificNoteCount": 5, "dedicatedNoteStatementTotal": 8, "inlineParentheticalNoteCells": 22, "inlineParentheticalReferenceCount": 23, "inlineBreakdown": { "L2.A": { "cells": 1, "references": 1 }, "L2.B": { "cells": 0, "references": 0 }, "L1.A": { "cells": 0, "references": 0 }, "L1.B": { "cells": 8, "references": 9 }, "L1.C": { "cells": 5, "references": 5 }, "L1.D": { "cells": 8, "references": 8 } } }, "crossSheetChecks": [ { "id": "XS-01", "status": "MATCH", "subject": "panel headers versus E1.0 distribution schedule", "finding": "All six E6.1 voltage, bus, MLO, AIC and floor-location records agree with the E1.0 distribution records: L2.A/L2.B 250A 22kA; L1.A 225A 42kA; L1.B 100A 30kA; L1.C/L1.D 200A 42kA." }, { "id": "XS-02", "status": "CONFLICT", "subject": "E1.0A voltage-drop current versus E6.1 demand current", "finding": "Three feeder calculation currents are lower than E6.1 demand current: L1.A 164A versus 180A, L2.A 189A versus 201A, and L2.B 180A versus 215A. L1.B 45A, L1.C 146A and L1.D 138A match exactly.", "differencesA": { "L1.A": 16, "L2.A": 12, "L2.B": 35 } }, { "id": "XS-03", "status": "MATCH", "subject": "second-floor power callouts", "finding": "E3.1 callouts L2.A-26 corridor receptacles, L2.A-28 corridor/storage receptacles, L2.A-30 fire/smoke damper, and L2.B-26,28 plus L2.B-30,32 for two EUHs agree with E6.1." }, { "id": "XS-04", "status": "MATCH", "subject": "first-floor fire/smoke damper", "finding": "E3.0 assigns the Level 1 fire/smoke-damper J-boxes to L1.D-20; E6.1 lists L1.D-20 FIRE SMOKE DAMPER, 20/1, 500VA." }, { "id": "XS-05", "status": "MATCH_WITH_SCOPE_NOTE", "subject": "site and sign circuits", "finding": "E5.0 callouts L1.B-2,4,6, L1.B-8,10, L1.B-12,14, L1.B-18 and L1.B-20 reconcile to monument sign, two site-lighting pairs, exterior lighting and flag pole respectively. E3.5 L1.B-16 reconciles to BUILDING SIGN. E5.0 keeps the flagpole J-box optional, while E6.1 carries a 200VA branch load." }, { "id": "XS-06", "status": "MATCH", "subject": "upper-floor common and stair lighting", "finding": "Lighting plans use L1.B-17,19; 21,23; 25,27; 29,31 and stair circuit L1.B-33, matching the E6.1 floor-by-floor corridor and stairs descriptions." }, { "id": "XS-07", "status": "CONFLICT", "subject": "L1.A room 111 assignment versus E3.0 room names", "finding": "E6.1 L1.A circuits 14/16 print PANEL \"A\" / 111 - KING STUDIO. E3.0 labels room 111 ENGINEER and separately labels room 114 CONNECTING KING STUDIO; room 114 has no corresponding L1.A room-panel feeder row. L1.C also contains RCPTS - CORRIDOR/ENGINEER and IG RCPTS - ENGINEER loads. The room-number conflict is confirmed; 114 is a plausible intended number but is not substituted without design confirmation." } ], "issues": [ { "number": 1, "severity": "high", "type": "room_number_cross_sheet_conflict", "text": "L1.A circuits 14/16 identify room 111 as a king-studio panel, but E3.0 identifies room 111 as ENGINEER and room 114 as CONNECTING KING STUDIO. Confirm the intended feeder destination before installation; do not assume 111 should be changed to 114 without designer approval." }, { "number": 2, "severity": "high", "type": "cross_sheet_current_conflict", "text": "E1.0A voltage-drop calculations use lower currents than the E6.1 demand schedules for L1.A, L2.A and L2.B. Recalculate feeder voltage drop with the governing demand currents or document the basis for the lower values." }, { "number": 3, "severity": "medium", "type": "displayed_row_sum_mismatch", "text": "Displayed integer circuit VA sums exceed the printed connected totals by 1VA at L2.A, 1VA at L1.A, 4VA at L1.B and 2VA at L1.D. L2.B and L1.C reconcile exactly. This is