E3.0 POWER FIRST FLOOR PLAN Engineering PDF page 42 Issued November 22, 2024 COMPLETE SOURCE TEXT LAYER { "schemaVersion": "1.0", "sheet": { "number": "E3.0", "title": "POWER FIRST FLOOR PLAN", "engineeringPdfPage": 42, "sourceImage": "/workspace/sites/ssx-cover-release/tmp/pdfs/next5-e30-e34/source-42.png", "sourceText": "/workspace/sites/ssx-cover-release/tmp/pdfs/next5-e30-e34/source-42.txt", "sourcePixels": [ 10800, 7200 ], "normalizedCanvas": [ 1920, 1280 ], "sourceToNormalizedDivisor": 5.625, "project": "HOME 2 SUITES", "location": "BRADENTON, FL.", "projectNumber": "210729", "drawnBy": "PL", "checkedBy": "DV", "sealDate": "NOV. 22, 2024", "revisions": [] }, "scaleEvidence": { "detail": "1/E3.0", "printed": "SCALE: 1/8\"=1'-0\"", "pdfPointsPerFoot": 9, "sourcePixelsPerFoot": 37.5, "normalizedUnitsPerFoot": 6.6666667, "marker": [ 1307, 749 ], "measurementPolicy": "Only visible black centerline plan-connection geometry is measured. Installed route, conductor, conduit, vertical rise/drop, hidden routing, slack and unshown fittings are null." }, "regions": [ { "id": "scaled-first-floor-plan", "bbox": [ 105, 90, 1400, 780 ], "scale": "1/8 inch = 1 foot" }, { "id": "keyed-notes", "bbox": [ 1434, 84, 1724, 614 ], "scale": "NTS" }, { "id": "fire-smoke-damper-note", "bbox": [ 1434, 634, 1724, 681 ], "scale": "NTS" }, { "id": "pool-notes", "bbox": [ 1434, 695, 1724, 838 ], "scale": "NTS" }, { "id": "general-notes", "bbox": [ 108, 784, 622, 1198 ], "scale": "NTS" }, { "id": "dry-storage-electrical-schedule", "bbox": [ 650, 795, 1406, 1014 ], "scale": "NTS" }, { "id": "dry-storage-general-notes", "bbox": [ 650, 1016, 1248, 1092 ], "scale": "NTS" }, { "id": "convenience-outlet-requirements", "bbox": [ 650, 1107, 1205, 1192 ], "scale": "NTS" }, { "id": "title-block", "bbox": [ 1768, 55, 1902, 1248 ], "scale": "NTS" } ], "roomAreaRegister": [ [ "STAIR 2", "001" ], [ "STAIR 1", "002" ], [ "ELEVATOR", "003" ], [ "POOL EQUIPMENT", "004" ], [ "UNI SEX ADA RESTROOM", "005" ], [ "KING STUDIO", "101" ], [ "KING ONE BEDROOM", "102" ], [ "KING STUDIO", "103" ], [ "KING STUDIO", "104" ], [ "CONNECTING KING STUDIO", "105" ], [ "KING STUDIO", "106" ], [ "ACCESSIBLE BEDROOM KING ONE", "107" ], [ "KING STUDIO", "108" ], [ "MECHANICAL ROOM", "109" ], [ "KING STUDIO", "110" ], [ "ENGINEER", "111" ], [ "CONNECTING KING STUDIO", "112" ], [ "ELECTRICAL", "113" ], [ "CONNECTING KING STUDIO", "114" ], [ "PBX", "115" ], [ "WOMENS", "116" ], [ "EMPLOYEE BREAKROOM", "117" ], [ "MENS", "118" ], [ "FOOD PREP", "119" ], [ "STORAGE", "120" ], [ "PROPOSED SPRINKLER ROOM", "121" ], [ "SALES", "122" ], [ "BREAKFAST", "123" ], [ "LOBBY", "124" ], [ "DRYER ROOM", "125" ], [ "VESTIBULE", "126" ], [ "LAUNDRY", "127" ], [ "MECHANICAL", "128" ], [ "MARKET", "129" ], [ "FITNESS ROOM", "130" ], [ "LAUNDRY DISCHARGE", "131" ], [ "GUEST LAUNDRY", "132" ], [ "MANAGER'S OFFICE", "133" ], [ "MECHANICAL", "134" ], [ "TV LOUNGE", "135" ], [ "SERVERY", "136" ], [ "WORK STATIONS", "137" ] ], "groups": [ { "id": "wall-duplex-receptacle-glyphs", "count": 53, "unit": "EA", "cert": "outline duplex wall symbol; vector signature plus raster fill classification", "markers": [ [ 1283.1, 373.4, "plan occurrence" ], [ 1317.2, 373.4, "plan occurrence" ], [ 1333.1, 326.4, "plan occurrence" ], [ 1283.1, 311.8, "plan occurrence" ], [ 1236.8, 311.8, "plan occurrence" ], [ 1295.6, 442.2, "plan occurrence" ], [ 1279.4, 442.2, "plan occurrence" ], [ 1263.4, 442.2, "plan occurrence" ], [ 1247.2, 442.2, "plan occurrence" ], [ 1245.8, 453.2, "plan occurrence" ], [ 1253.8, 601.5, "plan occurrence" ], [ 1148.4, 543.6, "plan occurrence" ], [ 1221.5, 439.2, "plan occurrence" ], [ 1137.4, 526.5, "plan occurrence" ], [ 1076.7, 568.9, "plan occurrence" ], [ 895.1, 567.8, "plan occurrence" ], [ 895.1, 392.9, "plan occurrence" ], [ 895.1, 466.7, "plan occurrence" ], [ 1081.3, 298.1, "plan occurrence" ], [ 1106.9, 298.1, "plan occurrence" ], [ 948.2, 292.4, "plan occurrence" ], [ 948.2, 315.4, "plan occurrence" ], [ 883.8, 589.9, "plan occurrence" ], [ 839.3, 562.6, "plan occurrence" ], [ 837.4, 227.8, "plan occurrence" ], [ 911.8, 227.8, "plan occurrence" ], [ 981.4, 266.2, "plan occurrence" ], [ 1053.4, 269.4, "plan occurrence" ], [ 1137.7, 269.4, "plan occurrence" ], [ 1157.3, 269.4, "plan occurrence" ], [ 1114.4, 214.0, "plan occurrence" ], [ 724.0, 154.7, "plan occurrence" ], [ 724.0, 165.7, "plan occurrence" ], [ 731.4, 217.6, "plan occurrence" ], [ 715.0, 232.0, "plan occurrence" ], [ 642.1, 243.5, "plan occurrence" ], [ 595.8, 304.3, "plan occurrence" ], [ 630.4, 276.3, "plan occurrence" ], [ 557.0, 319.9, "plan occurrence" ], [ 831.8, 399.5, "plan occurrence" ], [ 811.0, 557.3, "plan occurrence" ], [ 720.7, 364.9, "plan occurrence" ], [ 467.4, 337.2, "plan occurrence" ], [ 228.2, 364.9, "plan occurrence" ], [ 899.0, 363.5, "plan occurrence" ], [ 1173.6, 239.6, "plan occurrence" ], [ 1221.5, 381.1, "plan occurrence" ], [ 895.1, 537.4, "plan occurrence" ], [ 724.5, 714.6, "plan occurrence" ], [ 644.5, 328.2, "plan occurrence" ], [ 675.1, 328.2, "plan occurrence" ], [ 793.8, 328.2, "plan occurrence" ], [ 799.3, 274.2, "plan occurrence" ] ] }, { "id": "wall-quad-receptacle-glyphs", "count": 21, "unit": "EA", "method": "outline quad wall symbol; vector signature plus raster cross-fill classification", "markers": [ [ 1326.1, 311.8, "plan occurrence" ], [ 1048.2, 581.9, "plan occurrence" ], [ 1048.2, 587.4, "plan occurrence" ], [ 1058.5, 377.5, "plan occurrence" ], [ 974.0, 377.5, "plan occurrence" ], [ 1086.5, 306.9, "plan occurrence" ], [ 1081.3, 306.9, "plan occurrence" ], [ 1112.1, 306.9, "plan occurrence" ], [ 1106.9, 306.9, "plan occurrence" ], [ 883.8, 584.3, "plan occurrence" ], [ 1004.4, 266.2, "plan occurrence" ], [ 1067.0, 269.4, "plan occurrence" ], [ 684.6, 270.5, "plan occurrence" ], [ 697.9, 270.5, "plan occurrence" ], [ 695.4, 227.8, "plan occurrence" ], [ 701.2, 227.8, "plan occurrence" ], [ 715.0, 237.8, "plan occurrence" ], [ 664.1, 227.8, "plan occurrence" ], [ 669.9, 227.8, "plan occurrence" ], [ 557.0, 276.7, "plan occurrence" ], [ 956.6, 266.2, "plan occurrence" ] ] }, { "id": "wall-gfi-duplex-receptacle-glyphs", "count": 70, "unit": "EA", "method": "filled GFI duplex wall symbol; vector signature plus raster fill classification", "markers": [ [ 1233.2, 199.1, "plan occurrence" ], [ 1233.2, 292.6, "plan occurrence" ], [ 1254.1, 384.4, "plan occurrence" ], [ 1254.1, 392.2, "plan occurrence" ], [ 1311.0, 429.4, "plan occurrence" ], [ 1069.3, 575.6, "plan occurrence" ], [ 1044.8, 603.1, "plan occurrence" ], [ 895.1, 530.0, "plan occurrence" ], [ 895.1, 512.2, "plan occurrence" ], [ 895.1, 492.2, "plan occurrence" ], [ 895.1, 486.7, "plan occurrence" ], [ 895.1, 450.3, "plan occurrence" ], [ 1002.0, 275.2, "plan occurrence" ], [ 978.6, 275.2, "plan occurrence" ], [ 839.3, 402.7, "plan occurrence" ], [ 839.3, 451.6, "plan occurrence" ], [ 1054.2, 218.7, "plan occurrence" ], [ 1009.1, 218.7, "plan occurrence" ], [ 1052.8, 141.2, "plan occurrence" ], [ 934.4, 141.2, "plan occurrence" ], [ 942.5, 218.7, "plan occurrence" ], [ 869.1, 218.7, "plan occurrence" ], [ 748.3, 217.6, "plan occurrence" ], [ 754.8, 217.6, "plan occurrence" ], [ 670.4, 218.7, "plan occurrence" ], [ 678.5, 141.2, "plan occurrence" ], [ 642.1, 172.5, "plan occurrence" ], [ 1343.8, 318.7, "plan occurrence" ], [ 1173.7, 143.0, "plan occurrence" ], [ 145.8, 364.0, "plan occurrence" ], [ 781.8, 