E6.0 ELECTRICAL PANELS SCHEDULE Engineering PDF page 53 Issued November 22, 2024 COMPLETE SOURCE TEXT LAYER { "schema_version": "panel-schedule-audit-1.0", "sheet": "E6.0", "title": "ELECTRICAL PANELS SCHEDULE", "source": { "pdf": "/workspace/sites/ssx-cover-release/source-plans/engineering.pdf", "pdf_page_1_based": 53, "raster": "/workspace/sites/ssx-cover-release/tmp/pdfs/next3-e52-e61/source-53.png", "raster_pixels": [ 10800, 7200 ], "normalized_canvas": [ 1920, 1280 ], "project_name": "HOME 2 SUITES, BRADENTON, FL", "project_number": "#210729", "date": "NOV. 22, 2024", "drawn_by": "PL", "checked_by": "DV", "revisions_shown": 0 }, "scale": "NTS - tabular schedule sheet", "regions": [ { "panel": "L5.A", "bbox_norm": [ 94, 80, 834, 361 ] }, { "panel": "L4.B", "bbox_norm": [ 866, 80, 1608, 361 ] }, { "panel": "L5.B", "bbox_norm": [ 94, 394, 834, 673 ] }, { "panel": "L3.A", "bbox_norm": [ 866, 394, 1608, 673 ] }, { "panel": "L4.A", "bbox_norm": [ 94, 706, 834, 985 ] }, { "panel": "L3.B", "bbox_norm": [ 866, 706, 1608, 985 ] }, { "name": "sheet notes", "bbox_norm": [ 866, 1010, 1608, 1110 ] }, { "name": "panel index", "bbox_norm": [ 1644, 80, 1745, 185 ] }, { "name": "title block", "bbox_norm": [ 1745, 0, 1920, 1280 ] } ], "panel_index": [ [ "L5.A", "L4.B" ], [ "L5.B", "L3.A" ], [ "L4.A", "L3.B" ] ], "row_columns": [ "ckt", "load_type", "circuit_description", "notes", "poles", "breaker_amp", "wire", "volt_amps" ], "phase_cell_columns": [ "paired_row_start", "phase", "combined_volt_amps" ], "panels": [ { "panel": "L5.A", "fed_from": "MDP", "voltage": "120/208V, 3PH, 4W", "enclosure": "NEMA-1", "aic_ka": 22, "bus_amp": 250, "bus_material": "COPPER", "mains_amp": 250, "main_type": "M.L.O", "mounting": "SURFACE MOUNTED", "location": "STORAGE 5TH FLOOR", "rows": [ [ 1, "SUB", "PANEL \"A\" / 501 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 2, "SUB", "PANEL \"B\" / 507 - ACC KING ONE BEDROOM", null, 2, "100/2", 2, 8522 ], [ 3, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 4, "SUB", "↓", null, "-", "↓", "↓", 8522 ], [ 5, "SUB", "PANEL \"B\" / 502 - KING ONE BEDROOM", null, 2, "100/2", 2, 8443 ], [ 6, "SUB", "PANEL \"A\" / 508 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 7, "SUB", "↓", null, "-", "↓", "↓", 8443 ], [ 8, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 9, "SUB", "PANEL \"A\" / 503 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 10, "SUB", "PANEL \"A\" / 509 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 11, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 12, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 13, "SUB", "PANEL \"A\" / 504 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 14, "SUB", "PANEL \"A\" / 510 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 15, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 16, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 17, "SUB", "PANEL \"A\" / 505 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 18, "SUB", "PANEL \"A\" / 511 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 19, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 20, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 21, "SUB", "PANEL \"A\" / 506 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 22, "SUB", "PANEL \"A\" / 512 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 23, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 24, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 25, null, "SPARE", null, 2, "80/2", null, null ], [ 26, "REC", "RCPTS - CORRIDOR", null, 1, "20/1", 12, 900 ], [ 27, null, "↓", null, "-", "↓", null, null ], [ 28, "REC", "RCPTS - CORRIDOR/STORAGE", null, 1, "20/1", 12, 720 ], [ 29, null, "SPACE ONLY", null, null, null, null, null ], [ 30, "EQUIP", "FIRE SMOKE DAMPER", null, 1, "20/1", 12, 500 ], [ 31, null, null, null, null, null, null, null ], [ 32, "EQUIP", "ICE MACHINE", "(CLASS A GFCI BREAKER)", 1, "20/1", 12, 1500 ], [ 33, null, null, null, null, null, null, null ], [ 34, "REC", "RCPTS - ROOF", null, 1, "20/1", 12, 540 ], [ 35, null, null, null, null, null, null, null ], [ 36, "EQUIP", "EF-10", null, 1, "20/1", 12, 50 ], [ 37, null, null, null, null, null, null, null ], [ 38, "EQUIP", "CIRCULATE PUMP CONTROL PNL. (C.P)", null, 1, "20/1", 12, 441 ], [ 39, null, null, null, null, null, null, null ], [ 40, null, "SPARE", null, 1, "20/1", null, 0 ], [ 41, null, null, null, null, null, null, null ], [ 42, null, "↓", null, 1, "↓", null, 0 ] ], "phase_cells": [ [ 1, "A", 15216 ], [ 3, "B", 15216 ], [ 5, "C", 15137 ], [ 7, "A", 15137 ], [ 9, "B", 13388 ], [ 11, "C", 13388 ], [ 13, "A", 13388 ], [ 15, "B", 13388 ], [ 17, "C", 13388 ], [ 19, "A", 13388 ], [ 21, "B", 13388 ], [ 23, "C", 13388 ], [ 25, "A", 900 ], [ 27, "B", 720 ], [ 29, "C", 500 ], [ 31, "A", 1500 ], [ 33, "B", 540 ], [ 35, "C", 50 ], [ 37, "A", 441 ], [ 39, "B", 0 ], [ 41, "C", 0 ] ], "load_summary": { "connected": { "LTG": 0, "REC": 2160, "EQUIP": 2491, "AC": 0, "HTG": 0, "LGR": 0, "KIT": 0, "SUB": 167809, "GLTG": 0, "EVCS": 0, "VA": 172460, "AMPS": 479 }, "demand": { "LTG": 0, "REC": 2160, "EQUIP": 2491, "AC": 0, "HTG": 0, "LGR": 0, "KIT": 0, "SUB": 68802, "GLTG": 0, "EVCS": 0, "VA": 73453, "AMPS": 204 } }, "phase_summary": { "connected_kva": [ 59.97, 56.64, 55.85 ], "connected_amps": [ 499.75, 472.0, 465.42 ], "demand_kva": [ 26.26, 23.97, 23.22 ], "demand_amps": [ 218.87, 199.72, 193.53 ] } }, { "panel": "L4.B", "fed_from": "MDP", "voltage": "120/208V, 3PH, 4W", "enclosure": "NEMA-1", "aic_ka": 22, "bus_amp": 250, "bus_material": "COPPER", "mains_amp": 250, "main_type": "M.L.O", "mounting": "SURFACE MOUNTED", "location": "STORAGE 4TH FLOOR", "rows": [ [ 1, "SUB", "PANEL \"A\" / 413 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 2, "SUB", "PANEL \"A\" / 419 - KING STUDIO", null, 2, "100/2", 2, 8522 ], [ 3, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 4, "SUB", "↓", null, "-", "↓", "↓", 8522 ], [ 5, "SUB", "PANEL \"A\" / 414 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 6, "SUB", "PANEL \"A\" / 420 - DOUBLE QUEEN", null, 2, "80/2", 3, 6694 ], [ 7, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 8, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 9, "SUB", "PANEL \"A\" / 415 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 10, "SUB", "PANEL \"A\" / 421 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 11, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 12, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 13, "SUB", "PANEL \"A\" / 416 - DOUBLE QUEEN", null, 2, "80/2", 3, 6817 ], [ 14, "SUB", "PANEL \"A\" / 422 - DOUBLE QUEEN", null, 2, "80/2", 3, 6694 ], [ 15, "SUB", "↓", null, "-", "↓", "↓", 6817 ], [ 16, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 17, "SUB", "PANEL \"A\" / 417 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 18, "SUB", "PANEL \"A\" / 424 - DOUBLE QUEEN", null, 2, "80/2", 3, 6694 ], [ 19, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 20, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 21, "SUB", "PANEL \"A\" / 418 - DOUBLE QUEEN", null, 2, "80/2", 3, 6817 ], [ 22, "SUB", "PANEL \"A\" / 426 - KING ACC", null, 2, "80/2", 3, 6694 ], [ 23, "SUB", "↓", null, "-", "↓", "↓", 6817 ], [ 24, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 25, null, "SPARE", null, 2, "80/2", null, 0 ], [ 26, null, "SPARE", null, 1, "20/1", null, 0 ], [ 27, null, "↓", null, "-", "↓", null, 0 ], [ 28, null, "↓", null, 1, "↓", null, 0 ], [ 29, null, "SPACE ONLY", null, null, null, null, 0 ], [ 30, null, "↓", null, 1, "↓", null, 0 ], [ 31, null, null, null, null, null, null, 0 ], [ 32, null, "SPACE ONLY", null, null, null, null, 0 ], [ 33, null, null, null, null, null, null, 0 ], [ 34, null, "↓", null, null, null, null, 0 ], [ 35, null, null, null, null, null, null, 0 ], [ 36, null, "↓", null, null, null, null, 0 ], [ 37, null, null, null, null, null, null, 0 ], [ 38, null, "↓", null, null, null, null, 0 ], [ 39, null, null, null, null, null, null, 0 ], [ 40, null, "↓", null, null, null, null, 0 ], [ 41, null, null, null, null, null, null, 0 ], [ 42, null, "↓", null, null, null, null, 0 ] ], "phase_cells": [ [ 1, "A", 15216 ], [ 3, "B", 15216 ], [ 5, "C", 13388 ], [ 7, "A", 13388 ], [ 9, "B", 13388 ], [ 11, "C", 13388 ], [ 13, "A", 13511 ], [ 15, "B", 13511 ], [ 17, "C", 13388 ], [ 19, "A", 13388 ], [ 21, "B", 13511 ], [ 23, "C", 13511 ], [ 25, "A", 0 ], [ 27, "B", 0 ], [ 29, "C", 0 ], [ 31, "A", 0 ], [ 33, "B", 0 ], [ 35, "C", 0 ], [ 37, "A", 0 ], [ 39, "B", 0 ], [ 41, "C", 0 ] ], "load_summary": { "connected": { "LTG": 0, "REC": 0, "EQUIP": 0, "AC": 0, "HTG": 0, "LGR": 0, "KIT": 0, "SUB": 164804, "GLTG": 0, "EVCS": 0, "VA": 164804, "AMPS": 458 }, "demand": { "LTG": 0, "REC": 0, "EQUIP": 0, "AC": 0, "HTG": 0, "LGR": 0, "KIT": 0, "SUB": 67570, "GLTG": 0, "EVCS": 0, "VA": 67570, "AMPS": 188 } }, "phase_summary": { "connected_kva": [ 55.5, 55.63, 53.68 ], "connected_amps": [ 462.53, 463.55, 447.29 ], "demand_kva": [ 22.76, 22.81, 22.01 ], "demand_amps": [ 189.64, 190.06, 183.39 ] } }, { "panel": "L5.B", "fed_from": "MDP", "voltage": "120/208V, 3PH, 4W", "enclosure": "NEMA-1", "aic_ka": 22, "bus_amp": 250, "bus_material": "COPPER", "mains_amp": 250, "main_type": "M.L.O", "mounting": "SURFACE MOUNTED", "location": "STORAGE 5TH FLOOR", "rows": [ [ 1, "SUB", "PANEL \"A\" / 513 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 2, "SUB", "PANEL \"A\" / 519 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 3, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 4, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 5, "SUB", "PANEL \"A\" / 514 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 6, "SUB", "PANEL \"A\" / 520 - DOUBLE QUEEN", null, 2, "80/2", 3, 6817 ], [ 7, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 8, "SUB", "↓", null, "-", "↓", "↓", 6817 ], [ 9, "SUB", "PANEL \"A\" / 515 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 