consistent with hidden fractional calculation values or spreadsheet rounding, but the basis is not printed." }, { "number": 4, "severity": "medium", "type": "lighting_demand_rounding", "text": "L1.B prints 12,943VA connected and 16,178VA demand under 125% lighting. Nearest-integer arithmetic on the printed connected total is 16,179VA; the one-VA difference is unexplained and accompanies the four-VA displayed-row discrepancy." }, { "number": 5, "severity": "medium", "type": "field_verification_controls", "text": "L1.D fills laundry and booster-pump breaker/conductor values but its two notes require field verification with the laundry manufacturer, code requirements and plumbing equipment schedule. Treat those sizes as coordination-controlled rather than final procurement values." }, { "number": 6, "severity": "low", "type": "continuation_arrow_convention", "text": "Several SPARE and repeated-load blocks print an amp/pole value once with a vertical continuation arrow. Counts here include every circuit row whose P column is occupied; the sheet provides no explicit legend for the arrow convention." }, { "number": 7, "severity": "medium", "type": "downstream_schedule_chain", "text": "L1.A, L2.A and L2.B feed room panels called PANEL \"A\" and PANEL \"B\", but E6.1's panel index contains only the six L-panel schedules. The downstream A/B room-panel breaker schedules are not resolved on this sheet." }, { "number": 8, "severity": "low", "type": "equipment_reference_chain", "text": "L1.C equipment identifiers (E35), (E36), (E37) and (E901) are not tied to a schedule/detail reference on E6.1; loads are preserved as printed but equipment-source verification remains external." }, { "number": 9, "severity": "low", "type": "optional_flagpole_scope", "text": "E5.0 describes flagpole J-box scope as optional while E6.1 assigns L1.B-20 and 200VA to LTS - FLAG POLE. Authorization to install remains a scope decision, not a schedule arithmetic issue." } ], "validation": { "jsonValid": true, "panelCount": 6, "panelIndexCount": 6, "panelIdsUnique": true, "allPositionBalancesPass": true, "positionBalanceByPanel": { "L2.A": "28 active + 7 spare + 7 space = 42", "L2.B": "28 active + 5 spare + 9 space = 42", "L1.A": "22 active + 2 spare + 18 space = 42", "L1.B": "29 active + 5 spare + 8 space = 42", "L1.C": "53 active + 10 spare + 3 space = 66", "L1.D": "30 active + 8 spare + 4 space = 42" }, "printedConnectedDemandPairsVA": { "L2.A": [ 171429, 72422 ], "L2.B": [ 174804, 77570 ], "L1.A": [ 154421, 64857 ], "L1.B": [ 12943, 16178 ], "L1.C": [ 58264, 52554 ], "L1.D": [ 49639, 49639 ] }, "printedConnectedDemandCurrentsA": { "L2.A": [ 476, 201 ], "L2.B": [ 486, 215 ], "L1.A": [ 429, 180 ], "L1.B": [ 36, 45 ], "L1.C": [ 162, 146 ], "L1.D": [ 138, 138 ] }, "dedicatedNoteStatementTotal": 8, "crossSheetConflictCount": 2, "arithmeticOrRoundingIssueCount": 2 } }, "independentCrossCheck": { "schemaVersion": "1.0", "documentType": "independent_cross_sheet_reconciliation", "batch": { "sheets": [ "E5.2", "E6.0", "E6.1" ], "engineeringPdfPages": [ 52, 53, 54 ], "sourcePdf": "/workspace/sites/ssx-cover-release/source-plans/engineering.pdf", "sourceImages": [ "/workspace/sites/ssx-cover-release/tmp/pdfs/next3-e52-e61/source-52.png", "/workspace/sites/ssx-cover-release/tmp/pdfs/next3-e52-e61/source-53.png", "/workspace/sites/ssx-cover-release/tmp/pdfs/next3-e52-e61/source-54.png" ], "priorEvidence": [ "/workspace/scratch/e9eeb133d6f5/delegated-next5/e10.json", "/workspace/scratch/e9eeb133d6f5/delegated-next5/crosscheck.json", "/workspace/scratch/e9eeb133d6f5/delegated-e12-e24/crosscheck.json", "/workspace/scratch/e9eeb133d6f5/delegated-e30-e34/crosscheck.json", "/workspace/scratch/e9eeb133d6f5/delegated-e35-e51/crosscheck.json", "/workspace/scratch/e9eeb133d6f5/delegated-e35-e51/e50.json", "/workspace/scratch/e9eeb133d6f5/delegated-e35-e51/e51.json", "/workspace/scratch/e9eeb133d6f5/delegated-e52-e61/e60-secondary.json" ], "method": "Read-only comparison of the full 10800 x 7200 source rasters and established E1.0-E5.1 evidence. Cut-sheet selection boxes, panel-index entries, panel headers, guest-panel feeder rows, branch descriptions, load-code rows and prior plan/schedule callouts were treated as separate evidence classes. Nothing illegible or unstated was inferred.", "scopeExclusions": [ "No physical-length takeoff was performed: both E5.2 details are explicitly NTS and E6.0/E6.1 are tabular schedules.", "Primary per-sheet audits were not duplicated.", "A cut-sheet image, schedule row, prototype room panel or load-analysis line is not automatically an installed quantity." ] }, "summary": { "overallStatus": "HOLD", "crossSheetTakeoffCompleteness": "PASS", "coordinationProcurementRelease": "HOLD", "takeoffCompletenessReason": "Both E5.2 NTS reference definitions and all twelve panel schedules visibly presented across E6.0/E6.1 were included in this reconciliation. The presented-sheet inventory is complete even though the project panel-schedule chain and several design relationships are not coordinated.", "releaseReason": "Release remains on HOLD because E5.2/E1.2 and E5.1 describe incompatible exterior-luminaire CCT, lumen and mounting bases; E5.2 leaves mounting and color unselected; the E6 index omits L1.E, PP and SP; L1.A prints twelve room feeders that do not match the eleven first-floor guestrooms or its own 11-unit demand note; upper-floor connecting-room types are flattened in panel descriptions; first-floor HVAC, L1.E site-lighting, DOAS distribution and EV charger branch sources are not fully scheduled; and the inherited utility fault-current and DOAS-2 voltage-drop issues remain open.", "findingCounts": { "PASS": 10, "HOLD": 11 } }, "sheetRegister": [ { "sheet": "E5.2", "title": "LIGHTING CUT-SHEETS", "page": 52, "content": "Two JSA JPL-1 manufacturer cut-sheet definitions", "scaleRule": "Each detail is explicitly SCALE: NTS; neither detail supports length or installed-count takeoff." }, { "sheet": "E6.0", "title": "ELECTRICAL PANELS SCHEDULE", "page": 53, "panelIndex": [ "L5.A", "L5.B", "L4.A", "L4.B", "L3.A", "L3.B" ], "scaleRule": "Tabular schedule; scale is not applicable." }, { "sheet": "E6.1", "title": "ELECTRICAL PANELS SCHEDULE", "page": 54, "panelIndex": [ "L2.A", "L2.B", "L1.A", "L1.B", "L1.C", "L1.D" ], "scaleRule": "Tabular schedule; scale is not applicable." } ], "fixtureReconciliation": { "e52ReferenceDefinitions": [ { "detailLabel": "LIGHTING CUT-SHEET TYPE \"SA\", \"SB\"", "scale": "NTS", "selectedFields": { "catalog": "JPL-1", "lightDistribution": "Type 2 (T2)", "ledCount": "16 (16L)", "driveCurrent": "1050 milliamps (1)", "cctCri": "3000K, 80 CRI (30K8)", "voltage": "120-277V (UNV)", "option": "House Side Shield (HSS)" }, "wattageChart": "16L at 1050 milliamps = 56W", "unselectedFields": [ "mounting", "color/finish" ] }, { "detailLabel": "LIGHTING CUT-SHEET TYPE \"SA1\", \"SB1\", \"SC1\"", "scale": "NTS", "selectedFields": { "catalog": "JPL-1", "lightDistribution": "Type 2 (T2)", "ledCount": "16 (16L)", "driveCurrent": "1050 milliamps (1)", "cctCri": "3000K, 80 CRI (30K8)", "voltage": "120-277V (UNV)" }, "wattageChart": "16L at 1050 milliamps = 56W", "optionStatus": "No HSS selection box is marked", "unselectedFields": [ "mounting", "color/finish" ] } ], "installedQuantityChain": { "e50PlanArrangements": { "SA": 7, "SA1": 