679.7, "plan occurrence" ], [ 720.7, 572.2, "plan occurrence" ], [ 298.5, 572.2, "plan occurrence" ], [ 315.0, 725.0, "plan occurrence" ], [ 212.5, 572.2, "plan occurrence" ], [ 227.5, 704.5, "plan occurrence" ], [ 791.8, 618.2, "plan occurrence" ], [ 255.8, 725.4, "plan occurrence" ], [ 255.8, 683.7, "plan occurrence" ], [ 1127.3, 203.3, "plan occurrence" ], [ 839.3, 506.2, "plan occurrence" ], [ 630.4, 190.2, "plan occurrence" ], [ 557.8, 150.9, "plan occurrence" ], [ 595.0, 141.2, "plan occurrence" ], [ 595.5, 242.7, "plan occurrence" ], [ 595.0, 130.4, "plan occurrence" ], [ 736.3, 130.4, "plan occurrence" ], [ 1232.7, 165.9, "plan occurrence" ], [ 557.8, 170.9, "plan occurrence" ], [ 557.0, 190.9, "plan occurrence" ], [ 557.0, 210.9, "plan occurrence" ], [ 557.0, 230.9, "plan occurrence" ], [ 771.8, 265.2, "plan occurrence" ], [ 707.8, 328.2, "plan occurrence" ], [ 722.0, 328.2, "plan occurrence" ], [ 735.2, 328.2, "plan occurrence" ], [ 748.6, 328.2, "plan occurrence" ], [ 761.7, 328.2, "plan occurrence" ], [ 828.1, 259.7, "plan occurrence" ], [ 859.9, 259.7, "plan occurrence" ], [ 902.2, 259.7, "plan occurrence" ], [ 939.5, 253.8, "plan occurrence" ], [ 939.5, 259.1, "plan occurrence" ], [ 891.2, 312.6, "plan occurrence" ], [ 885.4, 312.6, "plan occurrence" ], [ 726.3, 281.1, "plan occurrence" ], [ 773.0, 227.8, "plan occurrence" ], [ 642.1, 300.2, "plan occurrence" ], [ 843.0, 141.2, "plan occurrence" ], [ 892.3, 179.0, "plan occurrence" ] ] }, { "id": "card-readers", "count": 9, "unit": "EA", "markers": [ [ 1176.9, 145.6, "CR at Laundry Discharge/CU-2 access" ], [ 1342.1, 323.7, "CR at TV Lounge exterior/access" ], [ 158.2, 358.9, "CR at Stair 2" ], [ 1188.8, 391.2, "CR at Guest Laundry" ], [ 1133.0, 560.0, "CR paired with IT at Vestibule" ], [ 936.6, 594.6, "CR near Sales" ], [ 232.1, 600.4, "CR near Pool Equipment" ], [ 822.9, 610.4, "CR near west side of Mechanical 128" ], [ 790.0, 623.9, "CR near Mechanical 128/plan access" ] ] }, { "id": "named-hvac-power-connections", "count": 17, "unit": "EA", "markers": [ [ 595, 137, "CU-1" ], [ 736, 137, "ACCU-1.6" ], [ 843, 137, "ACCU-1.5" ], [ 934, 137, "ACCU-1.4" ], [ 1054, 152, "AHU-1.5" ], [ 1127, 137, "CU-2" ], [ 1233, 154, "ACCU-1.3" ], [ 1317, 154, "ACCU-1.2" ], [ 1384, 154, "ACCU-1.1" ], [ 771, 281, "AHU-1.6" ], [ 720, 301, "FCU-1" ], [ 1069, 256, "FCU-2" ], [ 1077, 450, "AHU-1.4" ], [ 791, 544, "AHU-1.3" ], [ 1311, 601, "AHU-1.2" ], [ 1311, 625, "AHU-1.1" ], [ 1263, 176, "EUH" ] ] }, { "id": "electrical-distribution-and-control-equipment", "count": 10, "unit": "EA", "markers": [ [ 654, 163, "ATS-2" ], [ 655, 205, "EP" ], [ 690, 230, "L1.D" ], [ 742, 252, "L1.C" ], [ 787, 252, "L1.B" ], [ 833, 252, "L1.A" ], [ 690, 177, "MDP" ], [ 906, 303, "PP" ], [ 1110, 145, "FPC" ], [ 1142, 145, "JP" ] ] }, { "id": "dry-storage-active-schedule-quantity", "count": 19, "unit": "EA", "markers": [], "sourceNote": "Explicit QTY-column total across active schedule rows; item 02 has QTY 2, 17 other active rows have QTY 1. This is scheduled equipment quantity, not symbol inference." }, { "id": "scaled-plan-connection-curves", "count": 56, "unit": "RUN", "markers": [], "sourceNote": "Visible black circuit/connection centerlines only; 729.4 drawing LF." } ], "receptacleClassificationCaution": "The three circular wall-receptacle groups are exact repeated CAD-glyph occurrences isolated from the scaled plan and classified by outline/cross/fill signature. Text modifiers such as WP, AB and IG are retained visually on the plan but are not rolled into separate additional quantities; they modify these receptacle occurrences.", "scaledPlanRuns": { "service": "electrical plan connection/circuit graphics", "count": 56, "totalDrawingLF": 729.4, "rounding": "total is calculated from unrounded source geometry; individual runs are rounded independently to nearest 0.5 LF and therefore sum to 729.5 LF", "installedRouteLF": null, "conductorLF": null, "conduitLF": null, "verticalLF": null, "hiddenRoutingLF": null, "polylines": [ { "id": "run-01", "p": [ [ 595.0, 130.4 ], [ 665.6, 137.6 ], [ 736.3, 130.4 ] ], "lf": 21.5 }, { "id": "run-02", "p": [ [ 1232.7, 165.9 ], [ 1207.1, 144.5 ], [ 1173.7, 143.1 ] ], "lf": 10.0 }, { "id": "run-03", "p": [ [ 668.2, 218.7 ], [ 683.2, 181.3 ], [ 678.5, 141.1 ] ], "lf": 12.0 }, { "id": "run-04", "p": [ [ 642.1, 172.5 ], [ 664.6, 161.8 ], [ 678.5, 141.1 ] ], "lf": 7.5 }, { "id": "run-05", "p": [ [ 843.0, 141.2 ], [ 862.9, 166.2 ], [ 892.3, 179.0 ] ], "lf": 9.5 }, { "id": "run-06", "p": [ [ 724.0, 165.7 ], [ 755.0, 178.9 ], [ 788.7, 178.9 ], [ 819.7, 165.6 ], [ 843.0, 141.2 ] ], "lf": 20.5 }, { "id": "run-07", "p": [ [ 869.2, 218.7 ], [ 908.5, 185.6 ], [ 934.4, 141.2 ] ], "lf": 15.5 }, { "id": "run-08", "p": [ [ 1054.1, 218.7 ], [ 1065.6, 179.7 ], [ 1052.8, 141.2 ] ], "lf": 12.5 }, { "id": "run-09", "p": [ [ 557.8, 150.9 ], [ 578.3, 153.4 ], [ 595.0, 141.2 ] ], "lf": 6.5 }, { "id": "run-10", "p": [ [ 1173.7, 143.1 ], [ 1151.7, 146.9 ], [ 1134.2, 160.7 ], [ 1125.4, 181.1 ], [ 1127.3, 203.3 ] ], "lf": 13.5 }, { "id": "run-12", "p": [ [ 1173.6, 239.6 ], [ 1173.1, 221.2 ], [ 1162.5, 206.1 ], [ 1145.3, 199.4 ], [ 1127.3, 203.3 ] ], "lf": 11.0 }, { "id": "run-13", "p": [ [ 1009.1, 218.8 ], [ 975.8, 208.7 ], [ 942.5, 218.8 ] ], "lf": 10.5 }, { "id": "run-14", "p": [ [ 942.5, 218.7 ], [ 905.8, 209.1 ], [ 869.1, 218.7 ] ], "lf": 11.5 }, { "id": "run-15", "p": [ [ 1114.4, 214.0 ], [ 1092.1, 218.7 ], [ 1073.3, 230.4 ], [ 1059.6, 247.8 ], [ 1052.6, 269.4 ] ], "lf": 13.5 }, { "id": "run-16", "p": [ [ 1157.3, 269.5 ], [ 1158.1, 249.3 ], [ 1149.7, 231.0 ], [ 1134.1, 218.3 ], [ 1114.4, 214.1 ] ], "lf": 12.0 }, { "id": "run-17", "p": [ [ 1009.1, 218.7 ], [ 1031.6, 224.1 ], [ 1054.1, 218.7 ] ], "lf": 7.0 }, { "id": "run-18", "p": [ [ 981.4, 266.1 ], [ 953.0, 235.3 ], [ 911.8, 227.8 ] ], "lf": 13.0 }, { "id": "run-19", "p": [ [ 837.4, 227.8 ], [ 874.6, 239.0 ], [ 911.8, 227.8 ] ], "lf": 12.0 }, { "id": "run-20", "p": [ [ 773.0, 227.8 ], [ 762.8, 234.5 ], [ 758.6, 245.9 ], [ 761.9, 257.6 ], [ 771.5, 265.1 ] ], "lf": 7.5 }, { "id": "run-21", "p": [ [ 557.0, 230.9 ], [ 573.9, 244.5 ], [ 595.6, 242.8 ] ], "lf": 6.5 }, { "id": "run-22", "p": [ [ 859.9, 259.7 ], [ 854.0, 245.4 ], [ 840.4, 238.1 ], [ 825.3, 241.0 ], [ 815.5, 252.9 ] ], "lf": 9.5 }, { "id": "run-23", "p": [ [ 642.1, 243.5 ], [ 679.5, 253.6 ], [ 715.0, 237.8 ] ], "lf": 12.0 }, { "id": "run-24", "p": [ [ 1053.4, 269.4 ], [ 1037.4, 256.7 ], [ 1017.7, 251.6 ], [ 997.6, 254.9 ], [ 980.6, 266.1 ] ], "lf": 12.5 }, { "id": "run-25", "p": [ [ 815.5, 260.0 ], [ 835.3, 273.6 ], [ 858.9, 278.3 ], [ 882.4, 273.4 ], [ 902.2, 259.7 ] ], "lf": 14.5 }, { "id": "run-26", "p": [ [ 726.4, 281.1 ], [ 735.4, 273.4 ], [ 731.0, 262.4 ] ], "lf": 4.0 }, { "id": "run-27", "p": [ [ 642.1, 300.2 ], [ 677.5, 307.9 ], [ 712.8, 304.2 ], [ 745.1, 289.7 ], [ 771.8, 265.2 ] ], "lf": 21.5 }, { "id": "run-28", "p": [ [ 1004.4, 266.1 ], [ 1035.3, 275.5 ], [ 1067.0, 269.4 ] ], "lf": 10.0 }, { "id": "run-29", "p": [ [ 630.4, 276.3 ], [ 605.2, 280.5 ], [ 595.8, 304.3 ] ], "lf": 8.0 }, { "id": "run-30", "p": [ [ 978.7, 275.2 ], [ 990.3, 281.1 ], [ 1002.0, 275.2 ] ], "lf": 4.0 }, { "id": "run-31", "p": [ [ 595.8, 304.3 ], [ 614.6, 338.0 ], [ 645.2, 361.6 ], [ 682.6, 371.0 ], [ 720.7, 364.9 ] ], "lf": 23.5 }, { "id": "run-32", "p": [ [ 1283.1, 311.8 ], [ 1304.6, 319.4 ], [ 1326.1, 311.8 ] ], "lf": 7.0 }, { "id": "run-33", "p": [ [ 1236.7, 