  "schemaVersion": "1.0",
  "sheet": {
    "number": "C-13",
    "title": "Signage and Marking Plan",
    "civilPdfPage": 13,
    "issueDate": "2024-02-23",
    "addressPrinted": "308 8th Street West, City of Bradenton, Florida",
    "scale": "1\" = 20 FT · PRINTED SCALE"
  },
  "coordinateSpace": {
    "width": 1920,
    "height": 1280
  },
  "groups": [
    {
      "id": "stop",
      "label": "STOP signs",
      "count": 4,
      "unit": "EA",
      "color": "#299bba",
      "basis": "SHOWN / SOURCE-LINKED",
      "status": "PLAN"
    },
    {
      "id": "warning",
      "label": "Detectable warning surfaces",
      "count": 6,
      "unit": "EA",
      "color": "#d66a35",
      "basis": "SHOWN / SOURCE-LINKED",
      "status": "PLAN"
    },
    {
      "id": "do-not-enter",
      "label": "DO NOT ENTER signs",
      "count": 1,
      "unit": "EA",
      "color": "#876bd5",
      "basis": "SHOWN / SOURCE-LINKED",
      "status": "PLAN"
    },
    {
      "id": "one-way",
      "label": "ONE WAY signs",
      "count": 1,
      "unit": "EA",
      "color": "#398d79",
      "basis": "SHOWN / SOURCE-LINKED",
      "status": "PLAN"
    },
    {
      "id": "arrows",
      "label": "White directional arrows",
      "count": 12,
      "unit": "EA",
      "color": "#ba9138",
      "basis": "SHOWN / SOURCE-LINKED",
      "status": "PLAN"
    },
    {
      "id": "crosswalk",
      "label": "12 IN white crosswalk groups",
      "count": 3,
      "unit": "REF",
      "color": "#b06bad",
      "basis": "SHOWN / SOURCE-LINKED",
      "status": "PLAN"
    },
    {
      "id": "stop-bar",
      "label": "18 IN white stop bars shown",
      "count": 4,
      "unit": "EA",
      "color": "#d9534f",
      "basis": "SHOWN / SOURCE-LINKED",
      "status": "PLAN"
    },
    {
      "id": "accessible-sign",
      "label": "Accessible parking signs",
      "count": 2,
      "unit": "EA",
      "color": "#5f86c9",
      "basis": "SHOWN / SOURCE-LINKED",
      "status": "PLAN"
    },
    {
      "id": "fine-sign",
      "label": "$250 fine signs",
      "count": 2,
      "unit": "EA",
      "color": "#8c6b43",
      "basis": "SHOWN / SOURCE-LINKED",
      "status": "PLAN"
    },
    {
      "id": "bike-rack",
      "label": "Bike rack",
      "count": 1,
      "unit": "EA",
      "color": "#637a35",
      "basis": "SHOWN / SOURCE-LINKED",
      "status": "PLAN"
    },
    {
      "id": "ev",
      "label": "Double EV charging points",
      "count": 2,
      "unit": "EA",
      "color": "#b45f8f",
      "basis": "SHOWN / SOURCE-LINKED",
      "status": "PLAN"
    }
  ],
  "sourceMarkers": [
    {
      "id": "stop-01",
      "type": "stop",
      "x": 946,
      "y": 364,
      "labelX": 954,
      "labelY": 357,
      "sourceNote": "STOP signs 1",
      "scopeKey": "C-13/stop/1",
      "reconciliation": "SHOWN"
    },
    {
      "id": "stop-02",
      "type": "stop",
      "x": 490,
      "y": 585,
      "labelX": 498,
      "labelY": 578,
      "sourceNote": "STOP signs 2",
      "scopeKey": "C-13/stop/2",
      "reconciliation": "SHOWN"
    },
    {
      "id": "stop-03",
      "type": "stop",
      "x": 641,
      "y": 906,
      "labelX": 649,
      "labelY": 899,
      "sourceNote": "STOP signs 3",
      "scopeKey": "C-13/stop/3",
      "reconciliation": "SHOWN"