10, "SUB", "PANEL \"A\" / 521 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 11, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 12, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 13, "SUB", "PANEL \"A\" / 516 - DOUBLE QUEEN", null, 2, "80/2", 3, 6817 ], [ 14, "SUB", "PANEL \"A\" / 522 - DOUBLE QUEEN", null, 2, "80/2", 3, 6817 ], [ 15, "SUB", "↓", null, "-", "↓", "↓", 6817 ], [ 16, "SUB", "↓", null, "-", "↓", "↓", 6817 ], [ 17, "SUB", "PANEL \"A\" / 517 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 18, "SUB", "PANEL \"A\" / 524 - DOUBLE QUEEN", null, 2, "80/2", 3, 6817 ], [ 19, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 20, "SUB", "↓", null, "-", "↓", "↓", 6817 ], [ 21, "SUB", "PANEL \"A\" / 518 - DOUBLE QUEEN", null, 2, "80/2", 3, 6817 ], [ 22, "SUB", "PANEL \"A\" / 526 - KING ACC", null, 2, "80/2", 3, 7018 ], [ 23, "SUB", "↓", null, "-", "↓", "↓", 6817 ], [ 24, "SUB", "↓", null, "-", "↓", "↓", 7018 ], [ 25, null, "SPARE", null, 2, "80/2", null, 0 ], [ 26, null, "SPARE", null, 1, "20/1", null, 0 ], [ 27, null, "↓", null, "-", "↓", null, 0 ], [ 28, null, "↓", null, 1, "↓", null, 0 ], [ 29, null, "SPACE ONLY", null, null, null, null, 0 ], [ 30, null, "↓", null, 1, "↓", null, 0 ], [ 31, null, null, null, null, null, null, 0 ], [ 32, null, "SPACE ONLY", null, null, null, null, 0 ], [ 33, null, null, null, null, null, null, 0 ], [ 34, null, "↓", null, null, null, null, 0 ], [ 35, null, null, null, null, null, null, 0 ], [ 36, null, "↓", null, null, null, null, 0 ], [ 37, null, null, null, null, null, null, 0 ], [ 38, null, "↓", null, null, null, null, 0 ], [ 39, null, null, null, null, null, null, 0 ], [ 40, null, "↓", null, null, null, null, 0 ], [ 41, null, null, null, null, null, null, 0 ], [ 42, null, "↓", null, null, null, null, 0 ] ], "phase_cells": [ [ 1, "A", 13388 ], [ 3, "B", 13388 ], [ 5, "C", 13511 ], [ 7, "A", 13511 ], [ 9, "B", 13388 ], [ 11, "C", 13388 ], [ 13, "A", 13634 ], [ 15, "B", 13634 ], [ 17, "C", 13511 ], [ 19, "A", 13511 ], [ 21, "B", 13835 ], [ 23, "C", 13835 ], [ 25, "A", 0 ], [ 27, "B", 0 ], [ 29, "C", 0 ], [ 31, "A", 0 ], [ 33, "B", 0 ], [ 35, "C", 0 ], [ 37, "A", 0 ], [ 39, "B", 0 ], [ 41, "C", 0 ] ], "load_summary": { "connected": { "LTG": 0, "REC": 0, "EQUIP": 0, "AC": 0, "HTG": 0, "LGR": 0, "KIT": 0, "SUB": 162534, "GLTG": 0, "EVCS": 0, "VA": 162534, "AMPS": 451 }, "demand": { "LTG": 0, "REC": 0, "EQUIP": 0, "AC": 0, "HTG": 0, "LGR": 0, "KIT": 0, "SUB": 66639, "GLTG": 0, "EVCS": 0, "VA": 66639, "AMPS": 185 } }, "phase_summary": { "connected_kva": [ 54.04, 54.25, 54.25 ], "connected_amps": [ 450.37, 452.04, 452.04 ], "demand_kva": [ 22.16, 22.24, 22.24 ], "demand_amps": [ 184.65, 185.34, 185.34 ] } }, { "panel": "L3.A", "fed_from": "MDP", "voltage": "120/208V, 3PH, 4W", "enclosure": "NEMA-1", "aic_ka": 22, "bus_amp": 250, "bus_material": "COPPER", "mains_amp": 250, "main_type": "M.L.O", "mounting": "SURFACE MOUNTED", "location": "STORAGE 3RD FLOOR", "rows": [ [ 1, "SUB", "PANEL \"A\" / 301 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 2, "SUB", "PANEL \"B\" / 307 - ACC KING ONE BEDROOM", null, 2, "100/2", 2, 8522 ], [ 3, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 4, "SUB", "↓", null, "-", "↓", "↓", 8522 ], [ 5, "SUB", "PANEL \"B\" / 302 - KING ONE BEDROOM", null, 2, "100/2", 2, 8443 ], [ 6, "SUB", "PANEL \"A\" / 308 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 7, "SUB", "↓", null, "-", "↓", "↓", 8443 ], [ 8, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 9, "SUB", "PANEL \"A\" / 303 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 10, "SUB", "PANEL \"A\" / 309 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 11, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 12, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 13, "SUB", "PANEL \"A\" / 304 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 14, "SUB", "PANEL \"A\" / 310 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 15, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 16, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 17, "SUB", "PANEL \"A\" / 305 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 18, "SUB", "PANEL \"A\" / 311 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 19, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 20, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 21, "SUB", "PANEL \"A\" / 306 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 22, "SUB", "PANEL \"A\" / 312 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 23, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 24, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 25, null, "SPARE", null, 2, "80/2", null, null ], [ 26, "REC", "RCPTS - CORRIDOR", null, 1, "20/1", 12, 900 ], [ 27, null, "↓", null, "-", "↓", null, null ], [ 28, "REC", "RCPTS - CORRIDOR/STORAGE", null, 1, "20/1", 12, 720 ], [ 29, null, "SPACE ONLY", null, null, null, null, null ], [ 30, "EQUIP", "FIRE SMOKE DAMPER", null, 1, "20/1", 12, 500 ], [ 31, null, null, null, null, null, null, null ], [ 32, "EQUIP", "ICE MACHINE", "(CLASS A GFCI BREAKER)", 1, "20/1", 12, 1500 ], [ 33, null, null, null, null, null, null, null ], [ 34, "EQUIP", "CIRCULATE PUMP CONTROL PNL. (C.P)", null, 1, "20/1", 12, 441 ], [ 35, null, null, null, null, null, null, null ], [ 36, null, "SPARE", null, 1, "20/1", null, 0 ], [ 37, null, null, null, null, null, null, 0 ], [ 38, null, "↓", null, 1, "↓", null, 0 ], [ 39, null, null, null, null, null, null, 0 ], [ 40, null, "↓", null, 1, "↓", null, 0 ], [ 41, null, null, null, null, null, null, 0 ], [ 42, null, "↓", null, 1, "↓", null, 0 ] ], "phase_cells": [ [ 1, "A", 15216 ], [ 3, "B", 15216 ], [ 5, "C", 15137 ], [ 7, "A", 15137 ], [ 9, "B", 13388 ], [ 11, "C", 13388 ], [ 13, "A", 13388 ], [ 15, "B", 13388 ], [ 17, "C", 13388 ], [ 19, "A", 13388 ], [ 21, "B", 13388 ], [ 23, "C", 13388 ], [ 25, "A", 900 ], [ 27, "B", 720 ], [ 29, "C", 500 ], [ 31, "A", 1500 ], [ 33, "B", 441 ], [ 35, "C", 0 ], [ 37, "A", 0 ], [ 39, "B", 0 ], [ 41, "C", 0 ] ], "load_summary": { "connected": { "LTG": 0, "REC": 1620, "EQUIP": 2441, "AC": 0, "HTG": 0, "LGR": 0, "KIT": 0, "SUB": 167809, "GLTG": 0, "EVCS": 0, "VA": 171870, "AMPS": 477 }, "demand": { "LTG": 0, "REC": 1620, "EQUIP": 2441, "AC": 0, "HTG": 0, "LGR": 0, "KIT": 0, "SUB": 68802, "GLTG": 0, "EVCS": 0, "VA": 72863, "AMPS": 202 } }, "phase_summary": { "connected_kva": [ 59.53, 56.54, 55.8 ], "connected_amps": [ 496.07, 471.18, 465.0 ], "demand_kva": [ 25.82, 23.87, 23.17 ], "demand_amps": [ 215.19, 198.89, 193.11 ] } }, { "panel": "L4.A", "fed_from": "MDP", "voltage": "120/208V, 3PH, 4W", "enclosure": "NEMA-1", "aic_ka": 22, "bus_amp": 250, "bus_material": "COPPER", "mains_amp": 250, "main_type": "M.L.O", "mounting": "SURFACE MOUNTED", "location": "STORAGE 4TH FLOOR", "rows": [ [ 1, "SUB", "PANEL \"A\" / 401 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 2, "SUB", "PANEL \"B\" / 407 - ACC KING ONE BEDROOM", null, 2, "100/2", 2, 8522 ], [ 3, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 4, "SUB", "↓", null, "-", "↓", "↓", 8522 ], [ 5, "SUB", "PANEL \"B\" / 402 - KING ONE BEDROOM", null, 2, "100/2", 2, 8443 ], [ 6, "SUB", "PANEL \"A\" / 408 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 7, "SUB", "↓", null, "-", "↓", "↓", 8443 ], [ 8, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 9, "SUB", "PANEL \"A\" / 403 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 10, "SUB", "PANEL \"A\" / 409 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 11, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 12, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 13, "SUB", "PANEL \"A\" / 404 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 14, "SUB", "PANEL \"A\" / 410 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 15, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 16, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 17, "SUB", "PANEL \"A\" / 405 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 18, "SUB", "PANEL \"A\" / 411 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 19, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 20, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 21, "SUB", "PANEL \"A\" / 406 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 22, "SUB", "PANEL \"A\" / 412 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 23, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 24, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 25, null, "SPARE", null, 2, "80/2", null, null ], [ 26, "REC", "RCPTS - CORRIDOR", null, 1, "20/1", 12, 900 ], [ 27, null, "↓", null, "-", "↓", null, null ], [ 28, "REC", "RCPTS - CORRIDOR/STORAGE", null, 1, "20/1", 12, 720 ], [ 29, null, "SPACE ONLY", null, null, null, null, null ], [ 30, "EQUIP", "FIRE SMOKE DAMPER", null, 1, "20/1", 12, 500 ], [ 31, null, null, null, null, null, null, null ], [ 32, "EQUIP", "ICE MACHINE", "(CLASS A GFCI BREAKER)", 1, "20/1", 12, 1500 ], [ 33, null, null, null, null, null, null, null ], [ 34, null, "SPARE", null, 1, "20/1", null, 0 ], [ 35, null, null, null, null, null, null, 0 ], [ 36, null, "↓", null, 1, "↓", null, 0 ], [ 37, null, null, null, null, null, null, 0 ], [ 38, null, "↓", null, 1, "↓", null, 0 ], [ 39, null, null, null, null, null, null, 0 ], [ 40, null, "↓", null, 1, "↓", null, 0 ], [ 41, null, null, null, null, null, null, 0 ], [ 42, null, "↓", null, 1, "↓", null, 0 ] ], "phase_cells": [ [ 1, "A", 15216 ], [ 3, "B", 15216 ], [ 5, "C", 15137 ], [ 7, "A", 15137 ], [ 9, "B", 13388 ], [ 11, "C", 13388 ], [ 13, "A", 13388 ], [ 15, "B", 13388 ], [ 17, "C", 13388 ], [ 19, "A", 13388 ], [ 21, "B", 13388 ], [ 23, "C", 13388 ], [ 25, "A", 900 ], [ 27, "B", 720 ], [ 29, "C", 500 ], [ 31, "A", 1500 ], [ 33, "B", 0 ], [ 35, "C", 0 ], [ 37, "A", 0 ], [ 39, "B", 0 ], [ 41, "C", 0 ] ], "load_summary": { "connected": { "LTG": 0, "REC": 1620, "EQUIP": 2000, "AC": 0, "HTG": 