C-7 - Erosion & Sediment Control Details 2 Civil PDF page 7; issued 02/23/2024; NTS Upright: minimum 2 x 2 lumber Horizontal: minimum 1 x 4 lumber Post: at least 4 FT long Post embedment: minimum 1 FT Post above grade: minimum 3 FT Barrier location: entire drip line TREE PROTECTION: Protect every designated tree at its drip line - Wood barricade and spiral-fence configurations are shown; storage, traffic and excavation are prohibited inside the barricade. MATERIAL: Minimum lumber sizes are printed - Uprights are not less than 2 x 2 lumber; horizontals are not less than 1 x 4 lumber. INSPECTION: Barricades require approval before construction begins - The City must inspect installed barricades before construction starts. CIV-ADDR: Project address requires reconciliation - The civil set identifies 308 8th Street West. The architectural/MEP takeoff set identifies 716 3rd Avenue Drive West. Confirm the governing parcel and address before bid documents and RFIs are issued. C7-02: Tree quantity is not plotted on C-7 - This NTS detail does not identify which trees remain or the number of barricades; reconcile with landscape/tree-removal plans. C7-03: Sheet-total conflict - The title block prints Sheet 7 of 21, while the cover index identifies a 20-sheet civil set. C7-04: Code reference needs edition confirmation - The barricade note cites code section 2.2.3.2.H; confirm current City requirements. C7-05: Alternative barrier acceptance is discretionary - Alternative barriers may be accepted at the sole discretion of the City; do not price an unapproved substitution as base scope.