{
  "schema": "delegated-sheet-takeoff-v1",
  "sheet": "E3.4",
  "title": "POWER FIFTH FLOOR PLAN",
  "engineeringPdfPage": 46,
  "pdfPageIndex": 45,
  "projectNo": "210729",
  "drawnBy": "PL",
  "checkedBy": "DV",
  "date": "NOV. 22, 2024",
  "source": {
    "raster": "/workspace/sites/ssx-cover-release/tmp/pdfs/next5-e30-e34/source-46.png",
    "rasterPixels": [
      10800,
      7200
    ],
    "text": "/workspace/sites/ssx-cover-release/tmp/pdfs/next5-e30-e34/source-46.txt",
    "pdf": "/workspace/sites/ssx-cover-release/source-plans/engineering.pdf",
    "pdfPagePoints": [
      2592,
      1728
    ]
  },
  "coordinateSpace": {
    "width": 1920,
    "height": 1280,
    "origin": "top-left",
    "sourceToNormalized": 5.625,
    "pdfToNormalized": 0.7407407407
  },
  "review": {
    "method": "E2.0 count-first full-sheet audit; every black plan occurrence marked once; detail 2 segregated as N.T.S. reference samples.",
    "status": "certified visible occurrences; wiring drawn-path-only",
    "accepted": false
  },
  "scale": {
    "detail1PrintedScale": "1/8 inch = 1 foot",
    "detail1PdfPointsPerFoot": 9,
    "detail1SourcePixelsPerFoot": 37.5,
    "detail1NormalizedUnitsPerFoot": 6.6666667,
    "detail1Verification": "Printed scale reconciled to native 36x24-inch PDF geometry: 72 pt/in x 1/8 in/ft = 9 PDF pt/ft; 10800/2592 gives 37.5 source px/ft.",
    "detail2Scale": "N.T.S.",
    "detail2MeasurementPolicy": "No LF or physical quantity measured from enlarged elevator-control detail."
  },
  "regions": [
    {
      "id": "plan",
      "label": "Detail 1 - Power Fifth Floor Plan",
      "box": [
        245,
        175,
        1585,
        720
      ],
      "scale": "1/8 inch = 1 foot"
    },
    {
      "id": "west_corridor",
      "label": "west maintenance receptacle chain",
      "box": [
        260,
        365,
        705,
        485
      ]
    },
    {
      "id": "central_corridor",
      "label": "C.P and L5.A-38 / L5.A-26",
      "box": [
        690,
        365,
        1010,
        490
      ]
    },
    {
      "id": "storage_elevator",
      "label": "Storage 523 / Elevator Lobby 500 / Stair 1",
      "box": [
        1275,
        195,
        1510,
        450
      ]
    },
    {
      "id": "general_notes",
      "label": "General Notes 1-4",
      "box": [
        290,
        790,
        745,
        985
      ]
    },
    {
      "id": "fire_smoke_damper_note",
      "label": "Fire Smoke Damper Note",
      "box": [
        290,
        995,
        745,
        1085
      ]
    },
    {
      "id": "key_notes",
      "label": "Key Notes 1-2",
      "box": [
        290,
        1095,
        745,
        1215
      ]
    },
    {
      "id": "elevator_detail",
      "label": "Detail 2 - Enlarged Elevator Control",
      "box": [
        760,
        785,
        1705,
        1215
      ],
      "scale": "N.T.S."
    }
  ],
  "counts": {
    "installedPlanOccurrences": 15,
    "byCategory": {
      "above_ceiling_duplex_receptacle": 7,
      "circuit_home_run_callout": 3,
      "duplex_receptacle": 1,
      "equipment_connection_assembly": 1,
      "panelboard": 2,
      "tagged_special_outlet_or_equipment_connection": 1
    },
    "aboveCeilingCorridorReceptacles": 7,
    "otherReceptacles": 1,
    "taggedEquipmentOrSpecialConnections": 2,
    "panelboards": 2,
    "planCircuitHomeRunCallouts": 3,
    "certifiedZero": {
      "guestroomPowerDevicesOnThisSheet": 0,
      "switches": 0,
      "standaloneMotorSymbols": 0,
      "fans": 0,
      "disconnectsSeparatelyTaggedOnScaledPlan": 0,
      "lowVoltageDevices": 0,
      "fireSmokeDamperJBoxesWithPlottedLocations": 0
    },
    "detailReferenceSamplesExcludedFromInstalledCounts": 14
  },
  "occurrences": [
    {
      "id": "E34-HR-28",
      "tag": "L5.A-28",
      "category": "circuit_home_run_callout",
      "center": [
        1314.81,
        247.41
      ],
      "roomOrArea": "STORAGE 523",
      "basis": "distinct visible plan occurrence",
      "status": "certified_visual_occurrence"
    },
    {
      "id": "E34-REC-STOR-01",
      "tag": "REC",
      "category": "duplex_receptacle",
      "center": [
        1320.96,
        257.85
      ],
      "roomOrArea": "STORAGE 523",
      "basis": "distinct visible plan occurrence",
      "status": "certified_visual_occurrence",
      "circuit": "L5.A-28"
    },
    {
      "id": "E34-PNL-L5A",
      "tag": "L5.A",
      "category": "panelboard",
      "center": [
        1330.15,
        258.07
      ],
      "roomOrArea": "STORAGE 523",
      "basis": "distinct visible plan occurrence",
      "status": "certified_visual_occurrence",
      "keyedNote": 1
    },
    {
      "id": "E34-PNL-L5B",
      "tag": "L5.B",
      "category": "panelboard",
      "center": [
        1344.59,
        258.07
      ],
      "roomOrArea": "STORAGE 523",
      "basis": "distinct visible plan occurrence",
      "status": "certified_visual_occurrence",
      "keyedNote": 1
    },
    {
      "id": "E34-HP-01",
      "tag": "HP",
      "category": "tagged_special_outlet_or_equipment_connection",
      "center": [
        1295.11,
        312.59
      ],
      "roomOrArea": "ELEVATOR LOBBY 500",
      "basis": "distinct visible plan occurrence",
      "status": "certified_visual_occurrence",
      "identity": "Exact HP tag preserved; device function is not defined on this sheet and is not guessed."
    },
    {
      "id": "E34-REC-AC-01",
      "tag": "REC-AC",
      "category": "above_ceiling_duplex_receptacle",
      "center": [
        298.89,
        408.96
      ],
      "roomOrArea": "CORRIDOR 533",
      "basis": "distinct visible plan occurrence",
      "status": "certified_visual_occurrence",
      "keyedNote": 2
    },
    {
      "id": "E34-REC-AC-03",
      "tag": "REC-AC",
      "category": "above_ceiling_duplex_receptacle",
      "center": [
        698.07,
        408.96
      ],
      "roomOrArea": "CORRIDOR 533",
      "basis": "distinct visible plan occurrence",
      "status": "certified_visual_occurrence",
      "keyedNote": 2
    },
    {
      "id": "E34-REC-AC-06",
      "tag": "REC-AC",
      "category": "above_ceiling_duplex_receptacle",
      "center": [
        1204.81,
        408.96
      ],
      "roomOrArea": "CORRIDOR 533",
      "basis": "distinct visible plan occurrence",
      "status": "certified_visual_occurrence",
      "keyedNote": 2
    },
    {
      "id": "E34-HR-38",
      "tag": "L5.A-38",
      "category": "circuit_home_run_callout",
      "center": [
        774.07,
        417.04
      ],
      "roomOrArea": "C.P / corridor ceiling zone",
      "basis": "distinct visible plan occurrence",
      "status": "certified_visual_occurrence"
    },
    {
      "id": "E34-CP-01",
      "tag": "C.P",
      "category": "equipment_connection_assembly",
      "center": [
        786.67,
        417.85
      ],
      "roomOrArea": "CORRIDOR 533 ceiling zone",
      "basis": "distinct visible plan occurrence",
      "status": "certified_visual_occurrence",
      "circuit": "L5.A-38",
      "identity": "Circulate pump per project abbreviation; adjacent square/circular connection graphic treated as one tagged assembly because subcomponents are not separately labeled."