0, "LGR": 0, "KIT": 0, "SUB": 167809, "GLTG": 0, "EVCS": 0, "VA": 171429, "AMPS": 476 }, "demand": { "LTG": 0, "REC": 1620, "EQUIP": 2000, "AC": 0, "HTG": 0, "LGR": 0, "KIT": 0, "SUB": 68802, "GLTG": 0, "EVCS": 0, "VA": 72422, "AMPS": 201 } }, "phase_summary": { "connected_kva": [ 59.53, 56.1, 55.8 ], "connected_amps": [ 496.07, 467.5, 465.0 ], "demand_kva": [ 25.82, 23.43, 23.17 ], "demand_amps": [ 215.19, 195.22, 193.11 ] } }, { "panel": "L3.B", "fed_from": "MDP", "voltage": "120/208V, 3PH, 4W", "enclosure": "NEMA-1", "aic_ka": 22, "bus_amp": 250, "bus_material": "COPPER", "mains_amp": 250, "main_type": "M.L.O", "mounting": "SURFACE MOUNTED", "location": "STORAGE 3RD FLOOR", "rows": [ [ 1, "SUB", "PANEL \"A\" / 313 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 2, "SUB", "PANEL \"A\" / 319 - KING STUDIO", null, 2, "100/2", 2, 8522 ], [ 3, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 4, "SUB", "↓", null, "-", "↓", "↓", 8522 ], [ 5, "SUB", "PANEL \"A\" / 314 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 6, "SUB", "PANEL \"A\" / 320 - DOUBLE QUEEN", null, 2, "80/2", 3, 6694 ], [ 7, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 8, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 9, "SUB", "PANEL \"A\" / 315 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 10, "SUB", "PANEL \"A\" / 321 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 11, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 12, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 13, "SUB", "PANEL \"A\" / 316 - DOUBLE QUEEN", null, 2, "80/2", 3, 6817 ], [ 14, "SUB", "PANEL \"A\" / 322 - DOUBLE QUEEN", null, 2, "80/2", 3, 6694 ], [ 15, "SUB", "↓", null, "-", "↓", "↓", 6817 ], [ 16, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 17, "SUB", "PANEL \"A\" / 317 - KING STUDIO", null, 2, "80/2", 3, 6694 ], [ 18, "SUB", "PANEL \"A\" / 324 - DOUBLE QUEEN", null, 2, "80/2", 3, 6694 ], [ 19, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 20, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 21, "SUB", "PANEL \"A\" / 318 - DOUBLE QUEEN", null, 2, "80/2", 3, 6817 ], [ 22, "SUB", "PANEL \"A\" / 326 - KING ACC", null, 2, "80/2", 3, 6694 ], [ 23, "SUB", "↓", null, "-", "↓", "↓", 6817 ], [ 24, "SUB", "↓", null, "-", "↓", "↓", 6694 ], [ 25, null, "SPARE", null, 2, "80/2", null, 0 ], [ 26, null, "SPARE", null, 1, "20/1", null, 0 ], [ 27, null, "↓", null, "-", "↓", null, 0 ], [ 28, null, "↓", null, 1, "↓", null, 0 ], [ 29, null, "SPACE ONLY", null, null, null, null, 0 ], [ 30, null, "↓", null, 1, "↓", null, 0 ], [ 31, null, null, null, null, null, null, 0 ], [ 32, null, "SPACE ONLY", null, null, null, null, 0 ], [ 33, null, null, null, null, null, null, 0 ], [ 34, null, "↓", null, null, null, null, 0 ], [ 35, null, null, null, null, null, null, 0 ], [ 36, null, "↓", null, null, null, null, 0 ], [ 37, null, null, null, null, null, null, 0 ], [ 38, null, "↓", null, null, null, null, 0 ], [ 39, null, null, null, null, null, null, 0 ], [ 40, null, "↓", null, null, null, null, 0 ], [ 41, null, null, null, null, null, null, 0 ], [ 42, null, "↓", null, null, null, null, 0 ] ], "phase_cells": [ [ 1, "A", 15216 ], [ 3, "B", 15216 ], [ 5, "C", 13388 ], [ 7, "A", 13388 ], [ 9, "B", 13388 ], [ 11, "C", 13388 ], [ 13, "A", 13511 ], [ 15, "B", 13511 ], [ 17, "C", 13388 ], [ 19, "A", 13388 ], [ 21, "B", 13511 ], [ 23, "C", 13511 ], [ 25, "A", 0 ], [ 27, "B", 0 ], [ 29, "C", 0 ], [ 31, "A", 0 ], [ 33, "B", 0 ], [ 35, "C", 0 ], [ 37, "A", 0 ], [ 39, "B", 0 ], [ 41, "C", 0 ] ], "load_summary": { "connected": { "LTG": 0, "REC": 0, "EQUIP": 0, "AC": 0, "HTG": 0, "LGR": 0, "KIT": 0, "SUB": 164804, "GLTG": 0, "EVCS": 0, "VA": 164804, "AMPS": 458 }, "demand": { "LTG": 0, "REC": 0, "EQUIP": 0, "AC": 0, "HTG": 0, "LGR": 0, "KIT": 0, "SUB": 67570, "GLTG": 0, "EVCS": 0, "VA": 67570, "AMPS": 188 } }, "phase_summary": { "connected_kva": [ 55.5, 55.63, 53.68 ], "connected_amps": [ 462.53, 463.55, 447.29 ], "demand_kva": [ 22.76, 22.81, 22.01 ], "demand_amps": [ 189.64, 190.06, 183.39 ] } } ], "load_code_definitions": [ { "code": "LTG", "text": "125% LIGHTING LOAD", "qualifier": "N/A" }, { "code": "REC", "text": "RCPTS LOAD (100% FIRST 10KVA +50% REMAIN)", "qualifier": "N/A on B panels" }, { "code": "EQUIP", "text": "EQUIPMENT LOAD", "qualifier": "N/A on B panels" }, { "code": "AC", "text": "HVAC LOAD", "qualifier": "N/A" }, { "code": "HTG", "text": "HEATING LOAD", "qualifier": "N/A" }, { "code": "LGR", "text": "125% LARGEST MOTOR", "qualifier": "N/A" }, { "code": "KIT", "text": "KITCHEN LOAD", "qualifier": "N/A" }, { "code": "SUB", "text": "SUB PANEL x 41% PF (FOR 12 UNITS)" }, { "code": "GLTG", "text": "GUESTROOM LIGHTING LOAD", "qualifier": "N/A" }, { "code": "EVCS", "text": "125% ELECTRIC VEHICLE CHARGING STATION", "qualifier": "N/A" } ], "sheet_notes": [ "CONTRACTOR SHALL PROVIDE A PERMANENTLY AFFIXED LABEL WITH THE MAXIMUM FAULT CURRENT PER ARTICLE 110.24. THE LABEL SHALL INCLUDE THE DATE THE FAULT-CURRENT CALCULATION WAS PERFORMED AND BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. THE LABEL SHALL BE 2\"X3\" IN SIZE AND SHALL BE BLUE LETTERING ON A CONTRASTING BACKGROUND.", "CONTRACTOR TO VERIFY FINAL CURRENT VALUES FROM ELECTRICAL UTILITY COMPANY AND PROVIDE AIC PROTECTION ACCORDINGLY.", "AIC RATINGS OF ALL THE PANELS & BRANCH BREAKERS SHALL MATCH THE FAULT CURRENT OF THE TRANSFORMER." ], "room_and_circuit_reconciliation": { "L3.A": { "guest_subpanels": 12, "king_studio": 10, "king_one_bedroom": 1, "accessible_king_one_bedroom": 1, "rooms": [ 301, 302, 303, 304, 305, 306, 307, 308, 309, 310, 311, 312 ] }, "L3.B": { "guest_subpanels": 12, "king_studio": 6, "double_queen": 5, "king_accessible": 1, "rooms": [ 313, 314, 315, 316, 317, 318, 319, 320, 321, 322, 324, 326 ], "not_listed_in_sequence": [ 323, 325 ] }, "L4.A": { "guest_subpanels": 12, "king_studio": 10, "king_one_bedroom": 1, "accessible_king_one_bedroom": 1, "rooms": [ 401, 402, 403, 404, 405, 406, 407, 408, 409, 410, 411, 412 ] }, "L4.B": { "guest_subpanels": 12, "king_studio": 6, "double_queen": 5, "king_accessible": 1, "rooms": [ 413, 414, 415, 416, 417, 418, 419, 420, 421, 422, 424, 426 ], "not_listed_in_sequence": [ 423, 425 ] }, "L5.A": { "guest_subpanels": 12, "king_studio": 10, "king_one_bedroom": 1, "accessible_king_one_bedroom": 1, "rooms": [ 501, 502, 503, 504, 505, 506, 507, 508, 509, 510, 511, 512 ] }, "L5.B": { "guest_subpanels": 12, "king_studio": 6, "double_queen": 5, "king_accessible": 1, "rooms": [ 513, 514, 515, 516, 517, 518, 519, 520, 521, 522, 524, 526 ], "not_listed_in_sequence": [ 523, 525 ] }, "sheet_total_guest_subpanels": 72, "basis": "schedule rows only; not independently verified to architectural floor plans" }, "equipment_and_special_load_register": [ { "panel": "L3.A", "circuits": { "26": "RCPTS - CORRIDOR", "28": "RCPTS - CORRIDOR/STORAGE", "30": "FIRE SMOKE DAMPER", "32": "ICE MACHINE", "34": "CIRCULATE PUMP CONTROL PNL. (C.P)" } }, { "panel": "L4.A", "circuits": { "26": "RCPTS - CORRIDOR", "28": "RCPTS - CORRIDOR/STORAGE", "30": "FIRE SMOKE DAMPER", "32": "ICE MACHINE" } }, { "panel": "L5.A", "circuits": { "26": "RCPTS - CORRIDOR", "28": "RCPTS - CORRIDOR/STORAGE", "30": "FIRE SMOKE DAMPER", "32": "ICE MACHINE", "34": "RCPTS - ROOF", "36": "EF-10", "38": "CIRCULATE PUMP CONTROL PNL. (C.P)" } }, { "panel": "L3.B", "circuits": {} }, { "panel": "L4.B", "circuits": {} }, { "panel": "L5.B", "circuits": {} } ], "cross_sheet_reconciliation": [ { "reference": "MDP", "status": "all six panels state FED FROM MDP; upstream MDP schedule/riser is not on E6.0" }, { "reference": "guestroom panels A/B", "status": "72 downstream room panel identifiers are scheduled; branch contents require E4.0/E1.0 and plan reconciliation" }, { "reference": "FIRE SMOKE DAMPER", "status": "scheduled on L3.A-30, L4.A-30, L5.A-30; mechanical/fire-alarm device locations are not shown on E6.0" }, { "reference": "ICE MACHINE", "status": "scheduled on L3.A-32, L4.A-32, L5.A-32 with CLASS A GFCI BREAKER note" }, { "reference": "CIRCULATE PUMP CONTROL PNL. (C.P)", "status": "scheduled on L3.A-34 and L5.A-38; no equipment schedule reference is printed" }, { "reference": "EF-10", "status": "scheduled only on L5.A-36; mechanical schedule/plan must be checked" }, { "reference": "RCPTS - ROOF", "status": "scheduled only on L5.A-34; roof plan must be checked" } ], "facts": [ "Six 42-circuit, 250 A bus, 250 A MLO, 120/208 V, 3-phase, 4-wire, copper, surface-mounted NEMA-1 panels are shown.", "All six panels are marked 22 kA AIC and fed from MDP.", "The schedule contains 72 guestroom subpanel feeders: 24 per floor across floors 3, 4 and 5.", "A-panels carry corridor and equipment loads; B-panels carry only guestroom feeders plus spares/space-only rows.", "SUB demand is calculated at 41% for 12 units in every panel load-code block.", "Connected totals range from 162,534 VA/451 A to 172,460 VA/479 A; demand totals range from 66,639 VA/185 A to 73,453 VA/204 A." ], "issues": [ { "id": 1, "severity": "high", "type": "printed_load_description_mismatch", "text": "L4.B circuit 2 and L3.B circuit 2 are described as KING STUDIO but are printed with 8,522 VA, 100/2 breaker and #2 wire, matching the accessible one-bedroom feeder values used on A-panels. Preserve as printed and verify room type/panel designation." }, { "id": 2, "severity": "high", "type": "printed_load_description_mismatch", "text": "L4.B/L3.B DOUBLE QUEEN and KING ACC feeders on the right side are printed at 6,694 VA, unlike L5.B where DOUBLE QUEEN is 6,817 VA and KING ACC is 7,018 VA. Verify whether L3.B/L4.B values are stale or descriptions are wrong." }, { "id": 3, "severity": "medium", "type": "fault_current", "text": "22 kA AIC is stated, but sheet notes require final utility fault current verification and equipment/branch ratings to match transformer fault current." }, { "id": 4, "severity": "medium", "type": "cross_sheet", "text": "MDP