3, "SB": 2, "SB1": 3, "SC1": 1, "totalArrangements": 16 }, "headMultiplicity": { "SA": 1, "SA1": 1, "SB": 2, "SB1": 2, "SC1": 3 }, "installedHeads": { "HSS": 11, "standard": 12, "total": 23 }, "e51Schedule": { "HSSQuantity": 11, "standardQuantity": 12, "total": 23 }, "quantityConclusion": "The HSS/non-HSS grouping and 23-head quantity reconcile. E5.2 contributes zero installed heads because it is a pair of NTS product definitions." } }, "panelReconciliation": { "e10Panelboards": [ "L5.A", "L5.B", "L4.A", "L4.B", "L3.A", "L3.B", "L2.A", "L2.B", "L1.A", "L1.B", "L1.C", "L1.D", "L1.E", "PP", "SP" ], "indexedOnE60E61": [ "L5.A", "L5.B", "L4.A", "L4.B", "L3.A", "L3.B", "L2.A", "L2.B", "L1.A", "L1.B", "L1.C", "L1.D" ], "notIndexedOnE60E61": [ "L1.E", "PP", "SP" ], "distributionAssembliesNotIndexedAsBranchPanelSchedules": [ "MDP", "EP", "generator integral panel" ], "headerMatchToE10": [ { "panels": "L2.A/L2.B through L5.A/L5.B", "e60e61": "120/208V, 3PH, 4W; 250A copper bus; 250A MLO; 22kA; NEMA-1; fed from MDP", "e10": "same panel ratings; feeder key 4, 285A" }, { "panel": "L1.A", "e61": "225A copper bus/MLO, 42kA, NEMA-1, fed from MDP", "e10": "same panel rating; feeder key 3, 230A" }, { "panel": "L1.B", "e61": "100A copper bus/MLO, 30kA, NEMA-1, fed from MDP", "e10": "same panel rating; feeder key 1, 130A" }, { "panels": "L1.C/L1.D", "e61": "200A copper bus/MLO, 42kA, NEMA-1, fed from MDP", "e10": "same panel ratings; feeder key 3, 230A" } ], "guestFeederCounts": { "E60": { "L3.A": 12, "L3.B": 12, "L4.A": 12, "L4.B": 12, "L5.A": 12, "L5.B": 12, "total": 72, "planRelationship": "Exactly 24 room-number feeders on each of floors 3, 4 and 5." }, "E61": { "L2.A": 12, "L2.B": 12, "L1.A": 12, "totalPrintedRoomRows": 36, "planRelationship": "The second-floor 24 rows reconcile to E3.1; the first-floor 12 rows do not reconcile to E3.0's 11 guestrooms." }, "combinedPrintedRoomRows": 108, "establishedEngineeringAndPowerPlanGuestrooms": 107, "difference": 1 }, "firstFloorConflict": { "l1aPrintedAsGuestroomFeeders": [ "101", "102", "103", "104", "105", "106", "107", "108", "109", "110", "111", "112" ], "e30ActualGuestrooms": [ "101", "102", "103", "104", "105", "106", "107", "108", "110", "112", "114" ], "falseGuestroomDescriptions": [ "109 is MECHANICAL ROOM on E3.0", "111 is ENGINEER on E3.0" ], "omittedActualGuestroom": "114 CONNECTING KING STUDIO", "internalScheduleContradiction": "L1.A prints 12 guest-panel feeder rows but its SUB demand line says SUB PANEL x 42% PF (FOR 11 UNITS)." }, "upperRoomTypeConflictExamples": [ "E6.0 calls rooms 505, 512 and 514 KING STUDIO; E3.4 calls each CONNECTING KING STUDIO.", "E6.0 calls room 524 DOUBLE QUEEN; E3.4 calls it CONNECTING QUEEN QUEEN.", "E1.0 assigns connecting prototypes their own calculated loads, so flattening the room descriptions is not merely nomenclature." ] }, "systemReconciliation": { "siteLighting": { "verifiedL1BBranches": [ { "circuits": [ 8, 10 ], "scheduleDescription": "LTS - SITE LIGHTING", "breaker": "20A/2P" }, { "circuits": [ 12, 14 ], "scheduleDescription": "LTS - SITE LIGHTING", "breaker": "20A/2P" }, { "circuits": [ 18 ], "scheduleDescription": "LTS - EXTERIOR", "breaker": "20A/1P" }, { "circuits": [ 20 ], "scheduleDescription": "LTS - FLAG POLE", "breaker": "20A/1P" }, { "circuits": [ 22 ], "scheduleDescription": "LTS - EXTERIOR", "breaker": "20A/1P" }, { "circuits": [ 24 ], "scheduleDescription": "LTS - EXTERIOR", "breaker": "20A/1P" } ], "controlNote": "The applicable L1.B rows carry Note 1: control by 20A mechanically held lighting contactors controlled by a 7-day N-1 time clock with 4-hour batteries in Panel L1.B.", "unresolved": "E5.0 also