311.8 ], [ 1259.9, 320.3 ], [ 1283.1, 311.8 ] ], "lf": 7.5 }, { "id": "run-34", "p": [ [ 1333.1, 326.4 ], [ 1314.4, 346.3 ], [ 1317.2, 373.4 ] ], "lf": 8.5 }, { "id": "run-35", "p": [ [ 228.2, 364.8 ], [ 292.4, 377.6 ], [ 350.8, 376.7 ], [ 407.7, 364.3 ], [ 467.4, 337.2 ], [ 527.0, 364.5 ], [ 591.1, 378.5 ], [ 656.6, 378.7 ], [ 720.7, 364.8 ] ], "lf": 76.5 }, { "id": "run-36", "p": [ [ 228.2, 364.8 ], [ 209.8, 350.7 ], [ 187.2, 345.5 ], [ 164.5, 350.2 ], [ 145.9, 364.0 ] ], "lf": 14.0 }, { "id": "run-37", "p": [ [ 895.1, 392.9 ], [ 902.0, 378.9 ], [ 899.0, 363.5 ] ], "lf": 5.0 }, { "id": "run-38", "p": [ [ 1283.1, 373.4 ], [ 1300.2, 379.7 ], [ 1317.2, 373.4 ] ], "lf": 5.5 }, { "id": "run-39", "p": [ [ 974.0, 377.6 ], [ 994.2, 388.5 ], [ 1016.2, 392.1 ], [ 1038.3, 388.5 ], [ 1058.5, 377.6 ] ], "lf": 13.5 }, { "id": "run-40", "p": [ [ 1221.5, 381.1 ], [ 1237.3, 387.8 ], [ 1254.1, 384.4 ] ], "lf": 5.0 }, { "id": "run-41", "p": [ [ 1221.5, 381.2 ], [ 1210.4, 410.2 ], [ 1221.5, 439.2 ] ], "lf": 9.5 }, { "id": "run-42", "p": [ [ 1310.9, 429.4 ], [ 1304.9, 411.0 ], [ 1291.5, 397.1 ], [ 1273.3, 390.4 ], [ 1254.0, 392.3 ] ], "lf": 11.5 }, { "id": "run-43", "p": [ [ 895.2, 392.9 ], [ 883.8, 410.2 ], [ 880.0, 429.8 ], [ 883.8, 449.4 ], [ 895.2, 466.7 ] ], "lf": 12.5 }, { "id": "run-44", "p": [ [ 839.2, 402.7 ], [ 830.8, 427.2 ], [ 839.2, 451.6 ] ], "lf": 8.0 }, { "id": "run-45", "p": [ [ 1245.8, 453.2 ], [ 1236.8, 440.8 ], [ 1221.5, 439.2 ] ], "lf": 4.5 }, { "id": "run-46", "p": [ [ 839.3, 451.6 ], [ 828.3, 463.3 ], [ 824.3, 478.9 ], [ 828.3, 494.5 ], [ 839.3, 506.2 ] ], "lf": 9.5 }, { "id": "run-47", "p": [ [ 1148.4, 543.6 ], [ 1169.5, 553.0 ], [ 1191.8, 554.9 ], [ 1213.6, 549.5 ], [ 1232.9, 536.9 ], [ 1246.9, 518.6 ], [ 1253.9, 497.3 ], [ 1253.6, 474.9 ], [ 1245.8, 453.2 ] ], "lf": 27.5 }, { "id": "run-48", "p": [ [ 895.1, 466.7 ], [ 877.5, 489.3 ], [ 871.3, 517.2 ], [ 877.5, 545.2 ], [ 895.1, 567.8 ] ], "lf": 17.5 }, { "id": "run-49", "p": [ [ 839.3, 506.2 ], [ 817.1, 527.4 ], [ 811.0, 557.3 ] ], "lf": 9.5 }, { "id": "run-50", "p": [ [ 1137.4, 526.4 ], [ 1116.6, 527.0 ], [ 1098.3, 535.2 ], [ 1084.4, 549.6 ], [ 1076.7, 568.9 ] ], "lf": 12.5 }, { "id": "run-51", "p": [ [ 1148.5, 543.6 ], [ 1162.8, 574.0 ], [ 1188.3, 595.9 ], [ 1220.4, 605.6 ], [ 1253.8, 601.5 ] ], "lf": 20.5 }, { "id": "run-52", "p": [ [ 1119.9, 555.3 ], [ 1108.7, 578.9 ], [ 1120.0, 602.5 ] ], "lf": 8.0 }, { "id": "run-53", "p": [ [ 811.0, 557.3 ], [ 823.4, 569.2 ], [ 839.3, 562.7 ] ], "lf": 5.5 }, { "id": "run-54", "p": [ [ 839.3, 562.7 ], [ 843.7, 577.2 ], [ 854.3, 588.0 ], [ 868.8, 592.6 ], [ 883.7, 589.9 ] ], "lf": 9.0 }, { "id": "run-55", "p": [ [ 212.5, 572.3 ], [ 203.0, 605.9 ], [ 202.5, 640.4 ], [ 210.7, 673.8 ], [ 227.5, 704.5 ] ], "lf": 21.0 }, { "id": "run-56", "p": [ [ 791.8, 618.2 ], [ 854.4, 645.5 ], [ 920.8, 651.8 ], [ 985.9, 637.6 ], [ 1044.8, 603.1 ] ], "lf": 40.5 }, { "id": "run-57", "p": [ [ 255.9, 725.4 ], [ 265.3, 704.5 ], [ 255.9, 683.7 ] ], "lf": 7.0 } ] }, "keyedNotes": [ [ 1, "LOCATE IN PIT FOR SUMP PUMP." ], [ 2, "RECEPTACLE OUTLETS ABOVE THE CEILING FOR MAINTENANCE." ], [ 3, "TELEPHONE BOARD" ], [ 4, "SECURITY BOARD" ], [ 5, "CABLE TV BOARD" ], [ 6, "FIELD LOCATE FOR DOOR MOTOR." ], [ 7, "FIRE ALARM CONTROL PANEL." ], [ 8, "RED CASED EMERGENCY PHONE." ], [ 9, "RECEPTACLES FOR PHOTOCOPIER/PRINTER. VERIFY WITH HILTON/OWNER PRIOR TO INSTALLATION." ], [ 10, "INDOOR UNIT POWERED FROM OUTDOOR UNIT. VERIFY THE REQUIREMENT WITH MECHANICAL PLAN PRIOR TO INSTALLATION." ], [ 11, "OUTLETS FOR TELEVISION. VERIFY LOCATION AND ELEVATION WITH ARCHITECTURAL PLAN PRIOR TO INSTALLATION." ], [ 12, "(NOT USED)." ], [ 13, "J.BOX FOR POOL LIFT STATION. VERIFY THE LOCATION WITH ARCHITECTURAL PLAN/POOL CONTRACTOR PRIOR TO INSTALLATION." ], [ 14, "(NOT USED)." ], [ 15, "J.BOX FOR MOTORIZED DAMPER. VERIFY THE LOCATION WITH MECHANICAL PLAN PRIOR TO INSTALLATION." ], [ 16, "240V, 3P, 60A DISCONNECT SWITCH W/60A CURRENT LIMITING CLASS RK1 FUSES (10K A.I.C) IN NEMA-3R ENCLOSURE FOR BOOSTER PUMP CONTROL PANEL. VERIFY THE LOCATION WITH PLUMBING PLAN PRIOR TO INSTALLATION." ], [ 17, "J.BOX FOR ROLLER SHADE. VERIFY THE LOCATION WITH ARCHITECTURAL PLAN PRIOR TO INSTALLATION." ], [ 18, "EMERGENCY SHUT-OFF BUTTON FOR GRILLS. VERIFY LOCATION WITH ARCHITECTURAL PLAN/OWNER PRIOR TO INSTALLATION." ], [ 19, "VERIFY THE LOCATION AT SITE PRIOR TO INSTALLATION." ], [ 20, "RECESSED J.BOX ROUTED FROM FLOOR THROUGH MILLWORK, COORDINATE WITH MILLWORK." ], [ 21, "HARDWIRED DATA OUTLETS ARE OPTIONAL IN PUBLIC SPACES - WIRELESS INTERNET IS REQUIRED." ], [ 22, "VERIFY WITH CASEWORK/HILTON FOR THE REQUIREMENTS OF POWER AND TEL/DATA OUTLETS AT FRONT DESK PRIOR TO INSTALLATION." ], [ 23, "COORDINATE ELECTRICAL WITH FURNITURE PLACEMENT FLUSH MOUNTED FLOOR OUTLET BOX WITH BRUSHED ALUMINUM COVER PLATE." ], [ 24, "FIELD VERIFICATION OF THE BEST LOCATION OF ELECTRICAL PANELS PRIOR TO INSTALLATION. THE LOCATION OF ELECTRICAL PANELS MUST COMPLY WITH 110.26 AND 240.24 OF THE NEC." ] ], "generalNotes": [ [ 1, "FOR HOME RUNS (FROM UNITS) 100 FT OR MORE, THE ELECTRICAL CONTRACTOR HAS TO CHECK THE VOLTAGE DROP AND SELECT THE SUITABLE CABLES SIZE TO COMPLY WITH THE MAXIMUM ALLOWED VOLTAGE DROP FOR THE FEEDER CONDUCTOR (3%). THE MAXIMUM COMBINED VOLTAGE DROP ON BOTH INSTALLED FEEDER CONDUCTORS AND BRANCH CIRCUIT CONDUCTORS TO THE FARTHEST CONNECTED LOAD OR OUTLET SHALL NOT EXCEED 5 PERCENT." ], [ 2, "THE CONTRACTOR SHALL VERIFY THE OWNER/FRANCHISE FOR THE QUANTITIES AND LOCATIONS OF THE LOW VOLTAGE SYSTEM DEVICES (CARD READER, WIRELESS ACCESS POINT, INTERCOM, ETC.) AND PROVIDE ALL NECESSARY ACCESSORIES TO COMPLETE THE WIRING, POWER SUPPLY FOR THE DEVICES AS PER THE MANUFACTURER SPECIFICATIONS/INSTALLATION GUIDELINES." ], [ 3, "ELECTRICAL ROOM TO HAVE PANIC HARDWARE INSTALLED AND DOOR SHALL SWING IN THE DIRECTION OF EGRESS. COMPLY WITH THE 2020 NEC, ARTICLE 110.26 (C)(3)." ], [ 4, "ALL GFI RECEPTACLES SHALL NOT BE HIDDEN OR OBSTRUCTED PER THE 2020 NEC, INCLUDE THE FOOD PREP AREA." ], [ 5, "THE CONTRACTOR SHALL VERIFY LOCATION OF ALL FLOOR OUTLETS WITH FURNITURE/ ARCH. PRIOR TO INSTALLATION" ], [ 6, "CONTRACTOR SHOULD VERIFY EXACT LOCATION, BREAKER SIZES, CABLE SIZES, HP, WIRING, ETC FOR ALL ELECTRICAL EQUIPMENT WITH KITCHEN SUPPLIER PRIOR TO INSTALLATION" ], [ 7, "PROVIDE TAMPER RESISTANT RECEPTACLES FOR THE BREAKFAST ROOM, LOBBY AND OTHER ASSEMBLY AREAS ACCESSIBLE TO THE PUBLIC (NEC 406.12)" ], [ 9, "THE CONTRACTOR SHALL VERIFY ALL REQUIREMENTS FOR WIRING CONTROL, NEUTRAL WIRES FOR ALL ELECTRICAL EQUIPMENT WITH THE SUPPLIER/MANUFACTURER PRIOR TO INSTALLATION." ], [ 10, "SPACE ALLOCATIONS FOR MATERIALS, EQUIPMENT AND DEVICES HAVE BEEN MADE ON THE BASIS OF PRESENT AND KNOWN FUTURE REQUIREMENTS AND THE DIMENSIONS OF ITEMS OF EQUIPMENT OR DEVICES OF A PARTICULAR MANUFACTURER. THE CONTRACTOR SHALL VERIFY THAT ALL MATERIALS, EQUIPMENT AND DEVICES PROPOSED FOR USE ON THIS PROJECT ARE WITHIN THE CONSTRAINTS OF THE ALLOCATED SPACE." ], [ 11, "HOMERUNS SHALL BE COMBINED WHERE POSSIBLE IN ACCORDING TO NFPA." ], [ 12, "HOMERUN CIRCUITS FOR ISOLATED GROUND RECEPTACLES SHALL BE SEPARATED FROM OTHER CIRCUITS. EACH CIRCUIT SHALL HAVE ITS OWN NEUTRAL CONDUCTOR AND EACH HOMERUN SHALL CONTAIN AN ISOLATED AND EQUIPMENT GROUND CONDUCTOR." ], [ 13, "COORDINATE THE LOCATION AND INSTALLATION DETAIL OF OUTLETS IN MILLWORK WITH ARCHITECTURAL DRAWINGS (WALL ELEVATIONS, MILLWORK DETAILS, ETC.) AND WITH