upstream protection, transformer fault current, guestroom panel schedules, and mechanical equipment schedules are outside this sheet; cross-sheet compliance is not certified here." }, { "id": 5, "severity": "medium", "type": "room_sequence", "text": "Rooms 323/325, 423/425 and 523/525 do not appear in B-panel room sequences. This may be architectural numbering, but cannot be resolved from E6.0 alone." }, { "id": 6, "severity": "low", "type": "arrow_semantics", "text": "Down arrows in description/breaker/wire cells are preserved literally as continuations. Omitted values were not propagated into blank cells." }, { "id": 7, "severity": "low", "type": "spare_space", "text": "Several SPARE and SPACE ONLY blocks use arrows across subsequent rows and show zero phase cells. Exact future breaker provisioning should be confirmed from the issued panel schedule rather than inferred." }, { "id": 8, "severity": "low", "type": "rounding", "text": "Summing the printed integer row VA values on L5.A, L3.A and L4.A is 1 VA higher than each printed connected-total VA. Phase-kVA totals agree with the printed connected totals to schedule precision; preserve the published totals and treat the 1 VA differences as rounding." } ], "validation": { "json_validated": true, "panels": 6, "rows_per_panel": 42, "total_rows": 252, "guest_subpanel_feeders": 72, "all_blanks_and_spares_preserved": true, "inferred_missing_values": false }, "secondaryAudit": { "schema": "E6.0-secondary-independent-verification-v1", "sheet": { "number": "E6.0", "title": "ELECTRICAL PANELS SCHEDULE", "engineeringPdfPage": 53, "pdfIndex": 52, "date": "NOV. 22, 2024", "sourcePdf": "/workspace/sites/ssx-cover-release/source-plans/engineering.pdf", "sourceImage": "/workspace/sites/ssx-cover-release/tmp/pdfs/next3-e52-e61/source-53.png", "sourcePixels": [ 10800, 7200 ], "normalized": [ 1920, 1280 ] }, "regions": [ { "id": "L5.A", "bbox": [ 89, 76, 844, 364 ] }, { "id": "L4.B", "bbox": [ 868, 76, 1621, 364 ] }, { "id": "L5.B", "bbox": [ 89, 388, 844, 676 ] }, { "id": "L3.A", "bbox": [ 868, 388, 1621, 676 ] }, { "id": "L4.A", "bbox": [ 89, 697, 844, 985 ] }, { "id": "L3.B", "bbox": [ 868, 697, 1621, 985 ] }, { "id": "NOTES", "bbox": [ 868, 1004, 1621, 1120 ] } ], "panels": [ { "panel": "L5.A", "feed": "MDP", "project": "HOME 2 SUITES, BRADENTON, FL", "projectNumber": "#210729", "voltage": "120/208V, 3PH, 4W", "enclosure": "NEMA-1", "aic": "22 KA", "bus": "250 AMP COPPER", "mains": "250 AMP M.L.O", "mounting": "SURFACE MOUNTED", "location": "STORAGE 5TH FLOOR", "circuitSpaces": 42, "guestFeeders": [ { "startCircuit": 1, "poles": [ 1, 3 ], "guestPanel": "A", "room": "501", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 2, "poles": [ 2, 4 ], "guestPanel": "B", "room": "507", "roomType": "ACC KING ONE BEDROOM", "breaker": "100/2", "breakerPoles": 2, "wireCount": 2, "voltAmpsPerOccupiedPole": 8522 }, { "startCircuit": 5, "poles": [ 5, 7 ], "guestPanel": "B", "room": "502", "roomType": "KING ONE BEDROOM", "breaker": "100/2", "breakerPoles": 2, "wireCount": 2, "voltAmpsPerOccupiedPole": 8443 }, { "startCircuit": 6, "poles": [ 6, 8 ], "guestPanel": "A", "room": "508", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 9, "poles": [ 9, 11 ], "guestPanel": "A", "room": "503", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 10, "poles": [ 10, 12 ], "guestPanel": "A", "room": "509", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 13, "poles": [ 13, 15 ], "guestPanel": "A", "room": "504", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 14, "poles": [ 14, 16 ], "guestPanel": "A", "room": "510", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 17, "poles": [ 17, 19 ], "guestPanel": "A", "room": "505", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 18, "poles": [ 18, 20 ], "guestPanel": "A", "room": "511", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 21, "poles": [ 21, 23 ], "guestPanel": "A", "room": "506", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 22, "poles": [ 22, 24 ], "guestPanel": "A", "room": "512", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 } ], "otherCircuits": [ { "circuits": [ 25, 27 ], "description": "SPARE", "breaker": "80/2", "poles": 2 }, { "circuits": [ 26 ], "description": "RCPTS - CORRIDOR", "breaker": "20/1", "poles": 1, "wire": 12, "VA": 900, "loadCode": "REC" }, { "circuits": [ 28 ], "description": "RCPTS - CORRIDOR/STORAGE", "breaker": "20/1", "poles": 1, "wire": 12, "VA": 720, "loadCode": "REC" }, { "circuits": [ 30 ], "description": "FIRE SMOKE DAMPER", "breaker": "20/1", "poles": 1, "wire": 12, "VA": 500, "loadCode": "EQUIP" }, { "circuits": [ 32 ], "description": "ICE MACHINE", "breaker": "20/1", "poles": 1, "wire": 12, "VA": 1500, "loadCode": "EQUIP", "note": "(CLASS A GFCI BREAKER)" }, { "circuits": [ 34 ], "description": "RCPTS - ROOF", "breaker": "20/1", "poles": 1, "wire": 12, "VA": 540, "loadCode": "REC" }, { "circuits": [ 36 ], "description": "EF-10", "breaker": "20/1", "poles": 1, "wire": 12, "VA": 50, "loadCode": "EQUIP" }, { "circuits": [ 38 ], "description": "CIRCULATE PUMP CONTROL PNL (C.P)", "breaker": "20/1", "poles": 1, "wire": 12, "VA": 441, "loadCode": "EQUIP" }, { "circuits": [ 40, 42 ], "description": "SPARE", "breaker": "20/1", "poles": 1, "VA": 0 }, { "circuits": [ 29, 31, 33, 35, 37, 39, 41 ], "description": "SPACE ONLY", "breaker": null } ], "loadCodes": { "LTG": { "connected": 0, "demand": 0 }, "REC": { "connected": 2160, "demand": 2160 }, "EQUIP": { "connected": 2491, "demand": 2491 }, "AC": { "connected": 0, "demand": 0 }, "HTG": { "connected": 0, "demand": 0 }, "LGR": { "connected": 0, "demand": 0 }, "KIT": { "connected": 0, "demand": 0 }, "SUB": { "connected": 167809, "demand": 68802 }, "GLTG": { "connected": 0, "demand": 0 }, "EVCS": { "connected": 0, "demand": 0 }, "VA": { "connected": 172460, "demand": 73453 }, "AMPS": { "connected": 479, "demand": 204 } }, "phases": { "connectedKVA": { "A": 59.97, "B": 56.64, "C": 55.85 }, "connectedAmps": { "A": 499.75, "B": 472, "C": 465.42 }, "demandKVA": { "A": 26.26, "B": 23.97, "C": 23.22 }, "demandAmps": { "A": 218.87, "B": 199.72, "C": 193.53 } } }, { "panel": "L4.B", "feed": "MDP", "project": "HOME 2 SUITES, BRADENTON, FL", "projectNumber": "#210729", "voltage": "120/208V, 3PH, 4W", "enclosure": "NEMA-1", "aic": "22 KA", "bus": "250 AMP COPPER", "mains": "250 AMP M.L.O", "mounting": "SURFACE MOUNTED", "location": "STORAGE 4TH FLOOR", "circuitSpaces": 42, "guestFeeders": [ { "startCircuit": 1, "poles": [ 1, 3 ], "guestPanel": "A", "room": "413", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 2, "poles": [ 2, 4 ], "guestPanel": "A", "room": "419", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 5, "poles": [ 5, 7 ], "guestPanel": "A", "room": "414", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 6, "poles": [ 6, 8 ], "guestPanel": "A", "room": "420", "roomType": "DOUBLE QUEEN", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 9, "poles": [ 9, 11 ], "guestPanel": "A", "room": "415", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 10, "poles": [ 10, 12 ], "guestPanel": "A", "room": "421", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 13, "poles": [ 13, 15 ], "guestPanel": "A", "room": "416", "roomType": "DOUBLE QUEEN", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6817 }, { "startCircuit": 14, "poles": [ 14, 16 ], "guestPanel": "A", "room": "422", "roomType": "DOUBLE QUEEN", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 17, "poles": [ 17, 19 ], "guestPanel": "A", "room": "417", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 18, "poles": [ 18, 20 ], "guestPanel": "A", "room": "424", "roomType": "DOUBLE QUEEN", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 21, "poles": [ 21, 23 ], "guestPanel": "A", "room": "418", "roomType": "DOUBLE QUEEN", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6817 }, { "startCircuit": 22, "poles": [ 22, 24 ], "guestPanel": "A", "room": "426", "roomType": "KING ACC", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 } ], "otherCircuits": [ { "circuits": [ 25, 27 ], "description": "SPARE", "breaker": "80/2", "poles": 2 }, { "circuits": [ 26, 28, 30 ], "description": "SPARE", "breaker": "20/1", "poles": 1 }, { "circuits": [ 29, 31, 33, 35, 37, 39, 41, 32, 34, 36, 38, 40, 42 ], "description": "SPACE ONLY", "breaker": null } ], "loadCodes": { "LTG": { "connected": 0, "demand": 0 }, "REC": { "connected": 0, "demand": 0 }, "EQUIP": { "connected": 0, "demand": 0 }, "AC": { "connected": 0, "demand": 0 }, "HTG": { "connected": 0, "demand": 0 }, "LGR": { "connected": 0, "demand": 0 }, "KIT": { "connected": 0, "demand": 0 }, "SUB": { "connected": 164804, "demand": 67570 }, "GLTG": { "connected": 0, "demand": 0 }, "EVCS": { "connected": 0, "demand": 0 }, "VA": { "connected": 164804, "demand": 67570 }, "AMPS": { "connected": 458, "demand": 188 } }, "phases": { "connectedKVA": { "A": 55.5, "B": 55.63, "C": 53.68 }, "connectedAmps": { "A": 462.53, "B": 463.55, "C": 447.29 }, "demandKVA": { "A": 22.76, "B": 22.81, "C": 22.01 }, "demandAmps": { "A": 189.64, "B": 190.06, "C": 183.39 } } }, { "panel": "L5.B", "feed": "MDP", "project": "HOME 2 SUITES, BRADENTON, FL", "projectNumber": "#210729", "voltage": "120/208V, 3PH, 4W", "enclosure": "NEMA-1", "aic": "22 KA", "bus": "250 AMP COPPER", "mains": "250 AMP M.L.O", "mounting": "SURFACE MOUNTED", "location": "STORAGE 5TH FLOOR", "circuitSpaces": 42, "guestFeeders": [ { "startCircuit": 1, "poles": [ 1, 3 ], "guestPanel": "A", "room": "513", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 2, "poles": [ 2, 4 ], "guestPanel": "A", "room": "519", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 5, "poles": [ 5, 7 ], "guestPanel": "A", "room": "514", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 6, "poles": [ 6, 8 ], "guestPanel": "A", "room": "520", "roomType": "DOUBLE