    },
    {
      "id": "stop-04",
      "type": "stop",
      "x": 1158,
      "y": 697,
      "labelX": 1166,
      "labelY": 690,
      "sourceNote": "STOP signs 4",
      "scopeKey": "C-13/stop/4",
      "reconciliation": "SHOWN"
    },
    {
      "id": "warning-01",
      "type": "warning",
      "x": 826,
      "y": 333,
      "labelX": 834,
      "labelY": 326,
      "sourceNote": "Detectable warning surfaces 1",
      "scopeKey": "C-13/warning/1",
      "reconciliation": "SHOWN"
    },
    {
      "id": "warning-02",
      "type": "warning",
      "x": 929,
      "y": 345,
      "labelX": 937,
      "labelY": 338,
      "sourceNote": "Detectable warning surfaces 2",
      "scopeKey": "C-13/warning/2",
      "reconciliation": "SHOWN"
    },
    {
      "id": "warning-03",
      "type": "warning",
      "x": 916,
      "y": 585,
      "labelX": 924,
      "labelY": 578,
      "sourceNote": "Detectable warning surfaces 3",
      "scopeKey": "C-13/warning/3",
      "reconciliation": "SHOWN"
    },
    {
      "id": "warning-04",
      "type": "warning",
      "x": 809,
      "y": 626,
      "labelX": 817,
      "labelY": 619,
      "sourceNote": "Detectable warning surfaces 4",
      "scopeKey": "C-13/warning/4",
      "reconciliation": "SHOWN"
    },
    {
      "id": "warning-05",
      "type": "warning",
      "x": 984,
      "y": 486,
      "labelX": 992,
      "labelY": 479,
      "sourceNote": "Detectable warning surfaces 5",
      "scopeKey": "C-13/warning/5",
      "reconciliation": "SHOWN"
    },
    {
      "id": "warning-06",
      "type": "warning",
      "x": 984,
      "y": 522,
      "labelX": 992,
      "labelY": 515,
      "sourceNote": "Detectable warning surfaces 6",
      "scopeKey": "C-13/warning/6",
      "reconciliation": "SHOWN"
    },
    {
      "id": "do-not-enter-01",
      "type": "do-not-enter",
      "x": 487,
      "y": 632,
      "labelX": 495,
      "labelY": 625,
      "sourceNote": "DO NOT ENTER signs 1",
      "scopeKey": "C-13/do-not-enter/1",
      "reconciliation": "SHOWN"
    },
    {
      "id": "one-way-01",
      "type": "one-way",
      "x": 750,
      "y": 545,
      "labelX": 758,
      "labelY": 538,
      "sourceNote": "ONE WAY signs 1",
      "scopeKey": "C-13/one-way/1",
      "reconciliation": "SHOWN"
    },
    {
      "id": "arrows-01",
      "type": "arrows",
      "x": 865,
      "y": 374,
      "labelX": 873,
      "labelY": 367,
      "sourceNote": "White directional arrows 1",
      "scopeKey": "C-13/arrows/1",
      "reconciliation": "SHOWN"
    },
    {
      "id": "arrows-02",
      "type": "arrows",
      "x": 548,
      "y": 615,
      "labelX": 556,
      "labelY": 608,
      "sourceNote": "White directional arrows 2",
      "scopeKey": "C-13/arrows/2",
      "reconciliation": "SHOWN"
    },
    {
      "id": "arrows-03",
      "type": "arrows",
      "x": 782,
      "y": 598,
      "labelX": 790,
      "labelY": 591,
      "sourceNote": "White directional arrows 3",
      "scopeKey": "C-13/arrows/3",
      "reconciliation": "SHOWN"
    },
    {
      "id": "arrows-04",
      "type": "arrows",
      "x": 401,
      "y": 736,
      "labelX": 409,
      "labelY": 729,
      "sourceNote": "White directional arrows 4",
      "scopeKey": "C-13/arrows/4",
      "reconciliation": "SHOWN"