    },
    {
      "id": "E34-HR-26",
      "tag": "L5.A-26",
      "category": "circuit_home_run_callout",
      "center": [
        951.85,
        427.78
      ],
      "roomOrArea": "CORRIDOR 533",
      "basis": "distinct visible plan occurrence",
      "status": "certified_visual_occurrence"
    },
    {
      "id": "E34-REC-AC-04",
      "tag": "REC-AC",
      "category": "above_ceiling_duplex_receptacle",
      "center": [
        783.26,
        428.15
      ],
      "roomOrArea": "CORRIDOR 533",
      "basis": "distinct visible plan occurrence",
      "status": "certified_visual_occurrence",
      "keyedNote": 2
    },
    {
      "id": "E34-REC-AC-02",
      "tag": "REC-AC",
      "category": "above_ceiling_duplex_receptacle",
      "center": [
        474.74,
        436.22
      ],
      "roomOrArea": "CORRIDOR 533",
      "basis": "distinct visible plan occurrence",
      "status": "certified_visual_occurrence",
      "keyedNote": 2
    },
    {
      "id": "E34-REC-AC-05",
      "tag": "REC-AC",
      "category": "above_ceiling_duplex_receptacle",
      "center": [
        951.48,
        436.22
      ],
      "roomOrArea": "CORRIDOR 533",
      "basis": "distinct visible plan occurrence",
      "status": "certified_visual_occurrence",
      "keyedNote": 2
    },
    {
      "id": "E34-REC-AC-07",
      "tag": "REC-AC",
      "category": "above_ceiling_duplex_receptacle",
      "center": [
        1449.7,
        436.22
      ],
      "roomOrArea": "CORRIDOR 533",
      "basis": "distinct visible plan occurrence",
      "status": "certified_visual_occurrence",
      "keyedNote": 2
    }
  ],
  "rooms": {
    "guestroomCount": 24,
    "otherLabeledSpaces": 5,
    "totalLabeledSpaces": 29,
    "guestroomTypeRollup": {
      "KING STUDIO": 13,
      "CONNECTING KING STUDIO": 3,
      "ACCESSIBLE KING ONE BEDROOM": 1,
      "KING ONE BEDROOM": 1,
      "QUEEN QUEEN": 4,
      "CONNECTING QUEEN QUEEN": 1,
      "KING ACCESSIBLE": 1
    },
    "entries": [
      {
        "number": "501",
        "name": "KING STUDIO",
        "labelCenter": [
          313.78,
          283.63
        ],
        "selectableText": true,
        "takeoffDisposition": "architectural_background_no_power_symbols_do_not_multiply"
      },
      {
        "number": "503",
        "name": "KING STUDIO",
        "labelCenter": [
          393.19,
          283.63
        ],
        "selectableText": true,
        "takeoffDisposition": "architectural_background_no_power_symbols_do_not_multiply"
      },
      {
        "number": "505",
        "name": "CONNECTING KING STUDIO",
        "labelCenter": [
          483.41,
          283.63
        ],
        "selectableText": true,
        "takeoffDisposition": "architectural_background_no_power_symbols_do_not_multiply"
      },
      {
        "number": "507",
        "name": "ACCESSIBLE KING ONE BEDROOM",
        "labelCenter": [
          567.26,
          314.22
        ],
        "selectableText": true,
        "takeoffDisposition": "architectural_background_no_power_symbols_do_not_multiply"
      },
      {
        "number": "509",
        "name": "KING STUDIO",
        "labelCenter": [
          734.44,
          283.63
        ],
        "selectableText": true,
        "takeoffDisposition": "architectural_background_no_power_symbols_do_not_multiply"
      },
      {
        "number": "511",
        "name": "KING STUDIO",
        "labelCenter": [
          822.81,
          283.63
        ],
        "selectableText": true,
        "takeoffDisposition": "architectural_background_no_power_symbols_do_not_multiply"
      },
      {
        "number": "513",
        "name": "KING STUDIO",
        "labelCenter": [
          901.41,
          283.63
        ],
        "selectableText": true,
        "takeoffDisposition": "architectural_background_no_power_symbols_do_not_multiply"
      },
      {
        "number": "515",
        "name": "KING STUDIO",
        "labelCenter": [
          989.41,
          283.63
        ],
        "selectableText": true,
        "takeoffDisposition": "architectural_background_no_power_symbols_do_not_multiply"
      },
      {
        "number": "517",
        "name": "KING STUDIO",
        "labelCenter": [
          1070.3,
          283.63
        ],
        "selectableText": true,
        "takeoffDisposition": "architectural_background_no_power_symbols_do_not_multiply"
      },
      {
        "number": "519",
        "name": "KING STUDIO",
        "labelCenter": [
          1160.52,
          283.63
        ],
        "selectableText": true,
        "takeoffDisposition": "architectural_background_no_power_symbols_do_not_multiply"
      },
      {
        "number": "521",
        "name": "KING STUDIO",
        "labelCenter": [
          1240.67,
          283.63
        ],
        "selectableText": true,
        "takeoffDisposition": "architectural_background_no_power_symbols_do_not_multiply"
      },
      {
        "number": "502",
        "name": "KING ONE BEDROOM",
        "labelCenter": [
          392.74,
          554.59
        ],
        "selectableText": true,
        "takeoffDisposition": "architectural_background_no_power_symbols_do_not_multiply"
      },
      {
        "number": "504",
        "name": "KING STUDIO",
        "labelCenter": [
          484.67,
          557.78
        ],
        "selectableText": true,
        "takeoffDisposition": "architectural_background_no_power_symbols_do_not_multiply"
      },
      {
        "number": "506",
        "name": "KING STUDIO",
        "labelCenter": [
          566.3,
          557.78
        ],
        "selectableText": true,
        "takeoffDisposition": "architectural_background_no_power_symbols_do_not_multiply"
      },
      {
        "number": "508",
        "name": "KING STUDIO",
        "labelCenter": [
          656.37,
          557.78
        ],
        "selectableText": true,
        "takeoffDisposition": "architectural_background_no_power_symbols_do_not_multiply"
      },
      {
        "number": "510",
        "name": "KING STUDIO",
        "labelCenter": [
          734.81,
          559.33
        ],
        "selectableText": true,
        "takeoffDisposition": "architectural_background_no_power_symbols_do_not_multiply"
      },
      {
        "number": "512",
        "name": "CONNECTING KING STUDIO",
        "labelCenter": [
          824.22,
          557.78
        ],
        "selectableText": true,
        "takeoffDisposition": "architectural_background_no_power_symbols_do_not_multiply"
      },
      {
        "number": "514",
        "name": "CONNECTING KING STUDIO",
        "labelCenter": [
          904.96,
          557.78
        ],
        "selectableText": true,
        "takeoffDisposition": "architectural_background_no_power_symbols_do_not_multiply"
      },
      {
        "number": "516",
        "name": "QUEEN QUEEN",
        "labelCenter": [
          990.81,
          557.78
        ],
        "selectableText": true,
        "takeoffDisposition": "architectural_background_no_power_symbols_do_not_multiply"
      },
      {
        "number": "518",
        "name": "QUEEN QUEEN",
        "labelCenter": [
          1075.85,
          557.78
        ],
        "selectableText": true,
        "takeoffDisposition": "architectural_background_no_power_symbols_do_not_multiply"
      },
      {
        "number": "520",
        "name": "QUEEN QUEEN",
        "labelCenter": [
          1160.37,
          557.78
        ],
        "selectableText": true,
        "takeoffDisposition": "architectural_background_no_power_symbols_do_not_multiply"
      },
      {
        "number": "522",
        "name": "QUEEN QUEEN",
        "labelCenter": [
          1245.19,
          557.78
        ],
        "selectableText": true,
        "takeoffDisposition": "architectural_background_no_power_symbols_do_not_multiply"
      },
      {
        "number": "524",
        "name": "CONNECTING QUEEN QUEEN",
        "labelCenter": [
          1329.41,
          566.0
        ],
        "selectableText": true,
        "takeoffDisposition": "architectural_background_no_power_symbols_do_not_multiply"
      },
      {
        "number": "526",
        "name": "KING ACCESSIBLE",
        "labelCenter": [
          1424.37,
          561.85
        ],
        "selectableText": true,
        "takeoffDisposition": "architectural_background_no_power_symbols_do_not_multiply"
      },
      {
        "number": "523",
        "name": "STORAGE",
        "labelCenter": [
          1327.26,
          243.33
        ],
        "selectableText": true,
        "takeoffDisposition": "direct_plan_area"
      },
      {
        "number": "500",
        "name": "ELEVATOR LOBBY",
        "labelCenter": [
          1327.26,
          315.41
        ],
        "selectableText": true,
        "takeoffDisposition": "direct_plan_area"
      },
      {
        "number": "001",
        "name": "STAIR 1",
        "labelCenter": [
          1450.3,
          312.07
        ],
        "selectableText": true,
        "takeoffDisposition": "direct_plan_area"
      },
      {
        "number": "002",
        "name": "STAIR 2",
        "labelCenter": [
          334.89,
          468.07
        ],
        "selectableText": true,
        "takeoffDisposition": "direct_plan_area"
      },
      {
        "number": "533",
        "name": "CORRIDOR",
        "labelCenter": [
          912.3,
          422.52
        ],
        "selectableText": true,
        "takeoffDisposition": "direct_plan_area"
      }
    ]
  },
  "gridReferences": {
    "numeric": [
      "1",
      "2",
      "3",
      "4",
      "5",
      "6",
      "7",
      "8",
      "9",
      "10",
      "11",
      "12",
      "13",
      "14",
      "15"
    ],
    "alphabetic": [
      "A",
      "B",
      "C",
      "D",
      "E",
      "F",
      "G",
      "H",
      "J",
      "J.1",
      "J.2"