QUEEN", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6817 }, { "startCircuit": 9, "poles": [ 9, 11 ], "guestPanel": "A", "room": "515", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 10, "poles": [ 10, 12 ], "guestPanel": "A", "room": "521", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 13, "poles": [ 13, 15 ], "guestPanel": "A", "room": "516", "roomType": "DOUBLE QUEEN", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6817 }, { "startCircuit": 14, "poles": [ 14, 16 ], "guestPanel": "A", "room": "522", "roomType": "DOUBLE QUEEN", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6817 }, { "startCircuit": 17, "poles": [ 17, 19 ], "guestPanel": "A", "room": "517", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 18, "poles": [ 18, 20 ], "guestPanel": "A", "room": "524", "roomType": "DOUBLE QUEEN", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6817 }, { "startCircuit": 21, "poles": [ 21, 23 ], "guestPanel": "A", "room": "518", "roomType": "DOUBLE QUEEN", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6817 }, { "startCircuit": 22, "poles": [ 22, 24 ], "guestPanel": "A", "room": "526", "roomType": "KING ACC", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 7018 } ], "otherCircuits": [ { "circuits": [ 25, 27 ], "description": "SPARE", "breaker": "80/2", "poles": 2 }, { "circuits": [ 26, 28, 30 ], "description": "SPARE", "breaker": "20/1", "poles": 1 }, { "circuits": [ 29, 31, 33, 35, 37, 39, 41, 32, 34, 36, 38, 40, 42 ], "description": "SPACE ONLY", "breaker": null } ], "loadCodes": { "LTG": { "connected": 0, "demand": 0 }, "REC": { "connected": 0, "demand": 0 }, "EQUIP": { "connected": 0, "demand": 0 }, "AC": { "connected": 0, "demand": 0 }, "HTG": { "connected": 0, "demand": 0 }, "LGR": { "connected": 0, "demand": 0 }, "KIT": { "connected": 0, "demand": 0 }, "SUB": { "connected": 162534, "demand": 66639 }, "GLTG": { "connected": 0, "demand": 0 }, "EVCS": { "connected": 0, "demand": 0 }, "VA": { "connected": 162534, "demand": 66639 }, "AMPS": { "connected": 451, "demand": 185 } }, "phases": { "connectedKVA": { "A": 54.04, "B": 54.25, "C": 54.25 }, "connectedAmps": { "A": 450.37, "B": 452.04, "C": 452.04 }, "demandKVA": { "A": 22.16, "B": 22.24, "C": 22.24 }, "demandAmps": { "A": 184.65, "B": 185.34, "C": 185.34 } } }, { "panel": "L3.A", "feed": "MDP", "project": "HOME 2 SUITES, BRADENTON, FL", "projectNumber": "#210729", "voltage": "120/208V, 3PH, 4W", "enclosure": "NEMA-1", "aic": "22 KA", "bus": "250 AMP COPPER", "mains": "250 AMP M.L.O", "mounting": "SURFACE MOUNTED", "location": "STORAGE 3RD FLOOR", "circuitSpaces": 42, "guestFeeders": [ { "startCircuit": 1, "poles": [ 1, 3 ], "guestPanel": "A", "room": "301", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 2, "poles": [ 2, 4 ], "guestPanel": "B", "room": "307", "roomType": "ACC KING ONE BEDROOM", "breaker": "100/2", "breakerPoles": 2, "wireCount": 2, "voltAmpsPerOccupiedPole": 8522 }, { "startCircuit": 5, "poles": [ 5, 7 ], "guestPanel": "B", "room": "302", "roomType": "KING ONE BEDROOM", "breaker": "100/2", "breakerPoles": 2, "wireCount": 2, "voltAmpsPerOccupiedPole": 8443 }, { "startCircuit": 6, "poles": [ 6, 8 ], "guestPanel": "A", "room": "308", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 9, "poles": [ 9, 11 ], "guestPanel": "A", "room": "303", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 10, "poles": [ 10, 12 ], "guestPanel": "A", "room": "309", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 13, "poles": [ 13, 15 ], "guestPanel": "A", "room": "304", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 14, "poles": [ 14, 16 ], "guestPanel": "A", "room": "310", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 17, "poles": [ 17, 19 ], "guestPanel": "A", "room": "305", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 18, "poles": [ 18, 20 ], "guestPanel": "A", "room": "311", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 21, "poles": [ 21, 23 ], "guestPanel": "A", "room": "306", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 22, "poles": [ 22, 24 ], "guestPanel": "A", "room": "312", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 } ], "otherCircuits": [ { "circuits": [ 25, 27 ], "description": "SPARE", "breaker": "80/2", "poles": 2 }, { "circuits": [ 26 ], "description": "RCPTS - CORRIDOR", "breaker": "20/1", "poles": 1, "wire": 12, "VA": 900, "loadCode": "REC" }, { "circuits": [ 28 ], "description": "RCPTS - CORRIDOR/STORAGE", "breaker": "20/1", "poles": 1, "wire": 12, "VA": 720, "loadCode": "REC" }, { "circuits": [ 30 ], "description": "FIRE SMOKE DAMPER", "breaker": "20/1", "poles": 1, "wire": 12, "VA": 500, "loadCode": "EQUIP" }, { "circuits": [ 32 ], "description": "ICE MACHINE", "breaker": "20/1", "poles": 1, "wire": 12, "VA": 1500, "loadCode": "EQUIP", "note": "(CLASS A GFCI BREAKER)" }, { "circuits": [ 34 ], "description": "CIRCULATE PUMP CONTROL PNL (C.P)", "breaker": "20/1", "poles": 1, "wire": 12, "VA": 441, "loadCode": "EQUIP" }, { "circuits": [ 36, 38, 40, 42 ], "description": "SPARE", "breaker": "20/1", "poles": 1, "VA": 0 }, { "circuits": [ 29, 31, 33, 35, 37, 39, 41 ], "description": "SPACE ONLY", "breaker": null } ], "loadCodes": { "LTG": { "connected": 0, "demand": 0 }, "REC": { "connected": 1620, "demand": 1620 }, "EQUIP": { "connected": 2441, "demand": 2441 }, "AC": { "connected": 0, "demand": 0 }, "HTG": { "connected": 0, "demand": 0 }, "LGR": { "connected": 0, "demand": 0 }, "KIT": { "connected": 0, "demand": 0 }, "SUB": { "connected": 167809, "demand": 68802 }, "GLTG": { "connected": 0, "demand": 0 }, "EVCS": { "connected": 0, "demand": 0 }, "VA": { "connected": 171870, "demand": 72863 }, "AMPS": { "connected": 477, "demand": 202 } }, "phases": { "connectedKVA": { "A": 59.53, "B": 56.54, "C": 55.8 }, "connectedAmps": { "A": 496.07, "B": 471.18, "C": 465 }, "demandKVA": { "A": 25.82, "B": 23.87, "C": 23.17 }, "demandAmps": { "A": 215.19, "B": 198.89, "C": 193.11 } } }, { "panel": "L4.A", "feed": "MDP", "project": "HOME 2 SUITES, BRADENTON, FL", "projectNumber": "#210729", "voltage": "120/208V, 3PH, 4W", "enclosure": "NEMA-1", "aic": "22 KA", "bus": "250 AMP COPPER", "mains": "250 AMP M.L.O", "mounting": "SURFACE MOUNTED", "location": "STORAGE 4TH FLOOR", "circuitSpaces": 42, "guestFeeders": [ { "startCircuit": 1, "poles": [ 1, 3 ], "guestPanel": "A", "room": "401", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 2, "poles": [ 2, 4 ], "guestPanel": "B", "room": "407", "roomType": "ACC KING ONE BEDROOM", "breaker": "100/2", "breakerPoles": 2, "wireCount": 2, "voltAmpsPerOccupiedPole": 8522 }, { "startCircuit": 5, "poles": [ 5, 7 ], "guestPanel": "B", "room": "402", "roomType": "KING ONE BEDROOM", "breaker": "100/2", "breakerPoles": 2, "wireCount": 2, "voltAmpsPerOccupiedPole": 8443 }, { "startCircuit": 6, "poles": [ 6, 8 ], "guestPanel": "A", "room": "408", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 9, "poles": [ 9, 11 ], "guestPanel": "A", "room": "403", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 10, "poles": [ 10, 12 ], "guestPanel": "A", "room": "409", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 13, "poles": [ 13, 15 ], "guestPanel": "A", "room": "404", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 14, "poles": [ 14, 16 ], "guestPanel": "A", "room": "410", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 17, "poles": [ 17, 19 ], "guestPanel": "A", "room": "405", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 18, "poles": [ 18, 20 ], "guestPanel": "A", "room": "411", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 21, "poles": [ 21, 23 ], "guestPanel": "A", "room": "406", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 22, "poles": [ 22, 24 ], "guestPanel": "A", "room": "412", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 } ], "otherCircuits": [ { "circuits": [ 25, 27 ], "description": "SPARE", "breaker": "80/2", "poles": 2 }, { "circuits": [ 26 ], "description": "RCPTS - CORRIDOR", "breaker": "20/1", "poles": 1, "wire": 12, "VA": 900, "loadCode": "REC" }, { "circuits": [ 28 ], "description": "RCPTS - CORRIDOR/STORAGE", "breaker": "20/1", "poles": 1, "wire": 12, "VA": 720, "loadCode": "REC" }, { "circuits": [ 30 ], "description": "FIRE SMOKE DAMPER", "breaker": "20/1", "poles": 1, "wire": 12, "VA": 500, "loadCode": "EQUIP" }, { "circuits": [ 32 ], "description": "ICE MACHINE", "breaker": "20/1", "poles": 1, "wire": 12, "VA": 1500, "loadCode": "EQUIP", "note": "(CLASS A GFCI BREAKER)" }, { "circuits": [ 34, 36, 38, 40, 42 ], "description": "SPARE", "breaker": "20/1", "poles": 1, "VA": 0 }, { "circuits": [ 29, 31, 33, 35, 37, 39, 41 ], "description": "SPACE ONLY", "breaker": null } ], "loadCodes": { "LTG": { "connected": 0, "demand": 0 }, "REC": { "connected": 1620, "demand": 1620 }, "EQUIP": { "connected": 2000, "demand": 2000 }, "AC": { "connected": 0, "demand": 0 }, "HTG": { "connected": 0, "demand": 0 }, "LGR": { "connected": 0, "demand": 0 }, "KIT": { "connected": 0, "demand": 0 }, "SUB": { "connected": 167809, "demand": 68802 }, "GLTG": { "connected": 0, "demand": 0 }, "EVCS": { "connected": 0, "demand": 0 }, "VA": { "connected": 171429, "demand": 72422 }, "AMPS": { "connected": 476, "demand": 201 } }, "phases": { "connectedKVA": { "A": 59.53, "B": 56.1, "C": 55.8 }, "connectedAmps": { "A": 496.07, "B": 467.5, "C": 465 }, "demandKVA": { "A": 25.82, "B": 23.43, "C": 23.17 }, "demandAmps": { "A": 215.19, "B": 195.22, "C": 193.11 } } }, { "panel": "L3.B", "feed": "MDP", "project": "HOME 2 SUITES, BRADENTON, FL", "projectNumber": "#210729", "voltage": "120/208V, 3PH, 4W", "enclosure": "NEMA-1", "aic": "22 KA", "bus": "250 AMP COPPER", "mains": "250 AMP M.L.O", "mounting": "SURFACE MOUNTED", "location": "STORAGE 3RD FLOOR", "circuitSpaces": 42, "guestFeeders": [ { "startCircuit": 1, "poles": [ 1, 3 ], "guestPanel": "A", "room": "313", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 2, "poles": [ 2, 