MILLWORK MANUFACTURER PRIOR TO ELECTRICAL ROUGH-IN." ], [ 14, "WALL AND FLOOR MOUNTED POWER RECEPTACLES SHOWN NEAR DATA OUTLETS SHALL BE LOCATED WITHIN SIX (6) INCHES OF THE DATA OUTLET. LOCATE AT SAME MOUNTING HEIGHT UNLESS NOTED OTHERWISE." ], [ 15, "ALL GFCI RECEPTACLES SHALL BE CONNECTED SO THAT ALL DEVICES ON THE SAME CIRCUIT AS THE GFCI RECEPTACLE DO NOT DE-ENERGIZE UPON TRIPPING. ALL GFCI RECEPTACLES SHALL INCLUDE A LOCK-OUT FUNCTION TO PROTECT AGAINST THE USE OF MISWIRED DEVICES OR DEVICES THAT HAVE BEEN DAMAGED DUE TO DISABLING SURGES." ], [ 16, "ELECTRICAL CONTRACTORS MUST VERIFY ALL ELECTRICAL REQUIREMENTS WITH THE HVAC AND PLUMBING SYSTEMS TO PROVIDE ALL NECESSARY ACCESSORIES TO COMPLETE THE CONTROL WIRING FOR THE MOTORS." ], [ 17, "CONTRACTOR SHOULD REFER TO THE EXHAUST /FRESH AIR FAN SCHEDULES ON SHEET M1.1 FOR THE CONTROL OF FANS." ], [ 18, "COORDINATE POWER & DATA REQUIREMENTS FOR CARDIO EQUIPMENT WITH EQUIPMENT VENDOR'S LAYOUT PRIOR TO INSTALLATION." ], [ 19, "VERIFY LOCATIONS AND QUANTITIES OF WIRELESS ACCESS POINT (WAP) WITH THE OWNER / HOTEL OPERATOR PRIOR TO INSTALLATION." ] ], "specialNotes": { "fireSmokeDamper": [ "CONTRACTOR SHALL PROVIDE J-BOXES FOR FIRE SMOKE DAMPERS AT LEVEL 1 FLOOR, CONNECT TO L1.D-20, USING 2#12, 1/2\"C." ], "pool": [ "POOL TO BE PERMITTED SEPARATELY.", "SWIMMING POOL CONTRACTOR SHALL INSTALL ALL ELECTRICAL DEVICES/EQUIPMENTS AND ASSOCIATED WIRING IN ACCORDANCE WITH ARTICLE 680 (NEC 2020)", "THE GROUNDING ELECTRODE SYSTEM @ THE POOL BUILDING SHALL COMPLY W/NEC 2020 250.32. NO SIGN APPROVAL UNDER THIS PERMIT. PLEASE SEE INFORMATION BULLETIN (IB) 191. NO EQUIPMENT GROUNDING CONDUCTORS ARE PERMITTED IN SERVICE LATERALS PER CPS ENERGY STANDARDS SECTION 1708.", "ELECTRICAL EQUIPMENT INSTALLED IN POOL EQUIPMENT ROOMS TO BE RATED FOR USE IN CORROSIVE ENVIRONMENTS." ] }, "dryStorageElectricalSchedule": { "columns": [ "item", "qty", "description", "manufacturer", "model", "volts", "phase", "amps", "electricalType", "aff", "electricalComments" ], "rows": [ [ "01", 1, "MOBILE REACH-IN FREEZER", "TRUE", "T-49F-HC", 120, 1, 9.6, "REC", "18\"", null ], [ "02", 2, "MOBILE REACH-IN REFRIGERATOR", "TRUE", "TS-49-HC", 120, 1, 5.4, "REC", "18\"", null ], [ "05", 1, "UNDERCOUNTER DISHMACHINE (HIGH TEMP)", "CHAMPION", "UH-100B", 208, 3, 29.0, "JBOX", "18\"", null ], [ "14", 1, "COFFEE MAKER (OPERATOR FURNISHED)", "FETCO", "CBS-2152XTS", null, 1, 22.5, "REC", "48\"", "(120/208V) 3 WIRE + GROUND. VERIFY REQUIREMENTS WITH OPERATOR SUPPLIED EQUIPMENT" ], [ "16", 1, "CONVECTION OVEN (VENTLESS)", "MOFFAT (TURBOFAN)", "E33D5H2", 208, 1, 27.8, "REC", "48\"", null ], [ "18", 1, "MOBILE REACH-IN FREEZER", "TRUE", "T-23F-HC", 120, 1, 7.2, "REC", "18\"", null ], [ "20", 1, "CONVECTION OVEN (VENTLESS) (OPTIONAL)", "MOFFAT (TURBOFAN)", "E33D5H2", 208, 1, 27.8, "REC", "48\"", null ], [ "22", 1, "MICROWAVE OVEN WITH SHELF", "AMANA", "HDC12A2/BMS2024", 120, 1, 16.8, "REC", "48\"", null ], [ "24", 1, "WAFFLE MAKER (BY VENDOR)", null, null, 120, 1, 13, "REC", "18\"", "DEDICATED CIRCUIT, VERIFY REQUIREMENTS WITH OPERATOR SUPPLIED EQUIPMENT" ], [ "25", 1, "WAFFLE MAKER (FUTURE) (BY VENDOR)", null, null, 120, 1, 13, "REC", "18\"", "DEDICATED CIRCUIT, VERIFY REQUIREMENTS WITH OPERATOR SUPPLIED EQUIPMENT, VERIFY ALL ELECTRICAL REQUIREMENTS WITH FUTURE EQUIPMENT" ], [ "26", 1, "CONVEYOR TOASTER", "APW WYOTT", "ECO 4000-350L-HILTON", 120, 1, 14.4, "REC", "18\"", "STUB OUT, TO FIXTURE MOUNTED OUTLET (BY ELECTRICAL DIVISION)" ], [ "27", 1, "DISPLAY SHOWCASE", "EQUIPEX", "WD780B-2/1", 120, 1, 15.0, "REC", "18\"", "STUB OUT, TO FIXTURE MOUNTED OUTLET (BY ELECTRICAL DIVISION)" ], [ "28", 1, "JUICE DISPENSER (BY VENDOR)", "NESTLE VITALITY", "EXPRESS", 120, 1, 6.0, "REC", "48\"", "VERIFY REQUIREMENTS WITH VENDOR SUPPLIED EQUIPMENT" ], [ "29", 1, "WARMING KETTLE (OPTIONAL)", "VOLLRATH", "72017", 120, 1, 6.7, "REC", "48\"", null ], [ "31", null, "NOT USED", null, null, null, null, null, null, null, null ], [ "34", 1, "YOGURT DISPENSER (BY VENDOR)", "PERFECT PARFAIT", "PPHG1BK", 120, 1, 1.4, "REC", "48\"", null ], [ "35", 1, "REACH-IN DISPLAY FREEZER", "TRUE", "GDM-23F-HC-TSL01", 120, 1, 6.2, "REC", "18\"", null ], [ "36", 1, "REACH-IN DISPLAY REFRIGERATOR", "TRUE", "GDM-49-HC-TSL01", 120, 1, 8.5, "REC", "18\"", null ], [ "37", 1, "WATER DISPENSER", "MARCO", "FRIIA HCS", null, 1, null, "REC", "18\"", "(2 @ 120V AT 180W AND 1400W)" ] ], "generalNotes": [ "THE CONTRACTOR SHALL COORDINATE ALL EQUIPMENT REQUIREMENTS AND LOCATIONS WITH THE KITCHEN VENDOR'S EQUIPMENT PLAN. IN CASE OF ANY CONFLICT BETWEEN THE ELECTRICAL PLAN AND THE KITCHEN PLAN, THE CONTRACTOR MUST ADHERE TO THE KITCHEN PLANS AND PROVIDE ALL NECESSARY ACCESSORIES TO COMPLETE THE WIRING AND POWER SUPPLY FOR THE KITCHEN EQUIPMENT.", "ALL RECEPTACLES IN KITCHEN SHALL BE GFCI PROTECTION." ] }, "convenienceOutletRequirements": { "columns": [ "item", "description", "volts", "phase", "amps", "kw", "hp", "electricalType", "aff", "electricalComments" ], "rows": [ [ "900", "CONVENIENCE RECEPTACLE", 120, 1, 15.0, null, null, "REC", "+18\"", "CONVENIENCE OUTLET; STUB OUT WALL" ], [ "901", "CONVENIENCE RECEPTACLE", 120, 1, 15.0, null, null, "REC", "+48\"", "CONVENIENCE OUTLET; STUB OUT WALL" ] ], "definitionNotQuantity": true }, "crossReferences": [ { "target": "M1.1", "source": "General Note 17", "purpose": "exhaust/fresh-air fan controls", "status": "present in drawing set; equipment/control coordination required" }, { "target": "mechanical plan", "source": "Keyed Notes 10 and 15", "purpose": "indoor/outdoor unit requirements and motorized-damper J-box locations", "status": "generic; no individual sheet/detail cited" }, { "target": "plumbing plan", "source": "Keyed Note 16", "purpose": "booster-pump control-panel disconnect location", "status": "generic; no individual sheet/detail cited" }, { "target": "architectural plan/prototype/millwork/furniture/vendor plans", "source": "Keyed Notes 9,11,13,17,18,20-23 and General Notes 2,5,6,10,13,18,19", "purpose": "field location, final requirements and quantities", "status": "coordination references without specific sheet/detail identifiers" }, { "target": "NEC 2020 Articles 110.26(C)(3), 110.26, 240.24, 250.32, 406.12, 680", "source": "notes", "purpose": "egress, panel clearance/location, grounding, tamper resistance and pool work", "status": "printed code references" }, { "target": "IB 191 and CPS Energy Standards Section 1708", "source": "Pool Note 3", "purpose": "pool-building grounding/service lateral requirements", "status": "jurisdictional applicability unresolved; project is labeled Bradenton, Florida while CPS Energy is associated with another utility territory" } ], "facts": [ { "id": "F1", "statement": "The scaled plan covers 41 labeled rooms/areas, including 11 guestrooms whose interiors are intentionally blank on E3.0 and require E4.0/E4.1 typical-room details." }, { "id": "F2", "statement": "Exactly 144 repeated circular wall-receptacle glyphs were isolated on the scaled plan: 53 duplex-outline, 21 quad-outline and 70 filled GFI-duplex signatures." }, { "id": "F3", "statement": "Exactly 56 visible black plan connection curves measure 729.4 drawing LF at 37.5 source pixels per foot. This is graphical centerline length, not installed routing or conductor/conduit quantity." }, { "id": "F4", "statement": "The Dry Storage Electrical Schedule has 19 printed rows: 18 active item definitions and one NOT USED