    ],
    "printedPlanDimensions": []
  },
  "notes": {
    "general": [
      {
        "number": 1,
        "text": "For home runs (from units) 100 FT or more, the electrical contractor has to check the voltage drop and select the suitable cables size to comply with the maximum allowed voltage drop for the feeder conductor (3%). The maximum combined voltage drop on both installed feeder conductors and branch circuit conductors to the farthest connected load or outlet shall not exceed 5 percent.",
        "region": "general_notes"
      },
      {
        "number": 2,
        "text": "The contractor shall verify with the owner/franchise for the quantities and locations of the low voltage system devices (camera, card reader, wireless access point, etc.) and provide all necessary accessories to complete the wiring, power supply for the devices as per the manufacturer specifications/installation guidelines.",
        "region": "general_notes"
      },
      {
        "number": 3,
        "text": "The contractor shall verify location of all floor outlets with furniture/arch. prior to installation.",
        "region": "general_notes"
      },
      {
        "number": 4,
        "text": "Electrical contractors must verify all electrical requirements with the HVAC and plumbing systems to provide all necessary accessories to complete the control wiring for the motors.",
        "region": "general_notes"
      }
    ],
    "fireSmokeDamper": {
      "number": 1,
      "text": "Contractor shall provide J-boxes for fire smoke dampers at 5th floor, connect to L5.A-30, using 2#12, 1/2-inch conduit.",
      "quantityPrinted": null,
      "plottedLocationCount": 0
    },
    "keyed": [
      {
        "number": 1,
        "text": "The panelboard shall be lockable and accessible to qualified persons only. Field verification of the best location of electrical panels prior to installation. The location of electrical panels must comply with 110.26 and 240.24 of the NEC.",
        "planReferences": [
          "L5.A",
          "L5.B"
        ]
      },
      {
        "number": 2,
        "text": "Receptacle outlets above the ceiling for maintenance.",
        "planReferences": [
          "seven corridor receptacle occurrences"
        ]
      }
    ],
    "elevator": [
      {
        "number": 1,
        "text": "Drawing for guideline only. Contact elevator suppliers to verify all power requirements prior to installation.",
        "region": "elevator_detail"
      },
      {
        "number": 2,
        "text": "Provide motor control (TSU) located at the top of the hoistway.",
        "region": "elevator_detail"
      },
      {
        "number": 3,
        "text": "Provide inspection & test panel (LDU) located within the door jamb at floor 5.",
        "region": "elevator_detail"
      },
      {
        "number": 4,
        "text": "Contractors to supply and install the following equipment (and wiring/conduit) per elevator requirements: (a) fusible disconnect (JH) with auxiliary contact & shunt trip, for elevator system; (b) fusible disconnect (JH1) with auxiliary contact, for motor control; (c) non-fusible disconnect (JHS) with auxiliary contact, for inspection & test panel (LDU); (d) disconnecting means (JHL) for auxiliary power and lighting; (e) overcurrent protective devices within JH and JH1; (f) ground fault protection, as required per NEC 620-61.",
        "region": "elevator_detail"
      },
      {
        "number": 5,
        "text": "Electrical contractors should verify all electrical requirement with elevator supplier prior to installation.",
        "region": "elevator_detail"
      }
    ]
  },
  "elevatorControlDetail": {
    "detailNumber": 2,
    "title": "ENLARGED ELEVATOR CONTROL (LOCATED ON A TOP OF ELEVATOR SHAFT)",
    "scale": "N.T.S.",
    "quantityPolicy": "reference graphics only; never added to scaled-plan installed quantities",
    "samples": [
      {
        "tag": "LDU",
        "description": "inspection & test panel within door jamb at floor 5",
        "referenceSampleCount": 2
      },
      {
        "tag": "JHS",
        "description": "non-fusible disconnect with auxiliary contact for LDU",
        "referenceSampleCount": 2
      },
      {
        "tag": "JH1",
        "description": "fusible disconnect with auxiliary contact for motor control",
        "referenceSampleCount": 2
      },
      {
        "tag": "TSU",
        "description": "motor control at top of hoistway",
        "referenceSampleCount": 2
      },
      {
        "tag": "EP-9",
        "description": "top-left elevator power callout",
        "referenceSampleCount": 1
      },
      {
        "tag": "EP-7",
        "description": "top-right elevator power callout",
        "referenceSampleCount": 1
      },
      {
        "tag": "EP-3",
        "description": "bottom-left elevator power callout",
        "referenceSampleCount": 1
      },
      {
        "tag": "EP-1",
        "description": "bottom-right elevator power callout",
        "referenceSampleCount": 1
      },
      {
        "tag": "001",
        "description": "callout printed at right side of each elevator sample",
        "referenceSampleCount": 2,
        "interpretation": "not resolved on sheet"
      }
    ],
    "unmeasuredCurves": "All detail-2 connection graphics; N.T.S.",
    "notesSource": "Notes for Elevator 1-5 and 4a-f"
  },
  "crossReferences": [
    {
      "target": "NEC 110.26 and 240.24",
      "source": "Key Note 1",
      "purpose": "panel access/location"
    },
    {
      "target": "NEC 620-61",
      "source": "Elevator Note 4f",
      "purpose": "ground-fault protection"
    },
    {
      "target": "elevator supplier requirements",
      "source": "Elevator Notes 1,4,5",
      "purpose": "power, equipment, wiring and conduit requirements",
      "status": "external verification required"
    },
    {
      "target": "owner/franchise and manufacturer specifications",
      "source": "General Note 2",
      "purpose": "low-voltage device quantities, locations, accessories and power",
      "status": "unresolved external selection"
    },
    {
      "target": "furniture/architect",
      "source": "General Note 3",
      "purpose": "floor outlet locations",
      "status": "field/design coordination"
    },
    {
      "target": "HVAC and plumbing systems",
      "source": "General Note 4",
      "purpose": "motor control wiring and accessories",
      "status": "external coordination"
    }
  ],
  "wiring": {
    "status": "drawn connection measurement - not complete installed routing takeoff",
    "runCount": 7,
    "totalDrawnPathLF": 181.9431,
    "totalDrawnPathLFNearestHalf": 182.0,
    "knownConductorLF": null,
    "installedRouteLF": null,
    "conduitLF": null,
    "verticalLF": null,
    "hiddenLF": null,
    "fittingCount": null,
    "notIncluded": [
      "N.T.S. elevator detail curves",
      "home-run arrow leaders/slash marks",
      "hidden routing",
      "vertical drops",
      "conductor multiplicity",
      "conduit fill",
      "slack",
      "unshown fire-smoke-damper J-box routing"
    ],
    "runs": [
      {
        "id": "E34-W01",
        "pdfDrawingIndex": 18923,
        "group": "L5.A-26 corridor maintenance receptacle chain",
        "category": "visible_plan_scale_connection",
        "sourceCommandsPdf": [
          [
            "C",
            403.498,
            552.106,
            469.438,
            607.98,
            561.125,
            622.195,
            640.886,
            588.914
          ]
        ],
        "normalizedPolyline": [
          [
            298.89,
            408.97
          ],
          [
            318.04,
            423.03
          ],
          [
            338.66,
            434.15
          ],
          [
            360.41,
            442.28
          ],
          [
            382.97,
            447.37
          ],
          [
            406.01,
            449.35
          ],
          [
            429.2,
            448.19
          ],
          [
            452.22,
            443.84
          ],
          [
            474.73,
            436.23
          ]
        ],
        "drawnPathLF": 28.0823,
        "cumulativeDrawnPathLF": 28.0823,
        "strokeWidthPdfPt": 0.5399999618530273,
        "dashes": "[] 0",
        "installedRouteLF": null,
        "conductorLF": null,
        "verticalDropLF": null,
        "hiddenRunLF": null,
        "conduitLF": null,
        "fittings": null,
        "measurement": "visible drawn centerline only",
        "accepted": false
      },
      {
        "id": "E34-W02",
        "pdfDrawingIndex": 18924,
        "group": "L5.A-26 corridor maintenance receptacle chain",
        "category": "visible_plan_scale_connection",
        "sourceCommandsPdf": [
          [
            "C",
            942.372,
            552.065,
            840.588,
            530.628,
            734.568,
            543.576,
            640.934,
            588.878
          ]
        ],
        "normalizedPolyline": [
          [
            698.05,
            408.94
          ],
          [
            669.66,
            404.17
          ],
          [
            641.11,
            401.78
          ],
          [
            612.56,
            401.74
          ],
          [
            584.15,
            404.03
          ],
          [
            556.02,
            408.64
          ],
          [
            528.31,
            415.56
          ],
          [
            501.18,
            424.75
          ],
          [
            474.77,
            436.21
          ]
        ],
        "drawnPathLF": 34.3588,
        "cumulativeDrawnPathLF": 62.4411,
        "strokeWidthPdfPt": 0.5399999618530273,
        "dashes": "[] 0",
        "installedRouteLF": null,
        "conductorLF": null,
        "verticalDropLF": null,
        "hiddenRunLF": null,