    },
    {
      "id": "arrows-05",
      "type": "arrows",
      "x": 751,
      "y": 825,
      "labelX": 759,
      "labelY": 818,
      "sourceNote": "White directional arrows 5",
      "scopeKey": "C-13/arrows/5",
      "reconciliation": "SHOWN"
    },
    {
      "id": "arrows-06",
      "type": "arrows",
      "x": 1005,
      "y": 576,
      "labelX": 1013,
      "labelY": 569,
      "sourceNote": "White directional arrows 6",
      "scopeKey": "C-13/arrows/6",
      "reconciliation": "SHOWN"
    },
    {
      "id": "arrows-07",
      "type": "arrows",
      "x": 1038,
      "y": 610,
      "labelX": 1046,
      "labelY": 603,
      "sourceNote": "White directional arrows 7",
      "scopeKey": "C-13/arrows/7",
      "reconciliation": "SHOWN"
    },
    {
      "id": "arrows-08",
      "type": "arrows",
      "x": 1106,
      "y": 758,
      "labelX": 1114,
      "labelY": 751,
      "sourceNote": "White directional arrows 8",
      "scopeKey": "C-13/arrows/8",
      "reconciliation": "SHOWN"
    },
    {
      "id": "arrows-09",
      "type": "arrows",
      "x": 1234,
      "y": 850,
      "labelX": 1242,
      "labelY": 843,
      "sourceNote": "White directional arrows 9",
      "scopeKey": "C-13/arrows/9",
      "reconciliation": "SHOWN"
    },
    {
      "id": "arrows-10",
      "type": "arrows",
      "x": 1249,
      "y": 894,
      "labelX": 1257,
      "labelY": 887,
      "sourceNote": "White directional arrows 10",
      "scopeKey": "C-13/arrows/10",
      "reconciliation": "SHOWN"
    },
    {
      "id": "arrows-11",
      "type": "arrows",
      "x": 1390,
      "y": 756,
      "labelX": 1398,
      "labelY": 749,
      "sourceNote": "White directional arrows 11",
      "scopeKey": "C-13/arrows/11",
      "reconciliation": "SHOWN"
    },
    {
      "id": "arrows-12",
      "type": "arrows",
      "x": 1394,
      "y": 817,
      "labelX": 1402,
      "labelY": 810,
      "sourceNote": "White directional arrows 12",
      "scopeKey": "C-13/arrows/12",
      "reconciliation": "SHOWN"
    },
    {
      "id": "crosswalk-01",
      "type": "crosswalk",
      "x": 866,
      "y": 341,
      "labelX": 874,
      "labelY": 334,
      "sourceNote": "12 IN white crosswalk groups 1",
      "scopeKey": "C-13/crosswalk/1",
      "reconciliation": "SHOWN"
    },
    {
      "id": "crosswalk-02",
      "type": "crosswalk",
      "x": 810,
      "y": 577,
      "labelX": 818,
      "labelY": 570,
      "sourceNote": "12 IN white crosswalk groups 2",
      "scopeKey": "C-13/crosswalk/2",
      "reconciliation": "SHOWN"
    },
    {
      "id": "crosswalk-03",
      "type": "crosswalk",
      "x": 746,
      "y": 548,
      "labelX": 754,
      "labelY": 541,
      "sourceNote": "12 IN white crosswalk groups 3",
      "scopeKey": "C-13/crosswalk/3",
      "reconciliation": "SHOWN"
    },
    {
      "id": "stop-bar-01",
      "type": "stop-bar",
      "x": 874,
      "y": 315,
      "labelX": 882,
      "labelY": 308,
      "sourceNote": "18 IN white stop bars shown 1",
      "scopeKey": "C-13/stop-bar/1",
      "reconciliation": "SHOWN"
    },
    {
      "id": "stop-bar-02",
      "type": "stop-bar",
      "x": 438,
      "y": 574,
      "labelX": 446,
      "labelY": 567,
      "sourceNote": "18 IN white stop bars shown 2",