row (31). Active QTY values total 19 EA because item 02 has QTY 2." }, { "id": "F5", "statement": "General Notes are numbered 1-7 and 9-19; number 8 is absent." }, { "id": "F6", "statement": "Keyed Notes 12 and 14 are explicitly NOT USED." }, { "id": "F7", "statement": "The fire/smoke-damper note requires Level 1 J-boxes on L1.D-20 using 2#12 in 1/2-inch conduit but provides no damper/J-box quantity." }, { "id": "F8", "statement": "No installed WAP quantity is certifiable; General Note 19 requires owner/hotel-operator verification." }, { "id": "F9", "statement": "No installed pool equipment/wiring quantity beyond plotted E3.0 symbols is certifiable because pool work is separately permitted and assigned to the pool contractor." } ], "issues": [ { "id": "I1", "severity": "numbering-gap", "statement": "General Note 8 is missing; numbering jumps from 7 to 9." }, { "id": "I2", "severity": "quantity-gap", "statement": "The fire/smoke-damper note requires J-boxes but gives no damper count or exact locations on E3.0." }, { "id": "I3", "severity": "coordination", "statement": "Guestroom interiors 101, 102, 103, 104, 105, 106, 107, 108, 110, 112 and 114 carry no individual power devices on E3.0. Counts must be linked once from E4.0/E4.1; blank rooms are not zero-scope rooms." }, { "id": "I4", "severity": "coordination", "statement": "WAP, card-reader/intercom and other low-voltage quantities are subject to owner/franchise verification; nine CR labels are plotted, but note-driven additions remain unknown." }, { "id": "I5", "severity": "potential-jurisdiction-conflict", "statement": "Pool Note 3 cites CPS Energy Standards Section 1708 although the project title block says Bradenton, Florida. Verify the intended utility/jurisdiction before applying the service-lateral statement." }, { "id": "I6", "severity": "schedule-blank", "statement": "Dry-storage item 14 has a blank volts cell but an electrical comment calling for (120/208V) 3 wire + ground; item 37 has blank volts and amps cells while its comment lists two 120V loads at 180W and 1400W." }, { "id": "I7", "severity": "optional-future-scope", "statement": "Dry-storage items 20 and 29 are marked OPTIONAL; item 25 is marked FUTURE. Carry separately from base installed scope." }, { "id": "I8", "severity": "unresolved-routing", "statement": "Plan curves are diagrammatic centerlines. Installed route, verticals, concealed routing, conductor count, conduit size except where expressly noted, slack and fittings are not derivable from scale and remain null." }, { "id": "I9", "severity": "source-density", "statement": "Several tel/data/TV, special-outlet, floor-outlet, J-box and disconnect glyphs overlap circuit leaders and keyed-note bubbles. Their exact subtype totals are not certified in this register rather than guessed; use the normalized plan region and keyed-note requirements for manual follow-up." }, { "id": "I10", "severity": "generic-cross-reference", "statement": "Multiple notes cite architectural, mechanical, plumbing, prototype, vendor, millwork or furniture plans without sheet/detail numbers, preventing closed-loop reference validation on E3.0 alone." } ], "uncertifiedSourceObscuredItems": [ { "category": "telephone/data/television outlet subtype totals", "reason": "triangular glyphs overlap in dense workstation/front-desk clusters; no labels uniquely identify every triangle" }, { "category": "floor receptacle and floor voice/data subtype totals", "reason": "floor-box assemblies overlap equipment-item bubbles and keyed-note 20/23 leaders" }, { "category": "junction-box and safety-disconnect subtype totals", "reason": "J-box/safety-switch glyphs are frequently co-located with motors, AHUs, ACCUs and keyed-note hexagons" }, { "category": "pool equipment internal devices and wiring", "reason": "Pool Note 1 assigns separate permitting and the pool room equipment is not fully scheduled on E3.0" }, { "category": "guestroom installed devices", "reason": "guestroom interiors are blank and delegated to E4.0/E4.1" } ], "validation": { "visualCoverage": "entire 10800x7200 raster reviewed through full sheet and six full-resolution plan tiles plus dedicated note/schedule/title regions", "vectorCrossCheck": "PDF-derived SVG used only to isolate repeated black plan glyphs and connection-centerline geometry; architectural gray background, table borders, hatch lines and note/detail samples excluded", "runExclusion": "A 25.0-LF closed rectangular electrical-equipment outline was detected by the geometric filter and excluded; remaining 56 curves total 729.4 LF", "quantityIntegrity": "legend/note/detail samples are not counted as installed items; schedule quantities are separately labeled; null means not certifiable" }, "independentCrossCheck": { "schemaVersion": "1.0", "audit": { "type": "independent cross-sheet reconciliation", "scope": [ "E3.0", "E3.1", "E3.2", "E3.3", "E3.4" ], "engineeringPdfPages": [ 42, 43, 44, 45, 46 ], "sourceDirectory": "/workspace/sites/ssx-cover-release/tmp/pdfs/next5-e30-e34", "priorEvidenceUsed": [ "/workspace/sites/ssx-cover-release/dist/e11-full-audit.json", "/workspace/sites/ssx-cover-release/dist/e11-requirements.json", "/workspace/sites/ssx-cover-release/dist/e12-full-audit.json", "/workspace/scratch/e9eeb133d6f5/delegated-e12-e24/crosscheck.json", "/workspace/sites/ssx-cover-release/dist/m11-requirements.json", "/workspace/sites/ssx-cover-release/dist/m12-requirements.json", "/workspace/sites/ssx-cover-release/dist/m21-requirements.json", "/workspace/sites/ssx-cover-release/dist/m22-requirements.json", "/workspace/sites/ssx-cover-release/dist/m23-requirements.json", "/workspace/sites/ssx-cover-release/dist/m24-requirements.json", "/workspace/sites/ssx-cover-release/dist/m21-symbols.json", "/workspace/sites/ssx-cover-release/dist/m22-symbols.json", "/workspace/sites/ssx-cover-release/dist/m23-symbols.json", "/workspace/sites/ssx-cover-release/dist/m24-symbols.json" ], "method": "Read-only comparison of full-resolution 10800x7200 source rasters, selectable source text, and established schedule/plan evidence. Primary per-sheet occurrence audits were not duplicated. Every unresolved identity, quantity, route, or external verification remains fail-closed.", "limitations": [ "Panel schedules and guestroom detail sheets E4.0/E4.1 were not among the supplied reconciliation evidence.", "Plumbing, pool, elevator-vendor, and kitchen-vendor schedules were not supplied as governing quantity sources.", "No hidden routing, vertical routing, conductor multiplicity, slack, or field routing was inferred.", "OCR omits many plotted tags; conclusions were checked against full-resolution raster evidence where needed." ] }, "summary": { "overallStatus": "HOLD", "crossSheetTakeoffCompleteness": "PASS", "crossSheetTakeoffCompletenessMeaning": "The reconciliation identifies the full five-sheet sequence, repeated-floor plan boundaries, visible pattern differences, reference-only graphics, and all observed non-certifiable quantity classes. This PASS does not convert unresolved device identities, note-only devices, typical-room scope, or diagrammatic wiring into releasable quantities.", "coordinationProcurementStatus": "HOLD", "passFindings": 7, "holdFindings": 11, "releaseReason": "Coordination/procurement remains on HOLD because E3.1-E3.4 omit an explicit guestroom-power detail mapping; six EUH-2 units plotted on mechanical floors 3-5 have no corresponding