        "conduitLF": null,
        "fittings": null,
        "measurement": "visible drawn centerline only",
        "accepted": false
      },
      {
        "id": "E34-W03",
        "pdfDrawingIndex": 18925,
        "group": "L5.A-28 east/storage/HP chain",
        "category": "visible_plan_scale_connection",
        "sourceCommandsPdf": [
          [
            "L",
            1626.54,
            552.06,
            1637.22,
            556.68
          ],
          [
            "L",
            1637.22,
            556.68,
            1648.02,
            561.12
          ],
          [
            "L",
            1648.02,
            561.12,
            1658.94,
            565.26
          ],
          [
            "L",
            1658.94,
            565.26,
            1669.86,
            569.22
          ],
          [
            "L",
            1669.86,
            569.22,
            1680.96,
            572.88
          ],
          [
            "L",
            1680.96,
            572.88,
            1692.06,
            576.36
          ],
          [
            "L",
            1692.06,
            576.36,
            1703.28,
            579.6
          ],
          [
            "L",
            1703.28,
            579.6,
            1714.5,
            582.6
          ],
          [
            "L",
            1714.5,
            582.6,
            1725.84,
            585.36
          ],
          [
            "L",
            1725.84,
            585.36,
            1737.24,
            587.88
          ],
          [
            "L",
            1737.24,
            587.88,
            1748.64,
            590.1
          ],
          [
            "L",
            1748.64,
            590.1,
            1760.16,
            592.14
          ],
          [
            "L",
            1760.16,
            592.14,
            1771.68,
            593.94
          ],
          [
            "L",
            1771.68,
            593.94,
            1783.2,
            595.44
          ],
          [
            "L",
            1783.2,
            595.44,
            1794.78,
            596.76
          ],
          [
            "L",
            1794.78,
            596.76,
            1806.42,
            597.78
          ],
          [
            "L",
            1806.42,
            597.78,
            1818.06,
            598.62
          ],
          [
            "L",
            1818.06,
            598.62,
            1829.7,
            599.16
          ],
          [
            "L",
            1829.7,
            599.16,
            1841.34,
            599.46
          ],
          [
            "L",
            1841.34,
            599.46,
            1852.98,
            599.52
          ],
          [
            "L",
            1852.98,
            599.52,
            1864.62,
            599.34
          ],
          [
            "L",
            1864.62,
            599.34,
            1876.26,
            598.86
          ],
          [
            "L",
            1876.26,
            598.86,
            1887.9,
            598.2
          ],
          [
            "L",
            1887.9,
            598.2,
            1899.54,
            597.24
          ],
          [
            "L",
            1899.54,
            597.24,
            1911.12,
            596.04
          ],
          [
            "L",
            1911.12,
            596.04,
            1922.7,
            594.66
          ],
          [
            "L",
            1922.7,
            594.66,
            1934.22,
            592.98
          ],
          [
            "L",
            1934.22,
            592.98,
            1945.74,
            591.06
          ],
          [
            "L",
            1945.74,
            591.06,
            1957.2,
            588.9
          ]
        ],
        "normalizedPolyline": [
          [
            1204.84,
            408.93
          ],
          [
            1212.76,
            412.36
          ],
          [
            1220.76,
            415.64
          ],
          [
            1228.84,
            418.71
          ],
          [
            1236.93,
            421.64
          ],
          [
            1245.16,
            424.36
          ],
          [
            1253.38,
            426.93
          ],
          [
            1261.69,
            429.33
          ],
          [
            1270.0,
            431.56
          ],
          [
            1278.4,
            433.6
          ],
          [
            1286.84,
            435.47
          ],
          [
            1295.29,
            437.11
          ],
          [
            1303.82,
            438.62
          ],
          [
            1312.36,
            439.96
          ],
          [
            1320.89,
            441.07
          ],
          [
            1329.47,
            442.04
          ],
          [
            1338.09,
            442.8
          ],
          [
            1346.71,
            443.42
          ],
          [
            1355.33,
            443.82
          ],
          [
            1363.96,
            444.04
          ],
          [
            1372.58,
            444.09
          ],
          [
            1381.2,
            443.96
          ],
          [
            1389.82,
            443.6
          ],
          [
            1398.44,
            443.11
          ],
          [
            1407.07,
            442.4
          ],
          [
            1415.64,
            441.51
          ],
          [
            1424.22,
            440.49
          ],
          [
            1432.76,
            439.24
          ],
          [
            1441.29,
            437.82
          ],
          [
            1449.78,
            436.22
          ]
        ],
        "drawnPathLF": 37.5578,
        "cumulativeDrawnPathLF": 99.9989,
        "strokeWidthPdfPt": 0.5399999618530273,
        "dashes": "[] 0",
        "installedRouteLF": null,
        "conductorLF": null,
        "verticalDropLF": null,
        "hiddenRunLF": null,
        "conduitLF": null,
        "fittings": null,
        "measurement": "visible drawn centerline only",
        "accepted": false
      },
      {
        "id": "E34-W04",
        "pdfDrawingIndex": 18926,
        "group": "L5.A-28 east/storage/HP chain",
        "category": "visible_plan_scale_connection",
        "sourceCommandsPdf": [
          [
            "C",
            1957.14,
            588.907,
            1933.212,
            492.518,
            1847.666,
            424.114,
            1748.376,
            421.97
          ]
        ],
        "normalizedPolyline": [
          [
            1449.73,
            436.23
          ],
          [
            1441.02,
            410.48
          ],
          [
            1428.44,
            387.01
          ],
          [
            1412.41,
            366.14
          ],
          [
            1393.35,
            348.22
          ],
          [
            1371.67,
            333.57
          ],
          [
            1347.79,
            322.52
          ],
          [
            1322.13,
            315.41
          ],
          [
            1295.09,
            312.57
          ]
        ],
        "drawnPathLF": 31.9219,
        "cumulativeDrawnPathLF": 131.9208,
        "strokeWidthPdfPt": 0.5399999618530273,
        "dashes": "[] 0",
        "installedRouteLF": null,
        "conductorLF": null,
        "verticalDropLF": null,
        "hiddenRunLF": null,
        "conduitLF": null,
        "fittings": null,
        "measurement": "visible drawn centerline only",
        "accepted": false
      },
      {
        "id": "E34-W05",
        "pdfDrawingIndex": 18927,
        "group": "L5.A-28 east/storage/HP chain",
        "category": "visible_plan_scale_connection",
        "sourceCommandsPdf": [
          [
            "C",
            1748.393,
            421.951,
            1763.136,
            417.226,
            1775.258,
            406.594,
            1781.868,
            392.594
          ],
          [
            "C",
            1781.868,
            392.594,
            1788.48,
            378.595,
            1788.986,
            362.479,
            1783.27,
            348.091
          ]
        ],
        "normalizedPolyline": [
          [
            1295.11,
            312.56
          ],
          [
            1299.11,
            311.04
          ],
          [
            1302.9,
            309.14
          ],
          [
            1306.46,
            306.87
          ],
          [
            1309.76,
            304.26
          ],
          [
            1312.78,
            301.33
          ],
          [
            1315.5,
            298.09
          ],
          [
            1317.88,
            294.58
          ],
          [
            1319.9,
            290.81
          ],
          [
            1321.53,
            286.85
          ],
          [
            1322.73,
            282.78
          ],
          [
            1323.5,
            278.63
          ],
          [
            1323.85,
            274.44
          ],
          [
            1323.76,
            270.23
          ],
          [
            1323.25,
            266.03
          ],
          [
            1322.31,
            261.9
          ],
          [
            1320.94,
            257.85
          ]
        ],
        "drawnPathLF": 10.1768,
        "cumulativeDrawnPathLF": 142.0976,
        "strokeWidthPdfPt": 0.5399999618530273,
        "dashes": "[] 0",
        "installedRouteLF": null,
        "conductorLF": null,
        "verticalDropLF": null,
        "hiddenRunLF": null,
        "conduitLF": null,
        "fittings": null,
        "measurement": "visible drawn centerline only",