prints L1.E-18,20,22,24; E6.0/E6.1 contain no L1.E schedule." }, "mechanicalAndPlumbing": { "verified": [ "L5.A-34 RCPTS - ROOF, L5.A-36 EF-10 and L5.A-38 CIRCULATE PUMP CONTROL PNL agree with the E3.5 roof callouts.", "L3.A-34 and L5.A-38 are the scheduled circulation-pump-control branches previously called out on E3.2 and E3.4.", "L2.B provides two 30A/2P EUH branches on 26/28 and 30/32, matching the two E3.1 EUH-2 callouts.", "L1.D schedules the booster-pump control panel, two circulation-pump control panels, three gas water heaters, a motorized damper and fire/smoke damper branches; its notes require field coordination with laundry and plumbing schedules." ], "unresolved": [ "L3.B, L4.B and L5.B show circuits 26, 28 and 30 as SPARE and no EUH branch descriptions, while the mechanical plans plot two EUH-2 units on each of floors 3, 4 and 5 and the power plans omit their callouts.", "DOAS-1 and DOAS-2 are called from MDP on E3.5/E1.0, but no MDP branch schedule is presented on E6.0/E6.1.", "The first-floor power plan contains six AHUs, two FCUs with two outdoor CUs and six ACCUs; the omitted L1.E schedule prevents a complete branch/breaker reconciliation for this HVAC group." ] }, "evCharging": { "e10LoadBasis": "E1.0 includes ELECTRIC CHARGING STATION: 2 x 7.2kVA @ 125% = 18.0kVA.", "e50Conflict": "E5.0 specifies dual future-charger conduit/J-box rough-in and owner verification, while a review annotation requires at least two installed EV charging stations.", "e60e61Evidence": "Every visible scheduled panel load-code row shows EVCS = 0 / N.A., and no branch circuit description identifies an EV charger.", "conclusion": "The service load includes two chargers, but no installed branch source, panel or breaker is identified in this panel-schedule batch." } }, "findings": [ { "id": "PASS-01", "status": "PASS", "topic": "Sheet identity and scale boundary", "evidence": [ "Pages 52-54 are E5.2, E6.0 and E6.1 in order.", "Both E5.2 details print SCALE: NTS; E6.0/E6.1 are schedules." ], "conclusion": "No scaled length is released from this batch." }, { "id": "PASS-02", "status": "PASS", "topic": "E5.2 selected JPL-1 head definition", "evidence": [ "Both details select JPL-1, T2, 16L, 1050mA, 30K8 and UNV.", "The printed wattage chart gives 56W for 16L at 1050mA." ], "conclusion": "The two reference samples consistently define the same 56W, 3000K/80CRI JPL-1 head basis." }, { "id": "PASS-03", "status": "PASS", "topic": "HSS type grouping and head quantity", "evidence": [ "The SA/SB detail selects HSS; the SA1/SB1/SC1 detail does not.", "E5.0 multiplicities yield 11 HSS and 12 standard heads.", "E5.1 schedules QTY 11 HSS and QTY 12 standard." ], "conclusion": "Shield grouping and the 23 installed-head total reconcile exactly." }, { "id": "HOLD-01", "status": "HOLD", "topic": "Exterior luminaire product/performance basis conflict", "evidence": [ "E5.2 selects JPL-1/T2/16L/1050mA/30K8/UNV and prints 56W.", "E1.2 identifies 16-foot, 3000K JPL site-lighting assemblies and prints 21,163 lumens per single head.", "E5.1 instead schedules 19-foot, 4000K NV-description rows at 56W with 6,832 lumens standard and 4,252 lumens HSS." ], "conclusion": "E5.2 supports the E1.2 family/CCT/wattage direction, not the E5.1 CCT, mounting or lumen basis.", "requiredResolution": "Issue one coordinated approved catalog, optic/shield, CCT, lumen output and pole/mounting-height definition, then confirm the photometric model against it." }, { "id": "HOLD-02", "status": "HOLD", "topic": "E5.2 incomplete selectable procurement code", "evidence": [ "Neither E5.2 ordering guide marks a mounting option.", "Neither marks a color/finish option.", "E1.2 