      "scopeKey": "C-13/stop-bar/2",
      "reconciliation": "SHOWN"
    },
    {
      "id": "stop-bar-03",
      "type": "stop-bar",
      "x": 788,
      "y": 633,
      "labelX": 796,
      "labelY": 626,
      "sourceNote": "18 IN white stop bars shown 3",
      "scopeKey": "C-13/stop-bar/3",
      "reconciliation": "SHOWN"
    },
    {
      "id": "stop-bar-04",
      "type": "stop-bar",
      "x": 649,
      "y": 854,
      "labelX": 657,
      "labelY": 847,
      "sourceNote": "18 IN white stop bars shown 4",
      "scopeKey": "C-13/stop-bar/4",
      "reconciliation": "SHOWN"
    },
    {
      "id": "accessible-sign-01",
      "type": "accessible-sign",
      "x": 1136,
      "y": 486,
      "labelX": 1144,
      "labelY": 479,
      "sourceNote": "Accessible parking signs 1",
      "scopeKey": "C-13/accessible-sign/1",
      "reconciliation": "SHOWN"
    },
    {
      "id": "accessible-sign-02",
      "type": "accessible-sign",
      "x": 1136,
      "y": 522,
      "labelX": 1144,
      "labelY": 515,
      "sourceNote": "Accessible parking signs 2",
      "scopeKey": "C-13/accessible-sign/2",
      "reconciliation": "SHOWN"
    },
    {
      "id": "fine-sign-01",
      "type": "fine-sign",
      "x": 1195,
      "y": 486,
      "labelX": 1203,
      "labelY": 479,
      "sourceNote": "$250 fine signs 1",
      "scopeKey": "C-13/fine-sign/1",
      "reconciliation": "SHOWN"
    },
    {
      "id": "fine-sign-02",
      "type": "fine-sign",
      "x": 1195,
      "y": 522,
      "labelX": 1203,
      "labelY": 515,
      "sourceNote": "$250 fine signs 2",
      "scopeKey": "C-13/fine-sign/2",
      "reconciliation": "SHOWN"
    },
    {
      "id": "bike-rack-01",
      "type": "bike-rack",
      "x": 1021,
      "y": 553,
      "labelX": 1029,
      "labelY": 546,
      "sourceNote": "Bike rack 1",
      "scopeKey": "C-13/bike-rack/1",
      "reconciliation": "SHOWN"
    },
    {
      "id": "ev-01",
      "type": "ev",
      "x": 559,
      "y": 735,
      "labelX": 567,
      "labelY": 728,
      "sourceNote": "Double EV charging points 1",
      "scopeKey": "C-13/ev/1",
      "reconciliation": "SHOWN"
    },
    {
      "id": "ev-02",
      "type": "ev",
      "x": 1006,
      "y": 760,
      "labelX": 1014,
      "labelY": 753,
      "sourceNote": "Double EV charging points 2",
      "scopeKey": "C-13/ev/2",
      "reconciliation": "SHOWN"
    }
  ],
  "measurements": [
    {
      "id": "c13-stop-bars",
      "label": "18 IN stop bars - four visible centerlines",
      "unit": "LF",
      "lines": [
        [
          [
            812,
            317
          ],
          [
            930,
            335
          ]
        ],
        [
          [
            405,
            575
          ],
          [
            472,
            575
          ]
        ],
        [
          [
            786,
            577
          ],
          [
            786,
            646
          ]
        ],
        [
          [
            651,
            823
          ],
          [
            651,
            879
          ]
        ]
      ],
      "color": "#d9534f",
      "quantity": 116.8,
      "status": "MEASURED PATH - PRINTED SCALE",
      "basis": "Exact saved source polyline at the printed scale; only visible plan geometry is included."