        "accepted": false
      },
      {
        "id": "E34-W06",
        "pdfDrawingIndex": 19114,
        "group": "L5.A-26 corridor maintenance receptacle chain",
        "category": "visible_plan_scale_connection",
        "sourceCommandsPdf": [
          [
            "C",
            942.314,
            552.091,
            971.57,
            583.822,
            1017.401,
            594.146,
            1057.435,
            578.023
          ]
        ],
        "normalizedPolyline": [
          [
            698.01,
            408.96
          ],
          [
            706.68,
            417.02
          ],
          [
            716.31,
            423.55
          ],
          [
            726.7,
            428.51
          ],
          [
            737.65,
            431.85
          ],
          [
            748.99,
            433.53
          ],
          [
            760.5,
            433.51
          ],
          [
            772.0,
            431.73
          ],
          [
            783.29,
            428.17
          ]
        ],
        "drawnPathLF": 13.9458,
        "cumulativeDrawnPathLF": 156.0435,
        "strokeWidthPdfPt": 0.5399999618530273,
        "dashes": "[] 0",
        "installedRouteLF": null,
        "conductorLF": null,
        "verticalDropLF": null,
        "hiddenRunLF": null,
        "conduitLF": null,
        "fittings": null,
        "measurement": "visible drawn centerline only",
        "accepted": false
      },
      {
        "id": "E34-W07",
        "pdfDrawingIndex": 19115,
        "group": "L5.A-26 corridor maintenance receptacle chain",
        "category": "visible_plan_scale_connection",
        "sourceCommandsPdf": [
          [
            "C",
            1057.423,
            578.014,
            1128.778,
            611.177,
            1210.279,
            615.086,
            1284.48,
            588.907
          ]
        ],
        "normalizedPolyline": [
          [
            783.28,
            428.16
          ],
          [
            803.42,
            436.35
          ],
          [
            824.13,
            442.51
          ],
          [
            845.23,
            446.62
          ],
          [
            866.58,
            448.68
          ],
          [
            888.03,
            448.67
          ],
          [
            909.43,
            446.6
          ],
          [
            930.63,
            442.46
          ],
          [
            951.47,
            436.23
          ]
        ],
        "drawnPathLF": 25.8997,
        "cumulativeDrawnPathLF": 181.9431,
        "strokeWidthPdfPt": 0.5399999618530273,
        "dashes": "[] 0",
        "installedRouteLF": null,
        "conductorLF": null,
        "verticalDropLF": null,
        "hiddenRunLF": null,
        "conduitLF": null,
        "fittings": null,
        "measurement": "visible drawn centerline only",
        "accepted": false
      }
    ]
  },
  "provenance": [
    {
      "fact": "Room and sheet labels",
      "basis": "selectable PDF text/source-46.txt"
    },
    {
      "fact": "Plan occurrences",
      "basis": "full 10800x7200 raster visual audit; black overlay separated from gray architectural background"
    },
    {
      "fact": "Plan connection LF",
      "basis": "native page-46 black 0.54-pt vector paths, including one 29-segment polyline; PDF drawing indices retained"
    },
    {
      "fact": "Elevator equipment",
      "basis": "visually legible Detail 2 labels and Notes for Elevator; reference only because N.T.S."
    }
  ],
  "highlights": [
    "Scaled plan contains seven corridor receptacles keyed as above-ceiling maintenance outlets.",
    "Panelboards L5.A and L5.B are plotted in Storage 523 and both carry Key Note 1.",
    "Plan circuit callouts are L5.A-38 at C.P, L5.A-26 at the corridor maintenance chain, and L5.A-28 at the storage receptacle.",
    "Fire/smoke-damper J-boxes are required on L5.A-30 with 2#12 in 1/2-inch conduit, but no quantity or plotted locations are provided.",
    "The 182.0 LF rollup is visible plan connection geometry only; Detail 2 is N.T.S. and contributes zero measured LF."
  ],
  "issues": [
    {
      "id": 1,
      "severity": "blocking_guestroom_takeoff",
      "issue": "All 24 guestrooms are architectural backgrounds with no power symbols on E3.4, and this sheet prints no typical-room cross-reference. No multiplication or zero-quantity conclusion is supportable."
    },
    {
      "id": 2,
      "severity": "missing_quantity",
      "issue": "The fire/smoke-damper note requires J-boxes on the fifth floor but prints neither quantity nor locations; L5.A-30 routing is absent."
    },
    {
      "id": 3,
      "severity": "external_design_dependency",
      "issue": "Elevator detail is guideline-only and requires supplier verification of all power, equipment, wiring and conduit requirements."
    },
    {
      "id": 4,
      "severity": "notation_conflict",
      "issue": "Elevator Note 4d specifies a JHL disconnecting means, while visible detail labels show LDU, JHS, JH1 and TSU; no JHL label is visible in the enlarged sample."
    },
    {
      "id": 5,
      "severity": "unresolved_tag",
      "issue": "HP is plotted in Elevator Lobby 500 but HP is not defined on this sheet; its function/rating cannot be certified without another schedule or discipline reference."
    },
    {
      "id": 6,
      "severity": "assembly_ambiguity",
      "issue": "The C.P connection includes adjacent square/circular graphics but only the combined C.P tag is legible; separate accessory identities and quantities are not certifiable."
    },
    {
      "id": 7,
      "severity": "circuit_scope",
      "issue": "L5.A-26 and L5.A-28 identify source circuits, but the sheet does not state conductor count for the visible curved branches; the circuit split at shared-looking endpoints must not be inferred."
    },
    {
      "id": 8,
      "severity": "detail_scale",
      "issue": "All elevator-control graphic lengths are excluded because Detail 2 is explicitly N.T.S."
    },
    {
      "id": 9,
      "severity": "field_verification",
      "issue": "Panel locations, low-voltage quantities/locations, floor outlets, motor controls, and elevator requirements remain subject to owner/architect/contractor/supplier verification."
    },
    {
      "id": 10,
      "severity": "wire_takeoff_limitation",
      "issue": "Drawn curves do not establish installed routing, verticals, hidden lengths, conductor/conduit LF, or fittings; those fields remain null."
    }
  ],
  "independentCrossCheck": {
    "schemaVersion": "1.0",
    "audit": {
      "type": "independent cross-sheet reconciliation",
      "scope": [
        "E3.0",
        "E3.1",
        "E3.2",
        "E3.3",
        "E3.4"
      ],
      "engineeringPdfPages": [
        42,
        43,
        44,
        45,
        46
      ],
      "sourceDirectory": "/workspace/sites/ssx-cover-release/tmp/pdfs/next5-e30-e34",
      "priorEvidenceUsed": [
        "/workspace/sites/ssx-cover-release/dist/e11-full-audit.json",
        "/workspace/sites/ssx-cover-release/dist/e11-requirements.json",
        "/workspace/sites/ssx-cover-release/dist/e12-full-audit.json",
        "/workspace/scratch/e9eeb133d6f5/delegated-e12-e24/crosscheck.json",
        "/workspace/sites/ssx-cover-release/dist/m11-requirements.json",
        "/workspace/sites/ssx-cover-release/dist/m12-requirements.json",
        "/workspace/sites/ssx-cover-release/dist/m21-requirements.json",
        "/workspace/sites/ssx-cover-release/dist/m22-requirements.json",
        "/workspace/sites/ssx-cover-release/dist/m23-requirements.json",
        "/workspace/sites/ssx-cover-release/dist/m24-requirements.json",
        "/workspace/sites/ssx-cover-release/dist/m21-symbols.json",
        "/workspace/sites/ssx-cover-release/dist/m22-symbols.json",
        "/workspace/sites/ssx-cover-release/dist/m23-symbols.json",
        "/workspace/sites/ssx-cover-release/dist/m24-symbols.json"
      ],
      "method": "Read-only comparison of full-resolution 10800x7200 source rasters, selectable source text, and established schedule/plan evidence. Primary per-sheet occurrence audits were not duplicated. Every unresolved identity, quantity, route, or external verification remains fail-closed.",
      "limitations": [
        "Panel schedules and guestroom detail sheets E4.0/E4.1 were not among the supplied reconciliation evidence.",
        "Plumbing, pool, elevator-vendor, and kitchen-vendor schedules were not supplied as governing quantity sources.",
        "No hidden routing, vertical routing, conductor multiplicity, slack, or field routing was inferred.",
        "OCR omits many plotted tags; conclusions were checked against full-resolution raster evidence where needed."
      ]
    },
    "summary": {
      "overallStatus": "HOLD",
      "crossSheetTakeoffCompleteness": "PASS",
      "crossSheetTakeoffCompletenessMeaning": "The reconciliation identifies the full five-sheet sequence, repeated-floor plan boundaries, visible pattern differences, reference-only graphics, and all observed non-certifiable quantity classes. This PASS does not convert unresolved device identities, note-only devices, typical-room scope, or diagrammatic wiring into releasable quantities.",
      "coordinationProcurementStatus": "HOLD",
      "passFindings": 7,
      "holdFindings": 11,
      "releaseReason": "Coordination/procurement remains on HOLD because E3.1-E3.4 omit an explicit guestroom-power detail mapping; six EUH-2 units plotted on mechanical floors 3-5 have no corresponding visible power callouts; the FSD J-box notes provide circuits but no plotted J-box locations; E3.0 points to a fresh-air-fan schedule not present on M1.1; several upper-floor tags remain undefined; and E3.4 elevator Detail 2 contains a JHL/JHS notation conflict and vendor-dependent scope."
