  "schemaVersion": "1.0",
  "sheet": {
    "number": "C-6",
    "title": "Erosion & Sediment Control Details 1",
    "civilPdfPage": 6,
    "issueDate": "2024-02-23",
    "addressPrinted": "308 8th Street West, City of Bradenton, Florida",
    "scale": "NTS"
  },
  "coordinateSpace": {
    "width": 1920,
    "height": 1280
  },
  "groups": [
    {
      "id": "details",
      "label": "Major erosion-control details",
      "count": 4,
      "unit": "REF",
      "color": "#299bba",
      "basis": "SHOWN / SOURCE-LINKED",
      "status": "PLAN"
    },
    {
      "id": "inlet-types",
      "label": "Inlet-protection detail types",
      "count": 2,
      "unit": "REF",
      "color": "#d66a35",
      "basis": "SHOWN / SOURCE-LINKED",
      "status": "PLAN"
    }
  ],
  "measurements": [],
  "printedDimensions": [
    "Type III posts: 6 FT maximum spacing",
    "Type IV posts: 10 FT maximum spacing",
    "Tracking entrance: 50 FT standard length",
    "Tracking entrance: 15 FT minimum width",
    "Supported fence: 10 FT maximum post spacing",
    "Support-fence trench: 4 IN x 6 IN",
    "Wood post: 36 IN maximum height",
    "Inlet protection: 12 FT apron dimensions shown"
  ],
  "issues": [
    {
      "id": "CIV-ADDR",
      "title": "Project address requires reconciliation",
      "text": "The civil set identifies 308 8th Street West. The architectural/MEP takeoff set identifies 716 3rd Avenue Drive West. Confirm the governing parcel and address before bid documents and RFIs are issued."
    },
    {
      "id": "C6-02",
      "title": "Detail count is not installed quantity",
      "text": "C-6 is NTS. The four assemblies and subdetails define means and materials; their project LF/EA must come from the erosion-control plan or field sequencing."
    },
    {
      "id": "C6-03",
      "title": "Sheet-total conflict",
      "text": "The title block prints Sheet 6 of 21, while the cover index identifies a 20-sheet civil set."
    },
    {
      "id": "C6-04",
      "title": "Source standards require current-edition confirmation",
      "text": "Details cite FDOT indexes and City of Bradenton standards dated 2010, 2013 and 2016. Confirm the adopted editions."
    },
    {
      "id": "C6-05",
      "title": "Temporary-control duration is open",
      "text": "Maintenance duration, relocations and replacement cycles are not quantified on this detail sheet."
    }
  ]
}