4 ], "guestPanel": "A", "room": "319", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 5, "poles": [ 5, 7 ], "guestPanel": "A", "room": "314", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 6, "poles": [ 6, 8 ], "guestPanel": "A", "room": "320", "roomType": "DOUBLE QUEEN", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 9, "poles": [ 9, 11 ], "guestPanel": "A", "room": "315", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 10, "poles": [ 10, 12 ], "guestPanel": "A", "room": "321", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 13, "poles": [ 13, 15 ], "guestPanel": "A", "room": "316", "roomType": "DOUBLE QUEEN", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6817 }, { "startCircuit": 14, "poles": [ 14, 16 ], "guestPanel": "A", "room": "322", "roomType": "DOUBLE QUEEN", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 17, "poles": [ 17, 19 ], "guestPanel": "A", "room": "317", "roomType": "KING STUDIO", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 18, "poles": [ 18, 20 ], "guestPanel": "A", "room": "324", "roomType": "DOUBLE QUEEN", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 }, { "startCircuit": 21, "poles": [ 21, 23 ], "guestPanel": "A", "room": "318", "roomType": "DOUBLE QUEEN", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6817 }, { "startCircuit": 22, "poles": [ 22, 24 ], "guestPanel": "A", "room": "326", "roomType": "KING ACC", "breaker": "80/2", "breakerPoles": 2, "wireCount": 3, "voltAmpsPerOccupiedPole": 6694 } ], "otherCircuits": [ { "circuits": [ 25, 27 ], "description": "SPARE", "breaker": "80/2", "poles": 2 }, { "circuits": [ 26, 28, 30 ], "description": "SPARE", "breaker": "20/1", "poles": 1 }, { "circuits": [ 29, 31, 33, 35, 37, 39, 41, 32, 34, 36, 38, 40, 42 ], "description": "SPACE ONLY", "breaker": null } ], "loadCodes": { "LTG": { "connected": 0, "demand": 0 }, "REC": { "connected": 0, "demand": 0 }, "EQUIP": { "connected": 0, "demand": 0 }, "AC": { "connected": 0, "demand": 0 }, "HTG": { "connected": 0, "demand": 0 }, "LGR": { "connected": 0, "demand": 0 }, "KIT": { "connected": 0, "demand": 0 }, "SUB": { "connected": 164804, "demand": 67570 }, "GLTG": { "connected": 0, "demand": 0 }, "EVCS": { "connected": 0, "demand": 0 }, "VA": { "connected": 164804, "demand": 67570 }, "AMPS": { "connected": 458, "demand": 188 } }, "phases": { "connectedKVA": { "A": 55.5, "B": 55.63, "C": 53.68 }, "connectedAmps": { "A": 462.53, "B": 463.55, "C": 447.29 }, "demandKVA": { "A": 22.76, "B": 22.81, "C": 22.01 }, "demandAmps": { "A": 189.64, "B": 190.06, "C": 183.39 } } } ], "loadCodeDefinitions": { "LTG": "125% LIGHTING LOAD (N/A)", "REC": "RCPTS LOAD (100% FIRST 10KVA +50% REMAIN) on A panels; N/A on B panels", "EQUIP": "EQUIPMENT LOAD; N/A on B panels", "AC": "HVAC LOAD (N/A)", "HTG": "HEATING LOAD (N/A)", "LGR": "125% LARGEST MOTOR (N/A)", "KIT": "KITCHEN LOAD (N/A)", "SUB": "SUB PANEL x 41% PF (FOR 12 UNITS)", "GLTG": "GUESTROOM LIGHTING LOAD N/A", "EVCS": "125% ELECTRIC VEHICLE CHARGING STATION (N/A)" }, "summaryChecks": [ { "id": "S1", "finding": "Each schedule contains 12 guestroom subpanel feeders, each 2-pole. A panels L3.A/L4.A/L5.A each show ten 80/2, 3-wire Panel A feeders and two 100/2, 2-wire Panel B one-bedroom feeders. B panels show twelve 80/2, 3-wire Panel A feeders." }, { "id": "S2", "finding": "L4.B and L3.B are exact electrical duplicates in loads, phase values, breakers and room-type pattern; only room/floor identifiers differ." }, { "id": "S3", "finding": "Connected phase-kVA sums reproduce connected VA totals: L5.A 172.46; L4.B/L3.B 164.81 (rounding against 164804 VA); L5.B 162.54 (rounding against 162534 VA); L3.A 171.87; L4.A 171.43." }, { "id": "S4", "finding": "Demand totals reconcile to printed current at 120/208V 3-phase: 73453→204A, 67570→188A, 66639→185A, 72863→202A, 72422→201A." }, { "id": "S5", "finding": "Guestroom references form 24 rooms per floor: A panels rooms 301-312/401-412/501-512 and B panels 313-322, 324, 326 / 413-422, 424, 426 / 513-522, 524, 526. Room 323/423/523 and 325/425/525 do not appear as guest feeders." }, { "id": "S6", "finding": "Cross-sheet power-plan circuit chains agree: L3.A-26 corridor, -28 corridor/storage, -30 fire/smoke damper, -34 C.P.; L4.A-26, -28, -30 with no C.P.; L5.A-26, -28, -30, -38 C.P. No conflict identified." } ], "notes": [ { "id": 1, "text": "CONTRACTOR SHALL PROVIDE A PERMANENTLY AFFIXED LABEL WITH THE MAXIMUM FAULT CURRENT PER ARTICLE 110.24. THE LABEL SHALL INCLUDE THE DATE THE FAULT-CURRENT CALCULATION WAS PERFORMED AND BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. THE LABEL SHALL BE 2”X3” IN SIZE AND SHALL BE BLUE LETTERING ON A CONTRASTING BACKGROUND." }, { "id": 2, "text": "CONTRACTOR TO VERIFY FINAL CURRENT VALUES FROM ELECTRICAL UTILITY COMPANY AND PROVIDE AIC PROTECTION ACCORDINGLY." }, { "id": 3, "text": "AIC RATINGS OF ALL THE PANELS & BRANCH BREAKERS SHALL MATCH THE FAULT CURRENT OF THE TRANSFORMER." } ], "ambiguitiesAndIssues": [ { "id": 1, "severity": "medium", "text": "Schedule arrows repeat values into companion poles and spare chains. The JSON records each 2-pole guest feeder once with its occupied circuit pair; it does not miscount arrow-only rows as additional equipment." }, { "id": 2, "severity": "medium", "text": "B-panel SPARE on ckt 26 visually extends by arrows through ckt 28 and 30; recorded as a three-circuit spare chain. Similar right-side spare chains are arrow-derived and should be treated as reserved spaces, not active load." }, { "id": 3, "severity": "low", "text": "Phase-kVA displays are rounded to 0.01 kVA, so L4.B/L3.B show 164.81 kVA while the exact printed connected total is 164804 VA; L5.B shows 162.54 kVA vs 162534 VA. This is display rounding, not an arithmetic conflict." }, { "id": 4, "severity": "medium", "text": "The printed AIC is 22 KA on all six schedules, but notes 2-3 make final AIC dependent on utility current and transformer fault current. Cross-sheet short-circuit verification remains required." }, { "id": 5, "severity": "medium", "text": "The repeated guest-panel schedules identify downstream room panel references but provide no downstream branch-circuit details on E6.0; panel A/B room-panel schedules must be found elsewhere." }, { "id": 6, "severity": "low", "text": "Room sequences intentionally omit 323/423/523 and 325/425/525 from guest feeders; 523 is cross-sheet storage, supporting the omission. Other omitted numbers should be checked against architectural room use if needed." } ], "validation": { "panelCount": 6, "noteCount": 3, "guestFeederCount": 72, "guestFeedersPerPanel": 12, "allHeadersRead": true, "allOccupiedDescriptionsRead": true, "allLoadCodeTotalsRead": true, "arithmeticRecomputed": true, "OCRReliance": "none for numerical certification; full-resolution visual crops used", "status": "validated with stated arrow-chain and cross-sheet qualifications" } }, "independentCrossCheck": { "schemaVersion": "1.0", "documentType": "independent_cross_sheet_reconciliation", "batch": { "sheets": [ "E5.2", "E6.0", "E6.1" ], "engineeringPdfPages": [ 52, 53, 54 ], "sourcePdf": "/workspace/sites/ssx-cover-release/source-plans/engineering.pdf", "sourceImages": [ "/workspace/sites/ssx-cover-release/tmp/pdfs/next3-e52-e61/source-52.png", "/workspace/sites/ssx-cover-release/tmp/pdfs/next3-e52-e61/source-53.png", "/workspace/sites/ssx-cover-release/tmp/pdfs/next3-e52-e61/source-54.png" ], "priorEvidence": [ "/workspace/scratch/e9eeb133d6f5/delegated-next5/e10.json", "/workspace/scratch/e9eeb133d6f5/delegated-next5/crosscheck.json", "/workspace/scratch/e9eeb133d6f5/delegated-e12-e24/crosscheck.json", "/workspace/scratch/e9eeb133d6f5/delegated-e30-e34/crosscheck.json", "/workspace/scratch/e9eeb133d6f5/delegated-e35-e51/crosscheck.json", "/workspace/scratch/e9eeb133d6f5/delegated-e35-e51/e50.json", "/workspace/scratch/e9eeb133d6f5/delegated-e35-e51/e51.json", "/workspace/scratch/e9eeb133d6f5/delegated-e52-e61/e60-secondary.json" ], "method": "Read-only comparison of the full 10800 x 7200 source rasters and established E1.0-E5.1 evidence. Cut-sheet selection boxes, panel-index entries, panel headers, guest-panel feeder rows, branch descriptions, load-code rows and prior plan/schedule callouts were treated as separate evidence classes. Nothing illegible or unstated was inferred.", "scopeExclusions": [ "No physical-length takeoff was performed: both E5.2 details are explicitly NTS and E6.0/E6.1 are tabular schedules.", "Primary per-sheet audits were not duplicated.", "A cut-sheet image, schedule row, prototype room panel or load-analysis line is not automatically an installed quantity." ] }, "summary": { "overallStatus": "HOLD", "crossSheetTakeoffCompleteness": "PASS", "coordinationProcurementRelease": "HOLD", "takeoffCompletenessReason": "Both E5.2 NTS reference definitions and all twelve panel schedules visibly presented across E6.0/E6.1 were included in this reconciliation. The presented-sheet inventory is complete even though the project panel-schedule chain and several design relationships are not coordinated.", "releaseReason": "Release remains on HOLD because E5.2/E1.2 and E5.1 describe incompatible exterior-luminaire CCT, lumen and mounting bases; E5.2 leaves mounting and color unselected; the E6 index omits L1.E, PP and SP; L1.A prints twelve room feeders that do not match the eleven first-floor guestrooms or its own 11-unit demand note; upper-floor connecting-room types are flattened in panel descriptions; first-floor HVAC, L1.E site-lighting, DOAS distribution and EV charger branch sources are not fully scheduled; and the inherited utility fault-current and DOAS-2 voltage-drop issues remain open.", "findingCounts": { "PASS": 10, "HOLD": 11 } }, "sheetRegister": [ { "sheet": "E5.2", "title": "LIGHTING CUT-SHEETS", "page": 52, "content": "Two JSA JPL-1 manufacturer cut-sheet definitions", "scaleRule": "Each detail is