separately names a pole/finish assembly that is not fully selected on E5.2." ], "conclusion": "The cut sheets do not form a complete orderable pole/luminaire assembly.", "requiredResolution": "Select the required mounting and finish and publish the full coordinated catalog string." }, { "id": "PASS-04", "status": "PASS", "topic": "Presented panel-index coverage", "evidence": [ "E6.0 indexes and presents six schedules: L3.A/B, L4.A/B and L5.A/B.", "E6.1 indexes and presents six schedules: L2.A/B and L1.A-D." ], "conclusion": "Each of the twelve entries printed in the two panel indexes has a visible schedule on the same sheet pair." }, { "id": "PASS-05", "status": "PASS", "topic": "Panel source and header ratings", "evidence": [ "All twelve schedules say FED FROM MDP.", "Their voltage, bus, main, AIC and enclosure values match the corresponding E1.0 one-line panel definitions." ], "conclusion": "The twelve presented panel headers reconcile to the one-line sources and ratings." }, { "id": "HOLD-03", "status": "HOLD", "topic": "Project panel-index incompleteness", "evidence": [ "E1.0 defines 15 branch panelboards: L1.A-E, PP, SP and L2.A/B through L5.A/B.", "E6.0/E6.1 index only twelve and omit L1.E, PP and SP.", "MDP, EP and the generator integral panel also have no tabular branch schedules in this pair, although they are distribution assemblies rather than members of E1.0's 15-panelboard count." ], "conclusion": "The E6 index is complete only for the schedules shown, not for the project panelboard list.", "requiredResolution": "Issue the L1.E, PP and SP schedules or identify their governing separate-permit/schedule documents; state where MDP and EP branch details are governed." }, { "id": "PASS-06", "status": "PASS", "topic": "Upper-floor room-number feeder coverage", "evidence": [ "E6.0 has 12 guest-panel feeder rows in each A/B pair on floors 3, 4 and 5.", "The 24 room numbers on each floor match the 24 numbered guestrooms on E3.2-E3.4." ], "conclusion": "E6.0 covers 72 upper-floor room-number feeders without a room-number omission or duplicate." }, { "id": "PASS-07", "status": "PASS", "topic": "Second-floor room-number feeder coverage", "evidence": [ "L2.A and L2.B each contain 12 guest-panel feeder rows.", "Their combined 24 room numbers match E3.1's 24 guestrooms." ], "conclusion": "Second-floor feeder count is complete by room number." }, { "id": "HOLD-04", "status": "HOLD", "topic": "First-floor guest feeder count and identity conflict", "evidence": [ "L1.A prints 12 guest feeder rows for 101 through 112.", "E3.0 identifies only 11 guestrooms: 101-108, 110, 112 and 114.", "E3.0 calls 109 MECHANICAL ROOM and 111 ENGINEER, but E6.1 calls both KING STUDIO; E6.1 omits actual guestroom 114.", "L1.A's own SUB calculation says FOR 11 UNITS." ], "conclusion": "Across all schedules, 108 guest rows are printed against the 107-room engineering/plan basis, and the first-floor identities are not a simple one-row overcount.", "requiredResolution": "Correct the L1.A feeder-room mapping and recalculate connected/demand load from the coordinated 11-room first-floor matrix." }, { "id": "HOLD-05", "status": "HOLD", "topic": "Connecting-room type and load descriptions", "evidence": [ "E6.0 labels fifth-floor rooms 505, 512 and 514 as KING STUDIO while E3.4 labels them CONNECTING KING STUDIO.", "E6.0 labels room 524 DOUBLE QUEEN while E3.4 labels it CONNECTING QUEEN QUEEN.", "E1.0 assigns separate calculated loads to connecting-room prototypes." ], "conclusion": "Room-number coverage passes, but the schedule cannot be treated as a coordinated room-type/load matrix.", "requiredResolution": "Reconcile every room