visible power callouts; the FSD J-box notes provide circuits but no plotted J-box locations; E3.0 points to a fresh-air-fan schedule not present on M1.1; several upper-floor tags remain undefined; and E3.4 elevator Detail 2 contains a JHL/JHS notation conflict and vendor-dependent scope." }, "sheetSequence": [ { "sheet": "E3.0", "engineeringPdfPage": 42, "title": "POWER FIRST FLOOR PLAN", "planDetail": 1, "scale": "1/8 inch = 1 foot", "status": "PASS" }, { "sheet": "E3.1", "engineeringPdfPage": 43, "title": "POWER SECOND FLOOR PLAN", "planDetail": 1, "scale": "1/8 inch = 1 foot", "status": "PASS" }, { "sheet": "E3.2", "engineeringPdfPage": 44, "title": "POWER THIRD FLOOR PLAN", "planDetail": 1, "scale": "1/8 inch = 1 foot", "status": "PASS" }, { "sheet": "E3.3", "engineeringPdfPage": 45, "title": "POWER FOURTH FLOOR PLAN", "planDetail": 1, "scale": "1/8 inch = 1 foot", "status": "PASS" }, { "sheet": "E3.4", "engineeringPdfPage": 46, "title": "POWER FIFTH FLOOR PLAN", "planDetail": 1, "scale": "1/8 inch = 1 foot", "status": "PASS", "additionalDetail": { "number": 2, "title": "ENLARGED ELEVATOR CONTROL (LOCATED ON A TOP OF ELEVATOR SHAFT)", "scale": "N.T.S.", "quantityDisposition": "reference only; no length or installed quantity inferred" } } ], "scaleRules": { "planScale": { "printed": "1/8 inch = 1 foot", "pdfPointsPerFoot": 9.0, "sourceRasterPixelsPerFootAt300Dpi": 37.5, "status": "PASS for visible plan-scale geometry only", "qualification": "The mathematical conversion is verified from print scale and render resolution, but no independent written dimension was found and the drawn curves do not establish installed routing." }, "ntsRule": { "appliesTo": "E3.4 Detail 2", "rule": "Do not measure or scale any elevator-detail linework.", "status": "PASS" } }, "floorReconciliation": { "guestroomProgram": { "E3.0": 11, "E3.1": 24, "E3.2": 24, "E3.3": 24, "E3.4": 24, "upperFloorSubtotal": 96, "fiveFloorTotal": 107, "status": "PASS against the established electrical/mechanical 107-room chain", "inheritedQualification": "The prior E1.1 audit retains a separate HOLD against an earlier architectural count of 85; this batch reinforces 107 but does not resolve that architectural conflict." }, "upperFloors": [ { "sheet": "E3.1", "floor": 2, "panels": [ "L2.A", "L2.B" ], "visiblePlanCircuitCallouts": [ "L2.A-26", "L2.A-28", "L2.B-26,28", "L2.B-30,32" ], "fireSmokeDamperNoteCircuit": "L2.A-30", "distinctConditions": [ "Two visible stair EUH power callouts, one at each stair.", "No C.P callout and no Key Note 2 maintenance-receptacle reference.", "Room 226 is QUEEN QUEEN ACCESSIBLE; connecting king studio occurs at 205." ] }, { "sheet": "E3.2", "floor": 3, "panels": [ "L3.A", "L3.B" ], "visiblePlanCircuitCallouts": [ "L3.A-26", "L3.A-28", "L3.A-34" ], "fireSmokeDamperNoteCircuit": "L3.A-30", "distinctConditions": [ "C.P assembly and one Key Note 2 reference for an above-ceiling maintenance receptacle are present.", "No visible stair EUH power callout.", "Room 326 is KING ACCESSIBLE; connecting king studio occurs at 305." ] }, { "sheet": "E3.3", "floor": 4, "panels": [ "L4.A", "L4.B" ], "visiblePlanCircuitCallouts": [ "L4.A-26", "L4.A-28" ], "fireSmokeDamperNoteCircuit": "L4.A-30", "distinctConditions": [ "No C.P callout and no Key Note 2 maintenance-receptacle reference.", "No visible stair EUH power callout.", "Six repeated corridor duplex-family graphics are present but must not be classified as FSD J-boxes.", "Room 426 is KING ACCESSIBLE; connecting king studio occurs at 405." ] }, { "sheet": "E3.4", "floor": 5, "panels": [ "L5.A", "L5.B" ], "visiblePlanCircuitCallouts": [ "L5.A-26", "L5.A-28", "L5.A-38" ], "fireSmokeDamperNoteCircuit": "L5.A-30", "distinctConditions": [ "C.P assembly and one Key Note 2 reference for an above-ceiling maintenance receptacle are present.", "No visible stair EUH power callout.", "E3.4 alone contains the N.T.S. elevator-control detail.", "Room 526 is KING ACCESSIBLE; connecting king studios occur at 505, 512, and 514." ] } ], "repeatedPatternRule": "Do not apply a four-floor multiplier. Room types and circuit callouts vary; C.P/maintenance scope occurs only on E3.2 and E3.4; stair EUH power is visible only on E3.1; E3.4 alone carries elevator Detail 2." }, "findings": [ { "id": "PASS-01", "status": "PASS", "topic": "Power-plan sheet order, titles, and scale", "sheets": [ "E3.0", "E3.1", "E3.2", "E3.3", "E3.4" ], "evidence": [ "Engineering PDF pages 42-46 progress first through fifth floor without a gap.", "Each Detail 1 plan prints 1/8 inch = 1 foot.", "E3.4 Detail 2 is explicitly N.T.S." ], "conclusion": "The batch sequence and scale labels are internally consistent." }, { "id": "PASS-02", "status": "PASS", "topic": "Electrical/mechanical guestroom count chain", "sheets": [ "E3.0", "E3.1", "E3.2", "E3.3", "E3.4", "E2.0", "E2.1", "E2.2", "E2.3", "E2.4" ], "evidence": [ "E3.0 contains 11 guestrooms.", "Each of E3.1-E3.4 contains 24 guestrooms, producing 96 upper-floor rooms.", "11 + 96 = 107, matching the established five-floor electrical/mechanical room chain." ], "conclusion": "The power-plan room labels reconcile to 107 guestrooms, subject to the inherited architectural-count HOLD." }, { "id": "PASS-03", "status": "PASS", "topic": "Upper-floor panel and repeated-circuit progression", "sheets": [ "E3.1", "E3.2", "E3.3", "E3.4" ], "evidence": [ "Local panel pairs progress L2.A/L2.B, L3.A/L3.B, L4.A/L4.B, and L5.A/L5.B.", "The repeated corridor and storage/lobby callouts progress by local floor panel, including L2.A-26/-28 through L5.A-26/-28.", "C.P branch callouts are actual variations: L3.A-34 on E3.2 and L5.A-38 on E3.4 only." ], "conclusion": "The visible plan callouts use the correct local-floor panel prefixes and the nonrepeating variations are identifiable." }, { "id": "PASS-04", "status": "PASS", "topic": "Fire/smoke-damper note circuit progression", "sheets": [ "E3.0", "E3.1", "E3.2", "E3.3", "E3.4" ], "evidence": [ "E3.0 assigns Level 1 FSD J-boxes to L1.D-20.", "E3.1-E3.4 assign floors 2-5 to L2.A-30, L3.A-30, L4.A-30, and L5.A-30 respectively.", "Each upper-floor note states 2#12 in 1/2-inch conduit." ], "conclusion": "The textual circuit progression is internally orderly; device locations and quantities remain separately held." }, { "id": "PASS-05", "status": "PASS", "topic": "Mechanical equipment schedule families", "sheets": [ "E3.0", "M1.1", "M1.2" ], "evidence": [ "M1.1 defines AHU-1.1 through AHU-1.6, FCU-1/FCU-2 with CU-1/CU-2, EUH-1/EUH-2, PTAC-1/PTAC-2, and EF-1 through EF-13 including EF-1.1.", "The visible E3.0 AHU/ACCU and FCU/CU equipment families are schedule-addressable by the established M1.1 evidence.", "M1.2 separately defines DOAS-1 and DOAS-2 as roof equipment; absence from the first-floor power plan is not a zero-count conclusion." ], "conclusion": "The principal HVAC tag families have schedule destinations; individual electrical connections remain occurrence-controlled." }, { "id": "PASS-06", "status": "PASS", "topic": "E1.1 symbol and special-outlet definition coverage", "sheets": [ "E1.1", "E3.0", "E3.1", "E3.2", "E3.3", "E3.4" ], "evidence": [ "E1.1 defines duplex/GFI receptacles, junction box, motor, panelboard, disconnect, voice/data, and floor voice/data symbol families.", "E1.1 special outlet A is the PTAC NEMA 6-20 outlet; B is the GFCI/disposer assembly; C is the fitness NEMA 5-30 floor outlet; D is the general NEMA 5-20 floor