explicitly SCALE: NTS; neither detail supports length or installed-count takeoff." }, { "sheet": "E6.0", "title": "ELECTRICAL PANELS SCHEDULE", "page": 53, "panelIndex": [ "L5.A", "L5.B", "L4.A", "L4.B", "L3.A", "L3.B" ], "scaleRule": "Tabular schedule; scale is not applicable." }, { "sheet": "E6.1", "title": "ELECTRICAL PANELS SCHEDULE", "page": 54, "panelIndex": [ "L2.A", "L2.B", "L1.A", "L1.B", "L1.C", "L1.D" ], "scaleRule": "Tabular schedule; scale is not applicable." } ], "fixtureReconciliation": { "e52ReferenceDefinitions": [ { "detailLabel": "LIGHTING CUT-SHEET TYPE \"SA\", \"SB\"", "scale": "NTS", "selectedFields": { "catalog": "JPL-1", "lightDistribution": "Type 2 (T2)", "ledCount": "16 (16L)", "driveCurrent": "1050 milliamps (1)", "cctCri": "3000K, 80 CRI (30K8)", "voltage": "120-277V (UNV)", "option": "House Side Shield (HSS)" }, "wattageChart": "16L at 1050 milliamps = 56W", "unselectedFields": [ "mounting", "color/finish" ] }, { "detailLabel": "LIGHTING CUT-SHEET TYPE \"SA1\", \"SB1\", \"SC1\"", "scale": "NTS", "selectedFields": { "catalog": "JPL-1", "lightDistribution": "Type 2 (T2)", "ledCount": "16 (16L)", "driveCurrent": "1050 milliamps (1)", "cctCri": "3000K, 80 CRI (30K8)", "voltage": "120-277V (UNV)" }, "wattageChart": "16L at 1050 milliamps = 56W", "optionStatus": "No HSS selection box is marked", "unselectedFields": [ "mounting", "color/finish" ] } ], "installedQuantityChain": { "e50PlanArrangements": { "SA": 7, "SA1": 3, "SB": 2, "SB1": 3, "SC1": 1, "totalArrangements": 16 }, "headMultiplicity": { "SA": 1, "SA1": 1, "SB": 2, "SB1": 2, "SC1": 3 }, "installedHeads": { "HSS": 11, "standard": 12, "total": 23 }, "e51Schedule": { "HSSQuantity": 11, "standardQuantity": 12, "total": 23 }, "quantityConclusion": "The HSS/non-HSS grouping and 23-head quantity reconcile. E5.2 contributes zero installed heads because it is a pair of NTS product definitions." } }, "panelReconciliation": { "e10Panelboards": [ "L5.A", "L5.B", "L4.A", "L4.B", "L3.A", "L3.B", "L2.A", "L2.B", "L1.A", "L1.B", "L1.C", "L1.D", "L1.E", "PP", "SP" ], "indexedOnE60E61": [ "L5.A", "L5.B", "L4.A", "L4.B", "L3.A", "L3.B", "L2.A", "L2.B", "L1.A", "L1.B", "L1.C", "L1.D" ], "notIndexedOnE60E61": [ "L1.E", "PP", "SP" ], "distributionAssembliesNotIndexedAsBranchPanelSchedules": [ "MDP", "EP", "generator integral panel" ], "headerMatchToE10": [ { "panels": "L2.A/L2.B through L5.A/L5.B", "e60e61": "120/208V, 3PH, 4W; 250A copper bus; 250A MLO; 22kA; NEMA-1; fed from MDP", "e10": "same panel ratings; feeder key 4, 285A" }, { "panel": "L1.A", "e61": "225A copper bus/MLO, 42kA, NEMA-1, fed from MDP", "e10": "same panel rating; feeder key 3, 230A" }, { "panel": "L1.B", "e61": "100A copper bus/MLO, 30kA, NEMA-1, fed from MDP", "e10": "same panel rating; feeder key 1, 130A" }, { "panels": "L1.C/L1.D", "e61": "200A copper bus/MLO, 42kA, NEMA-1, fed from MDP", "e10": "same panel ratings; feeder key 3, 230A" } ], "guestFeederCounts": { "E60": { "L3.A": 12, "L3.B": 12, "L4.A": 12, "L4.B": 12, "L5.A": 12, "L5.B": 12, "total": 72, "planRelationship": "Exactly 24 room-number feeders on each of floors 3, 4 and 5." }, "E61": { "L2.A": 12, "L2.B": 12, "L1.A": 12, "totalPrintedRoomRows": 36, "planRelationship": "The second-floor 24 rows reconcile to E3.1; the first-floor 12 rows do not reconcile to E3.0's 11 guestrooms." }, "combinedPrintedRoomRows": 108, "establishedEngineeringAndPowerPlanGuestrooms": 107, "difference": 1 }, "firstFloorConflict": { "l1aPrintedAsGuestroomFeeders": [ "101", "102", "103", "104", "105", "106", "107", "108", "109", "110", "111", "112" ], "e30ActualGuestrooms": [ "101", "102", "103", "104", "105", "106", "107", "108", "110", "112", "114" ], "falseGuestroomDescriptions": [ "109 is MECHANICAL ROOM on E3.0", "111 is ENGINEER on E3.0" ], "omittedActualGuestroom": "114 CONNECTING KING STUDIO", "internalScheduleContradiction": "L1.A prints 12 guest-panel feeder rows but its SUB demand line says SUB PANEL x 42% PF (FOR 11 UNITS)." }, "upperRoomTypeConflictExamples": [ "E6.0 calls rooms 505, 512 and 514 KING STUDIO; E3.4 calls each CONNECTING KING STUDIO.", "E6.0 calls room 524 DOUBLE QUEEN; E3.4 calls it CONNECTING QUEEN QUEEN.", "E1.0 assigns connecting prototypes their own calculated loads, so flattening the room descriptions is not merely nomenclature." ] }, "systemReconciliation": { "siteLighting": { "verifiedL1BBranches": [ { "circuits": [ 8, 10 ], "scheduleDescription": "LTS - SITE LIGHTING", "breaker": "20A/2P" }, { "circuits": [ 12, 14 ], "scheduleDescription": "LTS - SITE LIGHTING", "breaker": "20A/2P" }, { "circuits": [ 18 ], "scheduleDescription": "LTS - EXTERIOR", "breaker": "20A/1P" }, { "circuits": [ 20 ], "scheduleDescription": "LTS - FLAG POLE", "breaker": "20A/1P" }, { "circuits": [ 22 ], "scheduleDescription": "LTS - EXTERIOR", "breaker": "20A/1P" }, { "circuits": [ 24 ], "scheduleDescription": "LTS - EXTERIOR", "breaker": "20A/1P" } ], "controlNote": "The applicable L1.B rows carry Note 1: control by 20A mechanically held lighting contactors controlled by a 7-day N-1 time clock with 4-hour batteries in Panel L1.B.", "unresolved": "E5.0 also prints L1.E-18,20,22,24; E6.0/E6.1 contain no L1.E schedule." }, "mechanicalAndPlumbing": { "verified": [ "L5.A-34 RCPTS - ROOF, L5.A-36 EF-10 and L5.A-38 CIRCULATE PUMP CONTROL PNL agree with the E3.5 roof callouts.", "L3.A-34 and L5.A-38 are the scheduled circulation-pump-control branches previously called out on E3.2 and E3.4.", "L2.B provides two 30A/2P EUH branches on 26/28 and 30/32, matching the two E3.1 EUH-2 callouts.", "L1.D schedules the booster-pump control panel, two circulation-pump control panels, three gas water heaters, a motorized damper and fire/smoke damper branches; its notes require field coordination with laundry and plumbing schedules." ], "unresolved": [ "L3.B, L4.B and L5.B show circuits 26, 28 and 30 as SPARE and no EUH branch descriptions, while the mechanical plans plot two EUH-2 units on each of floors 3, 4 and 5 and the power plans omit their callouts.", "DOAS-1 and DOAS-2 are called from MDP on E3.5/E1.0, but no MDP branch schedule is presented on E6.0/E6.1.", "The first-floor power plan contains six AHUs, two FCUs with two outdoor CUs and six ACCUs; the omitted L1.E schedule prevents a complete branch/breaker reconciliation for this HVAC group." ] }, "evCharging": { "e10LoadBasis": "E1.0 includes ELECTRIC CHARGING STATION: 2 x 7.2kVA @ 125% = 18.0kVA.", "e50Conflict": "E5.0 specifies dual future-charger conduit/J-box rough-in and owner verification, while a review annotation requires at least two installed EV charging stations.", "e60e61Evidence": "Every visible scheduled panel load-code row shows EVCS = 0 / N.A., and no branch circuit description identifies an EV charger.", "conclusion": "The service load includes two chargers, but no installed branch source, panel or breaker is identified in this panel-schedule batch." } }, "findings": [ { "id": "PASS-01", "status": "PASS", "topic": "Sheet identity and scale boundary", "evidence": [ "Pages 52-54 are E5.2, E6.0 and E6.1 in order.", "Both E5.2 details print SCALE: NTS; E6.0/E6.1 are schedules." ], "conclusion": "No scaled length is released from this batch." }, { "id": "PASS-02", "status": "PASS", "topic": "E5.2 selected JPL-1 head definition", "evidence": [ "Both details select JPL-1, T2, 16L, 1050mA, 30K8 and UNV.", "The printed wattage chart gives 56W for 16L at 1050mA." ], "conclusion": "The two reference samples consistently define the same 56W, 3000K/80CRI JPL-1 head basis." }, { "id": "PASS-03", "status": "PASS", "topic": "HSS type grouping and head quantity", "evidence": [ "The SA/SB detail selects HSS; the SA1/SB1/SC1 detail does not.", "E5.0 multiplicities yield 11 HSS and 12 standard heads.", "E5.1 schedules QTY 11 HSS and QTY 12 standard." ], "conclusion": "Shield grouping and the 23 installed-head total reconcile exactly." }, { "id": "HOLD-01", "status": "HOLD", "topic": "Exterior luminaire product/performance basis conflict", "evidence": [ "E5.2 selects JPL-1/T2/16L/1050mA/30K8/UNV and prints 56W.", "E1.2 identifies 16-foot, 3000K JPL site-lighting assemblies and prints 21,163 lumens per single head.", "E5.1 instead schedules 19-foot, 4000K NV-description rows at 56W with 6,832 lumens standard and 4,252 lumens HSS." ], "conclusion": "E5.2 supports the E1.2 family/CCT/wattage direction, not the E5.1 CCT, mounting or lumen basis.", "requiredResolution": "Issue one coordinated approved catalog, optic/shield, CCT, lumen output and pole/mounting-height definition, then confirm the photometric model against it." }, { "id": "HOLD-02", "status": "HOLD", "topic": "E5.2 incomplete selectable procurement code", "evidence": [ "Neither E5.2 ordering guide marks a mounting option.", "Neither marks a color/finish option.", "E1.2 separately names a pole/finish assembly that is not fully selected on E5.2." ], "conclusion": "The cut sheets do not form a complete orderable pole/luminaire assembly.", "requiredResolution": "Select the required mounting and finish and publish the full coordinated catalog string." }, { "id": "PASS-04", "status": "PASS", "topic": "Presented panel-index coverage", "evidence": [ "E6.0 indexes and presents six schedules: L3.A/B, L4.A/B and L5.A/B.", "E6.1 indexes and presents six schedules: L2.A/B and L1.A-D." ], "conclusion": "Each of the twelve entries printed in the two panel indexes has a visible schedule on the same sheet pair." }, { "id": "PASS-05", "status": "PASS", "topic": "Panel source and header ratings", "evidence": [ "All twelve schedules say FED FROM MDP.", "Their voltage, bus, main, AIC and enclosure values match the corresponding E1.0 one-line panel definitions." ], "conclusion": "The twelve presented panel headers reconcile to the one-line sources and ratings." }, { "id": "HOLD-03", "status": "HOLD", "topic": "Project panel-index incompleteness", "evidence": [ "E1.0 