C-16 - Site Details 2 Civil PDF page 15; issued 02/23/2024; NTS Concrete walk: 4 IN typical; 6 IN where subject to vehicular traffic Crushed-concrete base: minimum 8 IN, LBR-100, 98% AASHTO T-180 Compacted subgrade: minimum 12 IN, LBR-40, 98% AASHTO T-180 Base under curb: minimum 6 IN and 12 IN beyond back of curb STOP sign: 30 IN x 30 IN, R1-1 Dumpster pad: minimum 10 FT x 10 FT x 6 IN Dumpster fence: 6 FT opaque Dumpster setback: 10 FT minimum unless approved sprinkler protection is provided CURB / PAVING: Type D curb section defines the pavement build-up - The section includes concrete walk, curb and gutter, asphalt surface, tack/prime coat, 8-inch crushed-concrete base and 12-inch compacted subgrade. DUMPSTER PAD: Food-service pad requires drainage and grease control - The minimum 10-by-10-foot pad is 6 inches thick, 3,000 PSI concrete with reinforcement, a sump drain and grease trap, plus an opaque 6-foot fence. FIRE SEPARATION: Dumpster proximity can trigger sprinkler scope - Keep the dumpster at least 10 feet from a building. If closer, a fire-sprinkler suppression system requires Fire Marshal approval. SIGN: STOP sign geometry is printed - The NTS site-sign detail shows one 30-by-30-inch R1-1 sign definition; installed count comes from C-13. CIV-ADDR: Project address requires reconciliation - The civil set identifies 308 8th Street West. The architectural/MEP takeoff set identifies 716 3rd Avenue Drive West. Confirm the governing parcel and address before bid documents and RFIs are issued. CIV-NUMBERING: C-14 is missing from the issued PDF - The source PDF proceeds from C-13 directly to C-15. The cover index and title-block totals are inconsistent; obtain the missing C-14 sheet or written confirmation that it was intentionally omitted. C16-03: Dumpster pad location is not identified on this detail - C-16 defines the assembly but does not establish whether the hotel or future restaurant carries the pad, drain, grease trap and enclosure. C16-04: Drain and grease-trap connection is unresolved - The detail requires a sump drain and grease trap for food and beverage service but provides no pipe size, route, invert or receiving system. C16-05: Detail count is not installed quantity - The three NTS details are definitions. Curb LF, sign EA and dumpster-pad EA must be reconciled to the plan and project scope.