outlet.", "The E1.1 special-outlet schedule contains definitions but no installed quantities." ], "conclusion": "The general symbol families and special-outlet types are defined; counts must come from applicable plan occurrences or mapped guestroom details." }, { "id": "PASS-07", "status": "PASS", "topic": "Elevator-detail duplicate control", "sheets": [ "E3.4", "E2.0", "E1.2" ], "evidence": [ "E3.4 Detail 2 shows two sample callouts marked 001, one at each elevator shaft graphic.", "E1.2 defines fixture type 001, and the established E2.0 evidence already accounts for two installed elevator-shaft 001 fixtures.", "E3.4 Detail 2 is N.T.S. and explicitly guideline-only." ], "conclusion": "The two Detail-2 001 samples are corroborating references and contribute zero additional fixtures to project totals." }, { "id": "HOLD-01", "status": "HOLD", "topic": "Missing typical-guestroom power mapping", "sheets": [ "E3.0", "E3.1", "E3.2", "E3.3", "E3.4", "E4.0", "E4.1" ], "evidence": [ "E3.1-E3.4 contain 96 guestroom labels but plot no complete in-room receptacle/PTAC/special-outlet layouts.", "Unlike the established E2.1-E2.4 lighting notes, the four upper-floor power sheets print no explicit E4.0/E4.1 guestroom-detail reference or room-type mapping.", "E1.1 special outlet A defines the PTAC outlet but does not establish occurrences." ], "conclusion": "A complete guestroom power-device takeoff cannot be released from E3.0-E3.4, and blank upper-floor rooms are not certified zero-device rooms.", "requiredResolution": "Issue or identify the governing guestroom power-detail sheet and a room-type-to-detail matrix, then reconcile all 107 rooms including accessible and one-bedroom/two-PTAC variants." }, { "id": "HOLD-02", "status": "HOLD", "topic": "Missing stair EUH-2 power on floors 3-5", "sheets": [ "E3.1", "E3.2", "E3.3", "E3.4", "M1.1", "M2.1", "M2.2", "M2.3", "M2.4" ], "evidence": [ "M1.1 defines EUH-2 for stairwells at 208/1/60, 5,000 W, 24 A.", "Each of M2.1-M2.4 has two certified EUH-2 plan occurrences, one at each stair, for eight upper-floor units.", "E3.1 visibly powers two stair EUH devices at L2.B-26,28 and L2.B-30,32.", "No corresponding stair EUH power callout is visible on E3.2, E3.3, or E3.4." ], "conclusion": "Six mechanically plotted EUH-2 units on floors 3-5 lack visible electrical power assignments in this batch. The electrical label EUH also omits the mechanical '-2' suffix.", "requiredResolution": "Add or identify power circuits/disconnect requirements for the two EUH-2 units on each of floors 3, 4, and 5 and confirm that E3.1's EUH labels correspond to EUH-2." }, { "id": "HOLD-03", "status": "HOLD", "topic": "FSD J-box location and symbol conflict", "sheets": [ "E1.1", "E3.1", "E3.2", "E3.3", "E3.4", "M2.1", "M2.2", "M2.3", "M2.4" ], "evidence": [ "Each upper-floor FSD note requires J-boxes on local circuit A-30 but prints no quantity.", "The A-30 routes and J-box locations are not visibly plotted on E3.1-E3.4.", "Six corridor duplex-family graphics recur at the same normalized locations on the upper-floor plans; they do not match the E1.1 junction-box symbol.", "Mechanical M2.1 contains six FD/FSD occurrences, while M2.2-M2.4 contain five each; no electrical note maps those mechanical occurrences one-for-one to plotted J-boxes." ], "conclusion": "The recurring corridor receptacle graphics must not be reclassified as FSD J-boxes, including on E3.3. FSD electrical quantities and locations are not certifiable from the note alone.", "requiredResolution": "Plot or schedule every FSD J-box and map it to the mechanical damper register and the applicable A-30 circuit. Correct any per-sheet audit that currently labels the six duplex-family graphics as FSD connection points." }, { "id": "HOLD-04", "status": "HOLD", "topic": "Undefined upper-floor C.P and HP tags", "sheets": [ "E1.1", "E3.1", "E3.2", "E3.3", "E3.4" ], "evidence": [ "HP is visibly repeated at the elevator-lobby/storage end of the upper-floor branch but is not expanded on E3.1-E3.4 or in the supplied E1.1 symbol definitions.", "C.P is visibly present only on E3.2 and E3.4 and is not expanded by the supplied legend.", "Key Note 2 on E3.2 and E3.4 identifies a receptacle outlet above the ceiling for maintenance but does not define C.P or the served equipment." ], "conclusion": "Occurrence counting can remain complete while device identity, rating, mounting, and served equipment are unresolved.", "requiredResolution": "Define HP and C.P and identify the applicable circuit/load and accessory assembly for each occurrence." }, { "id": "HOLD-05", "status": "HOLD", "topic": "Upper-floor panel schedule and breaker confirmation", "sheets": [ "E3.1", "E3.2", "E3.3", "E3.4" ], "evidence": [ "Visible local-floor callouts include A-26, A-28, floor-specific C.P circuits A-34/A-38, two E3.1 B-panel EUH circuit pairs, and note-only A-30 FSD circuits.", "The governing panel-schedule rows were not supplied in the current evidence set.", "Key Note 1 makes panel locations field-verification items." ], "conclusion": "Circuit labels are legible, but breaker description, poles, ampacity, connected load, spare conflicts, and final panel locations are not certified here.", "requiredResolution": "Reconcile every visible and note-only circuit against the governing panel schedules and equipment nameplates." }, { "id": "HOLD-06", "status": "HOLD", "topic": "Elevator-control detail notation and vendor scope", "sheets": [ "E3.4" ], "evidence": [ "Detail 2 states it is guideline-only and requires elevator-supplier verification before installation.", "The detail repeats LDU, JHS, JH1, and TSU graphics for two elevator shafts and shows EP-9/EP-7 at one shaft and EP-3/EP-1 at the other.", "Elevator Note 4d specifies disconnecting means JHL for auxiliary power and lighting, but no JHL tag is visible in the detail; the visible similar tag is JHS." ], "conclusion": "The JHL/JHS notation is a broken or ambiguous reference, and the detail cannot serve as final procurement quantity or wiring-route evidence.", "requiredResolution": "Correct the JHL/JHS designation, identify each disconnect/controller function and source circuit, and obtain an elevator-vendor power/controls schedule for both elevators." }, { "id": "HOLD-07", "status": "HOLD", "topic": "Broken fresh-air-fan schedule reference", "sheets": [ "E3.0", "M1.1", "M1.2" ], "evidence": [ "E3.0 General Note 17 directs exhaust/fresh-air fan controls to schedules on M1.1.", "M1.1 contains an Exhaust Fan Schedule and the established M1.1 requirements define EF-1 through EF-13 including EF-1.1.", "No distinct fresh-air-fan schedule or FAF tag was found in the supplied M1.1 evidence; M1.2 defines DOAS-1/DOAS-2 instead." ], "conclusion": "The exhaust-fan portion resolves to M1.1, but the fresh-air-fan portion has no defined destination in the supplied schedules.", "requiredResolution": "Clarify whether 'fresh air fan' means a DOAS component, another scheduled fan, or a missing schedule, and issue the applicable control requirements." }, { "id": "HOLD-08", "status": "HOLD", "topic": "E3.0 plumbing, pool, and motor-control dependencies", "sheets": [ "E3.0" ], "evidence": [ "Keyed Note 1 identifies a sump pump in a pit; Note 13 a pool lift-station J-box; Note 15 a motorized-damper J-box; and Note 16 a 240 V, 3-pole, 60 A fused NEMA 3R disconnect for the booster-pump control panel.", "General Note 16 requires verification of