    },
    "sheetSequence": [
      {
        "sheet": "E3.0",
        "engineeringPdfPage": 42,
        "title": "POWER FIRST FLOOR PLAN",
        "planDetail": 1,
        "scale": "1/8 inch = 1 foot",
        "status": "PASS"
      },
      {
        "sheet": "E3.1",
        "engineeringPdfPage": 43,
        "title": "POWER SECOND FLOOR PLAN",
        "planDetail": 1,
        "scale": "1/8 inch = 1 foot",
        "status": "PASS"
      },
      {
        "sheet": "E3.2",
        "engineeringPdfPage": 44,
        "title": "POWER THIRD FLOOR PLAN",
        "planDetail": 1,
        "scale": "1/8 inch = 1 foot",
        "status": "PASS"
      },
      {
        "sheet": "E3.3",
        "engineeringPdfPage": 45,
        "title": "POWER FOURTH FLOOR PLAN",
        "planDetail": 1,
        "scale": "1/8 inch = 1 foot",
        "status": "PASS"
      },
      {
        "sheet": "E3.4",
        "engineeringPdfPage": 46,
        "title": "POWER FIFTH FLOOR PLAN",
        "planDetail": 1,
        "scale": "1/8 inch = 1 foot",
        "status": "PASS",
        "additionalDetail": {
          "number": 2,
          "title": "ENLARGED ELEVATOR CONTROL (LOCATED ON A TOP OF ELEVATOR SHAFT)",
          "scale": "N.T.S.",
          "quantityDisposition": "reference only; no length or installed quantity inferred"
        }
      }
    ],
    "scaleRules": {
      "planScale": {
        "printed": "1/8 inch = 1 foot",
        "pdfPointsPerFoot": 9.0,
        "sourceRasterPixelsPerFootAt300Dpi": 37.5,
        "status": "PASS for visible plan-scale geometry only",
        "qualification": "The mathematical conversion is verified from print scale and render resolution, but no independent written dimension was found and the drawn curves do not establish installed routing."
      },
      "ntsRule": {
        "appliesTo": "E3.4 Detail 2",
        "rule": "Do not measure or scale any elevator-detail linework.",
        "status": "PASS"
      }
    },
    "floorReconciliation": {
      "guestroomProgram": {
        "E3.0": 11,
        "E3.1": 24,
        "E3.2": 24,
        "E3.3": 24,
        "E3.4": 24,
        "upperFloorSubtotal": 96,
        "fiveFloorTotal": 107,
        "status": "PASS against the established electrical/mechanical 107-room chain",
        "inheritedQualification": "The prior E1.1 audit retains a separate HOLD against an earlier architectural count of 85; this batch reinforces 107 but does not resolve that architectural conflict."
      },
      "upperFloors": [
        {
          "sheet": "E3.1",
          "floor": 2,
          "panels": [
            "L2.A",
            "L2.B"
          ],
          "visiblePlanCircuitCallouts": [
            "L2.A-26",
            "L2.A-28",
            "L2.B-26,28",
            "L2.B-30,32"
          ],
          "fireSmokeDamperNoteCircuit": "L2.A-30",
          "distinctConditions": [
            "Two visible stair EUH power callouts, one at each stair.",
            "No C.P callout and no Key Note 2 maintenance-receptacle reference.",
            "Room 226 is QUEEN QUEEN ACCESSIBLE; connecting king studio occurs at 205."
          ]
        },
        {
          "sheet": "E3.2",
          "floor": 3,
          "panels": [
            "L3.A",
            "L3.B"
          ],
          "visiblePlanCircuitCallouts": [
            "L3.A-26",
            "L3.A-28",
            "L3.A-34"
          ],
          "fireSmokeDamperNoteCircuit": "L3.A-30",
          "distinctConditions": [
            "C.P assembly and one Key Note 2 reference for an above-ceiling maintenance receptacle are present.",
            "No visible stair EUH power callout.",
            "Room 326 is KING ACCESSIBLE; connecting king studio occurs at 305."
          ]
        },
        {
          "sheet": "E3.3",
          "floor": 4,
          "panels": [
            "L4.A",
            "L4.B"
          ],
          "visiblePlanCircuitCallouts": [
            "L4.A-26",
            "L4.A-28"
          ],
          "fireSmokeDamperNoteCircuit": "L4.A-30",
          "distinctConditions": [
            "No C.P callout and no Key Note 2 maintenance-receptacle reference.",
            "No visible stair EUH power callout.",
            "Six repeated corridor duplex-family graphics are present but must not be classified as FSD J-boxes.",
            "Room 426 is KING ACCESSIBLE; connecting king studio occurs at 405."
          ]
        },
        {
          "sheet": "E3.4",
          "floor": 5,
          "panels": [
            "L5.A",
            "L5.B"
          ],
          "visiblePlanCircuitCallouts": [
            "L5.A-26",
            "L5.A-28",
            "L5.A-38"
          ],
          "fireSmokeDamperNoteCircuit": "L5.A-30",
          "distinctConditions": [
            "C.P assembly and one Key Note 2 reference for an above-ceiling maintenance receptacle are present.",
            "No visible stair EUH power callout.",
            "E3.4 alone contains the N.T.S. elevator-control detail.",
            "Room 526 is KING ACCESSIBLE; connecting king studios occur at 505, 512, and 514."
          ]
        }
      ],
      "repeatedPatternRule": "Do not apply a four-floor multiplier. Room types and circuit callouts vary; C.P/maintenance scope occurs only on E3.2 and E3.4; stair EUH power is visible only on E3.1; E3.4 alone carries elevator Detail 2."
    },
    "findings": [
      {
        "id": "PASS-01",
        "status": "PASS",
        "topic": "Power-plan sheet order, titles, and scale",
        "sheets": [
          "E3.0",
          "E3.1",
          "E3.2",
          "E3.3",
          "E3.4"
        ],
        "evidence": [
          "Engineering PDF pages 42-46 progress first through fifth floor without a gap.",
          "Each Detail 1 plan prints 1/8 inch = 1 foot.",
          "E3.4 Detail 2 is explicitly N.T.S."
        ],
        "conclusion": "The batch sequence and scale labels are internally consistent."
      },
      {
        "id": "PASS-02",
        "status": "PASS",
        "topic": "Electrical/mechanical guestroom count chain",
        "sheets": [
          "E3.0",
          "E3.1",
          "E3.2",
          "E3.3",
          "E3.4",
          "E2.0",
          "E2.1",
          "E2.2",
          "E2.3",
          "E2.4"
        ],
        "evidence": [
          "E3.0 contains 11 guestrooms.",
          "Each of E3.1-E3.4 contains 24 guestrooms, producing 96 upper-floor rooms.",
          "11 + 96 = 107, matching the established five-floor electrical/mechanical room chain."
        ],
        "conclusion": "The power-plan room labels reconcile to 107 guestrooms, subject to the inherited architectural-count HOLD."
      },
      {
        "id": "PASS-03",
        "status": "PASS",
        "topic": "Upper-floor panel and repeated-circuit progression",
        "sheets": [
          "E3.1",
          "E3.2",
          "E3.3",
          "E3.4"
        ],
        "evidence": [
          "Local panel pairs progress L2.A/L2.B, L3.A/L3.B, L4.A/L4.B, and L5.A/L5.B.",
          "The repeated corridor and storage/lobby callouts progress by local floor panel, including L2.A-26/-28 through L5.A-26/-28.",
          "C.P branch callouts are actual variations: L3.A-34 on E3.2 and L5.A-38 on E3.4 only."
        ],
        "conclusion": "The visible plan callouts use the correct local-floor panel prefixes and the nonrepeating variations are identifiable."
      },
      {
        "id": "PASS-04",
        "status": "PASS",
        "topic": "Fire/smoke-damper note circuit progression",
        "sheets": [
          "E3.0",
          "E3.1",
          "E3.2",
          "E3.3",
          "E3.4"
        ],
        "evidence": [
          "E3.0 assigns Level 1 FSD J-boxes to L1.D-20.",
          "E3.1-E3.4 assign floors 2-5 to L2.A-30, L3.A-30, L4.A-30, and L5.A-30 respectively.",
          "Each upper-floor note states 2#12 in 1/2-inch conduit."
        ],
        "conclusion": "The textual circuit progression is internally orderly; device locations and quantities remain separately held."