type and guest-panel A/B designation to the approved room matrix and update panel loads." }, { "id": "PASS-08", "status": "PASS", "topic": "L1.B site-lighting branch chain", "evidence": [ "E6.1 schedules L1.B 8/10 and 12/14 as 20A/2P SITE LIGHTING.", "It schedules L1.B-18, -20, -22 and -24 as exterior/flag-pole lighting.", "These circuit groups are called out on E5.0." ], "conclusion": "The E5.0 L1.B site-lighting branches have destinations and breaker definitions on E6.1." }, { "id": "HOLD-06", "status": "HOLD", "topic": "L1.E site-lighting callout has no schedule", "evidence": [ "E5.0 prints L1.E-18,20,22,24 at a site-lighting branch.", "E6.0/E6.1 omit L1.E from both indexes and provide no L1.E circuit schedule." ], "conclusion": "The distinct L1.E callout cannot be verified or safely merged into L1.B-18,20,22,24.", "requiredResolution": "Issue the L1.E schedule and confirm whether the E5.0 callout is intentional." }, { "id": "PASS-09", "status": "PASS", "topic": "Second-floor EUH branch relationship", "evidence": [ "L2.B schedules two 30A/2P EUH branches on 26/28 and 30/32.", "E3.1 assigns its two EUH-2 occurrences to the same circuit pairs." ], "conclusion": "Second-floor EUH quantity and circuit allocation reconcile." }, { "id": "HOLD-07", "status": "HOLD", "topic": "Floors 3-5 EUH power remains unscheduled", "evidence": [ "Mechanical plans show two EUH-2 units on each of floors 3, 4 and 5.", "E3.2-E3.4 show no EUH power callouts.", "L3.B, L4.B and L5.B mark 26, 28 and 30 SPARE and show no EUH description." ], "conclusion": "Six upper-floor heaters remain without a coordinated electrical branch assignment.", "requiredResolution": "Assign and schedule the six EUH branches or revise the mechanical equipment scope." }, { "id": "PASS-10", "status": "PASS", "topic": "Roof EF-10 and common-equipment branch chain", "evidence": [ "E3.5 calls L5.A-34 for roof receptacles, L5.A-36 for EF-10 and L5.A-38 for circulation-pump control.", "E6.0 contains matching descriptions, 20A/1P breakers and 540VA, 50VA and 441VA values." ], "conclusion": "These three roof/common branches are fully destination-addressable in the panel schedule." }, { "id": "HOLD-08", "status": "HOLD", "topic": "First-floor HVAC and DOAS schedule chain", "evidence": [ "E3.0 plots six AHUs, two FCUs with two outdoor CUs and six ACCUs.", "E3.5 calls DOAS-1 on MDP-44/46/48 and DOAS-2 on MDP-50/52/54.", "No L1.E or MDP branch schedule is present on E6.0/E6.1." ], "conclusion": "The panel-schedule batch cannot close the first-floor HVAC or DOAS breaker/load reconciliation.", "requiredResolution": "Issue the governing L1.E and MDP schedules and reconcile each equipment nameplate, disconnect and breaker." }, { "id": "HOLD-09", "status": "HOLD", "topic": "EV service load has no branch source", "evidence": [ "E1.0 includes 18.0kVA for two 7.2kVA chargers at 125 percent.", "E5.0 conflicts between future rough-in/owner verification and a minimum two installed-station annotation.", "Every E6.0/E6.1 EVCS load-code row is 0/N.A., and no visible circuit description identifies an EV charger." ], "conclusion": "The service-load allowance does not identify an installed source panel or branch breaker.", "requiredResolution": "Resolve installed versus future scope and issue panel/circuit, breaker, feeder, disconnect and equipment ratings for the approved EV quantity." }, { "id": "HOLD-10", "status": "HOLD", "topic": "Fault-current ratings remain conditional", "evidence": [ "The twelve panel AIC ratings equal the E1.0A selected values and exceed the calculated values under its assumption.", "E6.0/E6.1 notes require final utility current verification and AIC