HVAC/plumbing power and control accessories.", "The pool notes state that the pool is separately permitted and that the pool contractor installs pool electrical devices/equipment and associated wiring." ], "conclusion": "These notes establish coordination obligations, not final equipment quantities or a complete electrical bill of materials.", "requiredResolution": "Reconcile sump, booster, fire-pump, pool, and motorized-damper power/control requirements to the governing plumbing, fire-pump, pool, and mechanical submittals without double counting contractor-furnished scope." }, { "id": "HOLD-09", "status": "HOLD", "topic": "E3.0 dry-storage and convenience-outlet procurement scope", "sheets": [ "E3.0" ], "evidence": [ "The dry-storage electrical schedule lists equipment rows with QTY 1 and includes operator-furnished, vendor-furnished, optional, future, and NOT USED qualifications.", "Item 20 is optional, Item 25 is future, Item 31 is NOT USED, and several rows require vendor/owner verification.", "Convenience outlet rows 900 and 901 define mounting variants at +18 inches and +48 inches; the schedule rows do not substitute for plan occurrence counts." ], "conclusion": "The scheduled definitions are not safely additive to plan bubbles, and optional/future/vendor-furnished status must be resolved before procurement.", "requiredResolution": "Create a procurement responsibility matrix, confirm accepted alternates/options/future provisions, and count each accepted equipment/outlet occurrence once." }, { "id": "HOLD-10", "status": "HOLD", "topic": "Installed wiring and voltage-drop completeness", "sheets": [ "E3.0", "E3.1", "E3.2", "E3.3", "E3.4" ], "evidence": [ "The five sheets require a 3 percent feeder maximum and 5 percent combined feeder-plus-branch maximum for applicable long runs.", "Visible curves are diagrammatic plan connections and omit verticals, hidden routing, conductor allocation, conduit fill, slack, and field routing.", "E3.4 Detail 2 is N.T.S. and cannot support any length." ], "conclusion": "Visible drawn-path measurements may be audited as graphics, but installed route LF, conductor LF, conduit LF, and combined voltage-drop compliance are not certified.", "requiredResolution": "Establish field-installable routes and conductor assemblies, include vertical and hidden segments, and perform the required farthest-load combined voltage-drop calculations." }, { "id": "HOLD-11", "status": "HOLD", "topic": "Inherited 107-versus-85 room-count conflict", "sheets": [ "E3.0", "E3.1", "E3.2", "E3.3", "E3.4", "E1.0", "M2.0", "M2.1", "M2.2", "M2.3", "M2.4", "M6.0" ], "evidence": [ "The current power plans and prior electrical/mechanical evidence reconcile to 107 guestrooms.", "The prior E1.1 full audit records a conflicting earlier architectural count of 85." ], "conclusion": "This batch corroborates the 107-room engineering basis but cannot retire the architectural discrepancy.", "requiredResolution": "Issue a coordinated room matrix and identify the superseding architectural count before final guestroom procurement totals are released." } ], "referenceAndQuantityRules": [ { "source": "E1.1 legend and special outlet schedule", "rule": "Symbols and A-D outlet rows are definitions only; they contribute zero installed quantity without plan or mapped-detail occurrences." }, { "source": "E3.0 keyed notes and general notes", "rule": "A keyed-note bubble is a reference occurrence, not an installed device. Count the associated plotted device once where one exists." }, { "source": "E3.0 dry-storage schedule", "rule": "A QTY-1 equipment schedule row and its matching plan item bubble are two representations of the same equipment, not two units. Optional, future, vendor-furnished, and NOT USED rows require separate disposition." }, { "source": "E3.0 convenience outlet schedule", "rule": "Rows 900 and 901 define two mounting conditions; installed quantity comes from plan occurrences, not from the existence of two rows." }, { "source": "E3.1-E3.4 room labels", "rule": "Room labels establish room counts and types only. They do not create guestroom receptacle, PTAC outlet, data, TV, or control-device quantities." }, { "source": "E3.1-E3.4 FSD notes", "rule": "One note occurrence and one circuit reference do not equal one J-box. No FSD J-box quantity is accepted without mapped plan/device evidence." }, { "source": "M1.1/M1.2 schedules and M2.0-M2.4 plan tags", "rule": "Mechanical equipment and its electrical connection are coordinated representations of one physical unit. Do not add electrical connection symbols to mechanical equipment totals." }, { "source": "E3.4 Detail 2", "rule": "All LDU/JHS/JH1/TSU/EP/001 graphics are N.T.S. reference samples. They do not create additional installed quantities beyond governing plan and vendor schedules." }, { "source": "E3.4 Detail 2 fixture tag 001", "rule": "The two 001 samples corroborate the two E2.0 elevator-shaft fixtures already counted; additive quantity is zero." }, { "source": "Visible plan wiring curves", "rule": "A curve may support a drawn-path graphic trace only. It does not certify installed route, conductor, conduit, vertical, hidden, or slack quantities." } ], "releaseChecks": [ { "status": "PASS", "item": "E3.0-E3.4 page order, titles, and Detail-1 scales verified." }, { "status": "PASS", "item": "E3.4 elevator Detail 2 identified as N.T.S. and excluded from length takeoff." }, { "status": "PASS", "item": "Five-floor power-plan room count reconciles to the established 107-room electrical/mechanical chain." }, { "status": "PASS", "item": "Upper-floor local panel prefixes and actual circuit variations documented without a blind multiplier." }, { "status": "PASS", "item": "E1.1 special-outlet definitions and reference-only quantity treatment carried forward." }, { "status": "PASS", "item": "E3.4 Detail-2 001 samples prevented from duplicating the two established elevator-shaft fixture occurrences." }, { "status": "HOLD", "item": "Identify an explicit typical-guestroom power detail and room-type mapping for all 107 rooms." }, { "status": "HOLD", "item": "Provide power circuits for the six M2.2-M2.4 EUH-2 units not visibly served on E3.2-E3.4." }, { "status": "HOLD", "item": "Plot and map every FSD J-box to mechanical damper occurrences and local A-30 circuits; do not classify corridor duplex graphics as J-boxes." }, { "status": "HOLD", "item": "Define HP and C.P and resolve their equipment/circuit/accessory requirements." }, { "status": "HOLD", "item": "Verify every E3.1-E3.4 plan and note-only circuit against governing panel schedules." }, { "status": "HOLD", "item": "Correct E3.4 elevator JHL/JHS notation and obtain vendor-approved power/control requirements for both elevators." }, { "status": "HOLD", "item": "Resolve E3.0's missing fresh-air-fan schedule destination." }, { "status": "HOLD", "item": "Reconcile E3.0 sump, booster, fire-pump, pool, and motorized-damper electrical scope to governing discipline/vendor documents." }, { "status": "HOLD", "item": "Resolve optional/future/vendor-furnished kitchen equipment and count schedule/plan representations only once." }, { "status": "HOLD", "item": "Develop installed routing and combined voltage-drop calculations; visible plan curves are not installed LF." }, { "status": "HOLD", "item": "Retire the inherited 107-versus-85 architectural room-count conflict before final guestroom procurement release." } ] } }