      },
      {
        "id": "PASS-05",
        "status": "PASS",
        "topic": "Mechanical equipment schedule families",
        "sheets": [
          "E3.0",
          "M1.1",
          "M1.2"
        ],
        "evidence": [
          "M1.1 defines AHU-1.1 through AHU-1.6, FCU-1/FCU-2 with CU-1/CU-2, EUH-1/EUH-2, PTAC-1/PTAC-2, and EF-1 through EF-13 including EF-1.1.",
          "The visible E3.0 AHU/ACCU and FCU/CU equipment families are schedule-addressable by the established M1.1 evidence.",
          "M1.2 separately defines DOAS-1 and DOAS-2 as roof equipment; absence from the first-floor power plan is not a zero-count conclusion."
        ],
        "conclusion": "The principal HVAC tag families have schedule destinations; individual electrical connections remain occurrence-controlled."
      },
      {
        "id": "PASS-06",
        "status": "PASS",
        "topic": "E1.1 symbol and special-outlet definition coverage",
        "sheets": [
          "E1.1",
          "E3.0",
          "E3.1",
          "E3.2",
          "E3.3",
          "E3.4"
        ],
        "evidence": [
          "E1.1 defines duplex/GFI receptacles, junction box, motor, panelboard, disconnect, voice/data, and floor voice/data symbol families.",
          "E1.1 special outlet A is the PTAC NEMA 6-20 outlet; B is the GFCI/disposer assembly; C is the fitness NEMA 5-30 floor outlet; D is the general NEMA 5-20 floor outlet.",
          "The E1.1 special-outlet schedule contains definitions but no installed quantities."
        ],
        "conclusion": "The general symbol families and special-outlet types are defined; counts must come from applicable plan occurrences or mapped guestroom details."
      },
      {
        "id": "PASS-07",
        "status": "PASS",
        "topic": "Elevator-detail duplicate control",
        "sheets": [
          "E3.4",
          "E2.0",
          "E1.2"
        ],
        "evidence": [
          "E3.4 Detail 2 shows two sample callouts marked 001, one at each elevator shaft graphic.",
          "E1.2 defines fixture type 001, and the established E2.0 evidence already accounts for two installed elevator-shaft 001 fixtures.",
          "E3.4 Detail 2 is N.T.S. and explicitly guideline-only."
        ],
        "conclusion": "The two Detail-2 001 samples are corroborating references and contribute zero additional fixtures to project totals."
      },
      {
        "id": "HOLD-01",
        "status": "HOLD",
        "topic": "Missing typical-guestroom power mapping",
        "sheets": [
          "E3.0",
          "E3.1",
          "E3.2",
          "E3.3",
          "E3.4",
          "E4.0",
          "E4.1"
        ],
        "evidence": [
          "E3.1-E3.4 contain 96 guestroom labels but plot no complete in-room receptacle/PTAC/special-outlet layouts.",
          "Unlike the established E2.1-E2.4 lighting notes, the four upper-floor power sheets print no explicit E4.0/E4.1 guestroom-detail reference or room-type mapping.",
          "E1.1 special outlet A defines the PTAC outlet but does not establish occurrences."
        ],
        "conclusion": "A complete guestroom power-device takeoff cannot be released from E3.0-E3.4, and blank upper-floor rooms are not certified zero-device rooms.",
        "requiredResolution": "Issue or identify the governing guestroom power-detail sheet and a room-type-to-detail matrix, then reconcile all 107 rooms including accessible and one-bedroom/two-PTAC variants."
      },
      {
        "id": "HOLD-02",
        "status": "HOLD",
        "topic": "Missing stair EUH-2 power on floors 3-5",
        "sheets": [
          "E3.1",
          "E3.2",
          "E3.3",
          "E3.4",
          "M1.1",
          "M2.1",
          "M2.2",
          "M2.3",
          "M2.4"
        ],
        "evidence": [
          "M1.1 defines EUH-2 for stairwells at 208/1/60, 5,000 W, 24 A.",
          "Each of M2.1-M2.4 has two certified EUH-2 plan occurrences, one at each stair, for eight upper-floor units.",
          "E3.1 visibly powers two stair EUH devices at L2.B-26,28 and L2.B-30,32.",
          "No corresponding stair EUH power callout is visible on E3.2, E3.3, or E3.4."
        ],
        "conclusion": "Six mechanically plotted EUH-2 units on floors 3-5 lack visible electrical power assignments in this batch. The electrical label EUH also omits the mechanical '-2' suffix.",
        "requiredResolution": "Add or identify power circuits/disconnect requirements for the two EUH-2 units on each of floors 3, 4, and 5 and confirm that E3.1's EUH labels correspond to EUH-2."
      },
      {
        "id": "HOLD-03",
        "status": "HOLD",
        "topic": "FSD J-box location and symbol conflict",
        "sheets": [
          "E1.1",
          "E3.1",
          "E3.2",
          "E3.3",
          "E3.4",
          "M2.1",
          "M2.2",
          "M2.3",
          "M2.4"
        ],
        "evidence": [
          "Each upper-floor FSD note requires J-boxes on local circuit A-30 but prints no quantity.",
          "The A-30 routes and J-box locations are not visibly plotted on E3.1-E3.4.",
          "Six corridor duplex-family graphics recur at the same normalized locations on the upper-floor plans; they do not match the E1.1 junction-box symbol.",
          "Mechanical M2.1 contains six FD/FSD occurrences, while M2.2-M2.4 contain five each; no electrical note maps those mechanical occurrences one-for-one to plotted J-boxes."
        ],
        "conclusion": "The recurring corridor receptacle graphics must not be reclassified as FSD J-boxes, including on E3.3. FSD electrical quantities and locations are not certifiable from the note alone.",
        "requiredResolution": "Plot or schedule every FSD J-box and map it to the mechanical damper register and the applicable A-30 circuit. Correct any per-sheet audit that currently labels the six duplex-family graphics as FSD connection points."
      },
      {
        "id": "HOLD-04",
        "status": "HOLD",
        "topic": "Undefined upper-floor C.P and HP tags",
        "sheets": [
          "E1.1",
          "E3.1",
          "E3.2",
          "E3.3",
          "E3.4"
        ],
        "evidence": [
          "HP is visibly repeated at the elevator-lobby/storage end of the upper-floor branch but is not expanded on E3.1-E3.4 or in the supplied E1.1 symbol definitions.",
          "C.P is visibly present only on E3.2 and E3.4 and is not expanded by the supplied legend.",
          "Key Note 2 on E3.2 and E3.4 identifies a receptacle outlet above the ceiling for maintenance but does not define C.P or the served equipment."
        ],
        "conclusion": "Occurrence counting can remain complete while device identity, rating, mounting, and served equipment are unresolved.",
        "requiredResolution": "Define HP and C.P and identify the applicable circuit/load and accessory assembly for each occurrence."
      },
      {
        "id": "HOLD-05",
        "status": "HOLD",
        "topic": "Upper-floor panel schedule and breaker confirmation",
        "sheets": [
          "E3.1",
          "E3.2",
          "E3.3",
          "E3.4"
        ],
        "evidence": [
          "Visible local-floor callouts include A-26, A-28, floor-specific C.P circuits A-34/A-38, two E3.1 B-panel EUH circuit pairs, and note-only A-30 FSD circuits.",
          "The governing panel-schedule rows were not supplied in the current evidence set.",
          "Key Note 1 makes panel locations field-verification items."
        ],
        "conclusion": "Circuit labels are legible, but breaker description, poles, ampacity, connected load, spare conflicts, and final panel locations are not certified here.",
        "requiredResolution": "Reconcile every visible and note-only circuit against the governing panel schedules and equipment nameplates."
      },
      {
        "id": "HOLD-06",
        "status": "HOLD",
        "topic": "Elevator-control detail notation and vendor scope",
        "sheets": [
          "E3.4"
        ],
        "evidence": [
          "Detail 2 states it is guideline-only and requires elevator-supplier verification before installation.",
          "The detail repeats LDU, JHS, JH1, and TSU graphics for two elevator shafts and shows EP-9/EP-7 at one shaft and EP-3/EP-1 at the other.",
          "Elevator Note 4d specifies disconnecting means JHL for auxiliary power and lighting, but no JHL tag is visible in the detail; the visible similar tag is JHS."
        ],
        "conclusion": "The JHL/JHS notation is a broken or ambiguous reference, and the detail cannot serve as final procurement quantity or wiring-route evidence.",
        "requiredResolution": "Correct the JHL/JHS designation, identify each disconnect/controller function and source circuit, and obtain an elevator-vendor power/controls schedule for both elevators."
      },
      {
        "id": "HOLD-07",
        "status": "HOLD",
        "topic": "Broken fresh-air-fan schedule reference",
        "sheets": [
          "E3.0",
          "M1.1",
          "M1.2"
        ],
        "evidence": [
          "E3.0 General Note 17 directs exhaust/fresh-air fan controls to schedules on M1.1.",
          "M1.1 contains an Exhaust Fan Schedule and the established M1.1 requirements define EF-1 through EF-13 including EF-1.1.",
          "No distinct fresh-air-fan schedule or FAF tag was found in the supplied M1.1 evidence; M1.2 defines DOAS-1/DOAS-2 instead."