defines 15 branch panelboards: L1.A-E, PP, SP and L2.A/B through L5.A/B.", "E6.0/E6.1 index only twelve and omit L1.E, PP and SP.", "MDP, EP and the generator integral panel also have no tabular branch schedules in this pair, although they are distribution assemblies rather than members of E1.0's 15-panelboard count." ], "conclusion": "The E6 index is complete only for the schedules shown, not for the project panelboard list.", "requiredResolution": "Issue the L1.E, PP and SP schedules or identify their governing separate-permit/schedule documents; state where MDP and EP branch details are governed." }, { "id": "PASS-06", "status": "PASS", "topic": "Upper-floor room-number feeder coverage", "evidence": [ "E6.0 has 12 guest-panel feeder rows in each A/B pair on floors 3, 4 and 5.", "The 24 room numbers on each floor match the 24 numbered guestrooms on E3.2-E3.4." ], "conclusion": "E6.0 covers 72 upper-floor room-number feeders without a room-number omission or duplicate." }, { "id": "PASS-07", "status": "PASS", "topic": "Second-floor room-number feeder coverage", "evidence": [ "L2.A and L2.B each contain 12 guest-panel feeder rows.", "Their combined 24 room numbers match E3.1's 24 guestrooms." ], "conclusion": "Second-floor feeder count is complete by room number." }, { "id": "HOLD-04", "status": "HOLD", "topic": "First-floor guest feeder count and identity conflict", "evidence": [ "L1.A prints 12 guest feeder rows for 101 through 112.", "E3.0 identifies only 11 guestrooms: 101-108, 110, 112 and 114.", "E3.0 calls 109 MECHANICAL ROOM and 111 ENGINEER, but E6.1 calls both KING STUDIO; E6.1 omits actual guestroom 114.", "L1.A's own SUB calculation says FOR 11 UNITS." ], "conclusion": "Across all schedules, 108 guest rows are printed against the 107-room engineering/plan basis, and the first-floor identities are not a simple one-row overcount.", "requiredResolution": "Correct the L1.A feeder-room mapping and recalculate connected/demand load from the coordinated 11-room first-floor matrix." }, { "id": "HOLD-05", "status": "HOLD", "topic": "Connecting-room type and load descriptions", "evidence": [ "E6.0 labels fifth-floor rooms 505, 512 and 514 as KING STUDIO while E3.4 labels them CONNECTING KING STUDIO.", "E6.0 labels room 524 DOUBLE QUEEN while E3.4 labels it CONNECTING QUEEN QUEEN.", "E1.0 assigns separate calculated loads to connecting-room prototypes." ], "conclusion": "Room-number coverage passes, but the schedule cannot be treated as a coordinated room-type/load matrix.", "requiredResolution": "Reconcile every room type and guest-panel A/B designation to the approved room matrix and update panel loads." }, { "id": "PASS-08", "status": "PASS", "topic": "L1.B site-lighting branch chain", "evidence": [ "E6.1 schedules L1.B 8/10 and 12/14 as 20A/2P SITE LIGHTING.", "It schedules L1.B-18, -20, -22 and -24 as exterior/flag-pole lighting.", "These circuit groups are called out on E5.0." ], "conclusion": "The E5.0 L1.B site-lighting branches have destinations and breaker definitions on E6.1." }, { "id": "HOLD-06", "status": "HOLD", "topic": "L1.E site-lighting callout has no schedule", "evidence": [ "E5.0 prints L1.E-18,20,22,24 at a site-lighting branch.", "E6.0/E6.1 omit L1.E from both indexes and provide no L1.E circuit schedule." ], "conclusion": "The distinct L1.E callout cannot be verified or safely merged into L1.B-18,20,22,24.", "requiredResolution": "Issue the L1.E schedule and confirm whether the E5.0 callout is intentional." }, { "id": "PASS-09", "status": "PASS", "topic": "Second-floor EUH branch relationship", "evidence": [ "L2.B schedules two 30A/2P EUH branches on 26/28 and 30/32.", "E3.1 assigns its two EUH-2 occurrences to the same circuit pairs." ], "conclusion": "Second-floor EUH quantity and circuit allocation reconcile." }, { "id": "HOLD-07", "status": "HOLD", "topic": "Floors 3-5 EUH power remains unscheduled", "evidence": [ "Mechanical plans show two EUH-2 units on each of floors 3, 4 and 5.", "E3.2-E3.4 show no EUH power callouts.", "L3.B, L4.B and L5.B mark 26, 28 and 30 SPARE and show no EUH description." ], "conclusion": "Six upper-floor heaters remain without a coordinated electrical branch assignment.", "requiredResolution": "Assign and schedule the six EUH branches or revise the mechanical equipment scope." }, { "id": "PASS-10", "status": "PASS", "topic": "Roof EF-10 and common-equipment branch chain", "evidence": [ "E3.5 calls L5.A-34 for roof receptacles, L5.A-36 for EF-10 and L5.A-38 for circulation-pump control.", "E6.0 contains matching descriptions, 20A/1P breakers and 540VA, 50VA and 441VA values." ], "conclusion": "These three roof/common branches are fully destination-addressable in the panel schedule." }, { "id": "HOLD-08", "status": "HOLD", "topic": "First-floor HVAC and DOAS schedule chain", "evidence": [ "E3.0 plots six AHUs, two FCUs with two outdoor CUs and six ACCUs.", "E3.5 calls DOAS-1 on MDP-44/46/48 and DOAS-2 on MDP-50/52/54.", "No L1.E or MDP branch schedule is present on E6.0/E6.1." ], "conclusion": "The panel-schedule batch cannot close the first-floor HVAC or DOAS breaker/load reconciliation.", "requiredResolution": "Issue the governing L1.E and MDP schedules and reconcile each equipment nameplate, disconnect and breaker." }, { "id": "HOLD-09", "status": "HOLD", "topic": "EV service load has no branch source", "evidence": [ "E1.0 includes 18.0kVA for two 7.2kVA chargers at 125 percent.", "E5.0 conflicts between future rough-in/owner verification and a minimum two installed-station annotation.", "Every E6.0/E6.1 EVCS load-code row is 0/N.A., and no visible circuit description identifies an EV charger." ], "conclusion": "The service-load allowance does not identify an installed source panel or branch breaker.", "requiredResolution": "Resolve installed versus future scope and issue panel/circuit, breaker, feeder, disconnect and equipment ratings for the approved EV quantity." }, { "id": "HOLD-10", "status": "HOLD", "topic": "Fault-current ratings remain conditional", "evidence": [ "The twelve panel AIC ratings equal the E1.0A selected values and exceed the calculated values under its assumption.", "E6.0/E6.1 notes require final utility current verification and AIC matching.", "E1.0 leaves transformer capacity to the utility, while E1.0A assumes 750kVA and 5 percent impedance." ], "conclusion": "Panel AIC selection is internally coordinated but not final for procurement.", "requiredResolution": "Obtain utility maximum available fault current/final transformer data and reconfirm the study and equipment ratings." }, { "id": "HOLD-11", "status": "HOLD", "topic": "Inherited DOAS-2 voltage-drop exceedance", "evidence": [ "E1.0 states a 3 percent feeder limit.", "E1.0A calculates MDP-to-DOAS-2 at 3.26 percent.", "E6.0/E6.1 add no conductor or source revision that resolves it." ], "conclusion": "The DOAS-2 feeder remains above the stated design limit.", "requiredResolution": "Resize or reroute the feeder and update the one-line/calculation." } ], "quantityAndDuplicateRules": [ { "rule": "E5.2's two NTS cut-sheet samples are reference definitions only and add zero luminaires to project totals. Installed head quantity comes once from the E5.0 plan, corroborated by E5.1 schedule quantities." }, { "rule": "SA/SB/SA1/SB1/SC1 are arrangement tags. Apply the shown one-, two- or three-head multiplicity once; do not add arrangement count and head count together." }, { "rule": "The words PANEL A and PANEL B in guest feeder descriptions identify in-room prototype panels, not additional floor distribution panels Lx.A and Lx.B." }, { "rule": "Guest feeder rows, E1.0 prototype rows and E4.0/E4.1 detail samples are alternate views of guestroom scope. Do not sum them. The 108 printed feeder rows are not releasable until HOLD-04 is corrected." }, { "rule": "Panel schedule circuit rows and load-code totals are electrical allocation/load evidence, not counts of downstream receptacles, luminaires, dampers, heaters or pumps unless a one-to-one equipment identity is explicitly printed." }, { "rule": "SPARE and SPACE ONLY rows are not installed equipment quantities." }, { "rule": "E1.0's EV charging and other load-analysis entries are service-calculation allowances, not proof of installed equipment." } ], "releaseChecks": [ { "status": "PASS", "item": "Both E5.2 NTS product definitions captured; zero installed quantity assigned to samples." }, { "status": "PASS", "item": "All twelve schedules listed in the E6.0/E6.1 panel indexes reconciled." }, { "status": "PASS", "item": "HSS/non-HSS split and 23 exterior-luminaire heads reconcile." }, { "status": "HOLD", "item": "Coordinate JPL/NV catalog, 3000K/4000K, lumen and 16-foot/19-foot mounting bases." }, { "status": "HOLD", "item": "Complete E5.2 mounting and finish selections." }, { "status": "HOLD", "item": "Issue or identify L1.E, PP and SP schedules." }, { "status": "HOLD", "item": "Correct L1.A's first-floor room feeder identities and 12-row versus 11-unit contradiction." }, { "status": "HOLD", "item": "Reconcile connecting-room schedule descriptions and calculated loads." }, { "status": "HOLD", "item": "Resolve the unscheduled L1.E site-lighting circuit group." }, { "status": "HOLD", "item": "Assign power to six floor-3-through-floor-5 EUH-2 units." }, { "status": "HOLD", "item": "Provide the L1.E and MDP branch schedules for HVAC and DOAS coordination." }, { "status": "HOLD", "item": "Resolve EV installed-versus-future scope and branch source." }, { "status": "HOLD", "item": "Confirm utility fault current and correct DOAS-2 feeder voltage drop." } ], "validation": { "jsonSyntax": "valid; jq -e validation passed", "visualCoverage": "E5.2 full sheet plus full-resolution ordering-guide crops; E6.0 and E6.1 full sheets plus readable schedule crops, panel indexes, notes and title blocks.", "failClosed": true, "generatedUtc": "2026-09-07T22:39:27Z" } } }