    },
    {
      "id": "c13-crosswalks",
      "label": "White crosswalk lines - visible centerlines",
      "unit": "LF",
      "lines": [
        [
          [
            815,
            350
          ],
          [
            918,
            365
          ]
        ],
        [
          [
            813,
            373
          ],
          [
            900,
            385
          ]
        ],
        [
          [
            773,
            558
          ],
          [
            824,
            558
          ]
        ],
        [
          [
            773,
            575
          ],
          [
            824,
            575
          ]
        ],
        [
          [
            724,
            540
          ],
          [
            770,
            540
          ]
        ],
        [
          [
            724,
            553
          ],
          [
            770,
            553
          ]
        ]
      ],
      "color": "#299bba",
      "quantity": 144.7,
      "status": "MEASURED PATH - PRINTED SCALE",
      "basis": "Exact saved source polyline at the printed scale; only visible plan geometry is included."
    }
  ],
  "printedDimensions": [
    "STOP sign: R1-1, 30 IN x 30 IN",
    "Accessible parking sign: 18 IN x 12 IN",
    "Fine sign: 6 IN x 12 IN",
    "Plan callouts: 18 IN white stop bars",
    "Plan callouts: 4 IN and 12 IN white crosswalk",
    "All pavement markings: thermoplastic per C-15 detail note"
  ],
  "requirements": [
    [
      "critical",
      "PLAN COUNT",
      "All 38 numbered plan occurrences remain separate",
      "Legend definitions are not treated as installed quantity. Counts come from the numbered symbols placed on the plan.",
      "plan"
    ],
    [
      "cost",
      "THERMOPLASTIC",
      "Carry directional arrows, crosswalks and stop bars",
      "The plan shows 12 directional arrows, three crosswalk groups and four 18-inch stop bars; visible striping centerlines are traced separately.",
      "marking"
    ],
    [
      "critical",
      "ACCESSIBLE PARKING",
      "Two accessible stalls have paired signs",
      "Each accessible stall shows a disabled-parking sign and separate $250-fine sign, with detectable warnings at the adjacent route.",
      "accessible"
    ],
    [
      "cost",
      "EV / BIKE",
      "Charging and bicycle facilities are explicit",
      "The plan shows two double electrical-vehicle charging points and one bike rack.",
      "plan"
    ]
  ],
  "issues": [
    {
      "id": "CIV-ADDR",
      "title": "Project address requires reconciliation",
      "text": "The civil set identifies 308 8th Street West. The architectural/MEP takeoff set identifies 716 3rd Avenue Drive West. Confirm the governing parcel and address before bid documents and RFIs are issued."
    },
    {
      "id": "CIV-NUMBERING",
      "title": "C-14 is missing from the issued PDF",
      "text": "The source PDF proceeds from C-13 directly to C-15. The cover index and title-block totals are inconsistent; obtain the missing C-14 sheet or written confirmation that it was intentionally omitted."
    },
    {
      "id": "C13-03",
      "title": "Stop-bar width conflicts with legend",
      "text": "Plan callouts identify 18-inch white stop bars, while the legend defines symbol 7 as 24-inch white thermoplastic striping. Confirm the governing width."
    },
    {
      "id": "C13-04",
      "title": "Crosswalk callouts conflict with legend",
      "text": "Plan callouts show both 4-inch and 12-inch white crosswalk markings, while the legend defines symbol 6 as 12-inch white thermoplastic striping. Confirm line pattern and pay width."
    },
    {
      "id": "C13-05",
      "title": "EV charging equipment scope is not defined here",
      "text": "Two double charging-point symbols are plotted, but charger equipment, bollards, electrical feeders, network service and mounting details are not specified on C-13."
    }
  ]
}