        ],
        "conclusion": "The exhaust-fan portion resolves to M1.1, but the fresh-air-fan portion has no defined destination in the supplied schedules.",
        "requiredResolution": "Clarify whether 'fresh air fan' means a DOAS component, another scheduled fan, or a missing schedule, and issue the applicable control requirements."
      },
      {
        "id": "HOLD-08",
        "status": "HOLD",
        "topic": "E3.0 plumbing, pool, and motor-control dependencies",
        "sheets": [
          "E3.0"
        ],
        "evidence": [
          "Keyed Note 1 identifies a sump pump in a pit; Note 13 a pool lift-station J-box; Note 15 a motorized-damper J-box; and Note 16 a 240 V, 3-pole, 60 A fused NEMA 3R disconnect for the booster-pump control panel.",
          "General Note 16 requires verification of HVAC/plumbing power and control accessories.",
          "The pool notes state that the pool is separately permitted and that the pool contractor installs pool electrical devices/equipment and associated wiring."
        ],
        "conclusion": "These notes establish coordination obligations, not final equipment quantities or a complete electrical bill of materials.",
        "requiredResolution": "Reconcile sump, booster, fire-pump, pool, and motorized-damper power/control requirements to the governing plumbing, fire-pump, pool, and mechanical submittals without double counting contractor-furnished scope."
      },
      {
        "id": "HOLD-09",
        "status": "HOLD",
        "topic": "E3.0 dry-storage and convenience-outlet procurement scope",
        "sheets": [
          "E3.0"
        ],
        "evidence": [
          "The dry-storage electrical schedule lists equipment rows with QTY 1 and includes operator-furnished, vendor-furnished, optional, future, and NOT USED qualifications.",
          "Item 20 is optional, Item 25 is future, Item 31 is NOT USED, and several rows require vendor/owner verification.",
          "Convenience outlet rows 900 and 901 define mounting variants at +18 inches and +48 inches; the schedule rows do not substitute for plan occurrence counts."
        ],
        "conclusion": "The scheduled definitions are not safely additive to plan bubbles, and optional/future/vendor-furnished status must be resolved before procurement.",
        "requiredResolution": "Create a procurement responsibility matrix, confirm accepted alternates/options/future provisions, and count each accepted equipment/outlet occurrence once."
      },
      {
        "id": "HOLD-10",
        "status": "HOLD",
        "topic": "Installed wiring and voltage-drop completeness",
        "sheets": [
          "E3.0",
          "E3.1",
          "E3.2",
          "E3.3",
          "E3.4"
        ],
        "evidence": [
          "The five sheets require a 3 percent feeder maximum and 5 percent combined feeder-plus-branch maximum for applicable long runs.",
          "Visible curves are diagrammatic plan connections and omit verticals, hidden routing, conductor allocation, conduit fill, slack, and field routing.",
          "E3.4 Detail 2 is N.T.S. and cannot support any length."
        ],
        "conclusion": "Visible drawn-path measurements may be audited as graphics, but installed route LF, conductor LF, conduit LF, and combined voltage-drop compliance are not certified.",
        "requiredResolution": "Establish field-installable routes and conductor assemblies, include vertical and hidden segments, and perform the required farthest-load combined voltage-drop calculations."
      },
      {
        "id": "HOLD-11",
        "status": "HOLD",
        "topic": "Inherited 107-versus-85 room-count conflict",
        "sheets": [
          "E3.0",
          "E3.1",
          "E3.2",
          "E3.3",
          "E3.4",
          "E1.0",
          "M2.0",
          "M2.1",
          "M2.2",
          "M2.3",
          "M2.4",
          "M6.0"
        ],
        "evidence": [
          "The current power plans and prior electrical/mechanical evidence reconcile to 107 guestrooms.",
          "The prior E1.1 full audit records a conflicting earlier architectural count of 85."
        ],
        "conclusion": "This batch corroborates the 107-room engineering basis but cannot retire the architectural discrepancy.",
        "requiredResolution": "Issue a coordinated room matrix and identify the superseding architectural count before final guestroom procurement totals are released."
      }
    ],
    "referenceAndQuantityRules": [
      {
        "source": "E1.1 legend and special outlet schedule",
        "rule": "Symbols and A-D outlet rows are definitions only; they contribute zero installed quantity without plan or mapped-detail occurrences."
      },
      {
        "source": "E3.0 keyed notes and general notes",
        "rule": "A keyed-note bubble is a reference occurrence, not an installed device. Count the associated plotted device once where one exists."
      },
      {
        "source": "E3.0 dry-storage schedule",
        "rule": "A QTY-1 equipment schedule row and its matching plan item bubble are two representations of the same equipment, not two units. Optional, future, vendor-furnished, and NOT USED rows require separate disposition."
      },
      {
        "source": "E3.0 convenience outlet schedule",
        "rule": "Rows 900 and 901 define two mounting conditions; installed quantity comes from plan occurrences, not from the existence of two rows."
      },
      {
        "source": "E3.1-E3.4 room labels",
        "rule": "Room labels establish room counts and types only. They do not create guestroom receptacle, PTAC outlet, data, TV, or control-device quantities."
      },
      {
        "source": "E3.1-E3.4 FSD notes",
        "rule": "One note occurrence and one circuit reference do not equal one J-box. No FSD J-box quantity is accepted without mapped plan/device evidence."
      },
      {
        "source": "M1.1/M1.2 schedules and M2.0-M2.4 plan tags",
        "rule": "Mechanical equipment and its electrical connection are coordinated representations of one physical unit. Do not add electrical connection symbols to mechanical equipment totals."
      },
      {
        "source": "E3.4 Detail 2",
        "rule": "All LDU/JHS/JH1/TSU/EP/001 graphics are N.T.S. reference samples. They do not create additional installed quantities beyond governing plan and vendor schedules."
      },
      {
        "source": "E3.4 Detail 2 fixture tag 001",
        "rule": "The two 001 samples corroborate the two E2.0 elevator-shaft fixtures already counted; additive quantity is zero."
      },
      {
        "source": "Visible plan wiring curves",
        "rule": "A curve may support a drawn-path graphic trace only. It does not certify installed route, conductor, conduit, vertical, hidden, or slack quantities."
      }
    ],
    "releaseChecks": [
      {
        "status": "PASS",
        "item": "E3.0-E3.4 page order, titles, and Detail-1 scales verified."
      },
      {
        "status": "PASS",
        "item": "E3.4 elevator Detail 2 identified as N.T.S. and excluded from length takeoff."
      },
      {
        "status": "PASS",
        "item": "Five-floor power-plan room count reconciles to the established 107-room electrical/mechanical chain."
      },
      {
        "status": "PASS",
        "item": "Upper-floor local panel prefixes and actual circuit variations documented without a blind multiplier."
      },
      {
        "status": "PASS",
        "item": "E1.1 special-outlet definitions and reference-only quantity treatment carried forward."
      },
      {
        "status": "PASS",
        "item": "E3.4 Detail-2 001 samples prevented from duplicating the two established elevator-shaft fixture occurrences."
      },
      {
        "status": "HOLD",
        "item": "Identify an explicit typical-guestroom power detail and room-type mapping for all 107 rooms."
      },
      {
        "status": "HOLD",
        "item": "Provide power circuits for the six M2.2-M2.4 EUH-2 units not visibly served on E3.2-E3.4."
      },
      {
        "status": "HOLD",
        "item": "Plot and map every FSD J-box to mechanical damper occurrences and local A-30 circuits; do not classify corridor duplex graphics as J-boxes."
      },
      {
        "status": "HOLD",
        "item": "Define HP and C.P and resolve their equipment/circuit/accessory requirements."
      },
      {
        "status": "HOLD",
        "item": "Verify every E3.1-E3.4 plan and note-only circuit against governing panel schedules."
      },
      {
        "status": "HOLD",
        "item": "Correct E3.4 elevator JHL/JHS notation and obtain vendor-approved power/control requirements for both elevators."
      },
      {
        "status": "HOLD",
        "item": "Resolve E3.0's missing fresh-air-fan schedule destination."
      },
      {
        "status": "HOLD",
        "item": "Reconcile E3.0 sump, booster, fire-pump, pool, and motorized-damper electrical scope to governing discipline/vendor documents."
      },
      {
        "status": "HOLD",
        "item": "Resolve optional/future/vendor-furnished kitchen equipment and count schedule/plan representations only once."
      },
      {
        "status": "HOLD",
        "item": "Develop installed routing and combined voltage-drop calculations; visible plan curves are not installed LF."
      },
      {
        "status": "HOLD",
        "item": "Retire the inherited 107-versus-85 architectural room-count conflict before final guestroom procurement release."
      }
    ]
  }
}