matching.", "E1.0 leaves transformer capacity to the utility, while E1.0A assumes 750kVA and 5 percent impedance." ], "conclusion": "Panel AIC selection is internally coordinated but not final for procurement.", "requiredResolution": "Obtain utility maximum available fault current/final transformer data and reconfirm the study and equipment ratings." }, { "id": "HOLD-11", "status": "HOLD", "topic": "Inherited DOAS-2 voltage-drop exceedance", "evidence": [ "E1.0 states a 3 percent feeder limit.", "E1.0A calculates MDP-to-DOAS-2 at 3.26 percent.", "E6.0/E6.1 add no conductor or source revision that resolves it." ], "conclusion": "The DOAS-2 feeder remains above the stated design limit.", "requiredResolution": "Resize or reroute the feeder and update the one-line/calculation." } ], "quantityAndDuplicateRules": [ { "rule": "E5.2's two NTS cut-sheet samples are reference definitions only and add zero luminaires to project totals. Installed head quantity comes once from the E5.0 plan, corroborated by E5.1 schedule quantities." }, { "rule": "SA/SB/SA1/SB1/SC1 are arrangement tags. Apply the shown one-, two- or three-head multiplicity once; do not add arrangement count and head count together." }, { "rule": "The words PANEL A and PANEL B in guest feeder descriptions identify in-room prototype panels, not additional floor distribution panels Lx.A and Lx.B." }, { "rule": "Guest feeder rows, E1.0 prototype rows and E4.0/E4.1 detail samples are alternate views of guestroom scope. Do not sum them. The 108 printed feeder rows are not releasable until HOLD-04 is corrected." }, { "rule": "Panel schedule circuit rows and load-code totals are electrical allocation/load evidence, not counts of downstream receptacles, luminaires, dampers, heaters or pumps unless a one-to-one equipment identity is explicitly printed." }, { "rule": "SPARE and SPACE ONLY rows are not installed equipment quantities." }, { "rule": "E1.0's EV charging and other load-analysis entries are service-calculation allowances, not proof of installed equipment." } ], "releaseChecks": [ { "status": "PASS", "item": "Both E5.2 NTS product definitions captured; zero installed quantity assigned to samples." }, { "status": "PASS", "item": "All twelve schedules listed in the E6.0/E6.1 panel indexes reconciled." }, { "status": "PASS", "item": "HSS/non-HSS split and 23 exterior-luminaire heads reconcile." }, { "status": "HOLD", "item": "Coordinate JPL/NV catalog, 3000K/4000K, lumen and 16-foot/19-foot mounting bases." }, { "status": "HOLD", "item": "Complete E5.2 mounting and finish selections." }, { "status": "HOLD", "item": "Issue or identify L1.E, PP and SP schedules." }, { "status": "HOLD", "item": "Correct L1.A's first-floor room feeder identities and 12-row versus 11-unit contradiction." }, { "status": "HOLD", "item": "Reconcile connecting-room schedule descriptions and calculated loads." }, { "status": "HOLD", "item": "Resolve the unscheduled L1.E site-lighting circuit group." }, { "status": "HOLD", "item": "Assign power to six floor-3-through-floor-5 EUH-2 units." }, { "status": "HOLD", "item": "Provide the L1.E and MDP branch schedules for HVAC and DOAS coordination." }, { "status": "HOLD", "item": "Resolve EV installed-versus-future scope and branch source." }, { "status": "HOLD", "item": "Confirm utility fault current and correct DOAS-2 feeder voltage drop." } ], "validation": { "jsonSyntax": "valid; jq -e validation passed", "visualCoverage": "E5.2 full sheet plus full-resolution ordering-guide crops; E6.0 and E6.1 full sheets plus readable schedule crops, panel indexes, notes and title blocks.", "failClosed": true, "generatedUtc": "2026-09-07T22:39:27Z" } } }