  "schemaVersion": "1.0",
  "sheet": {
    "number": "C-10",
    "title": "Utility Plan",
    "civilPdfPage": 10,
    "issueDate": "2024-02-23",
    "addressPrinted": "308 8th Street West, City of Bradenton, Florida",
    "scale": "1\" = 20 FT · PRINTED SCALE"
  },
  "coordinateSpace": {
    "width": 1920,
    "height": 1280
  },
  "groups": [
    {
      "id": "water-accessories",
      "label": "Water/fire accessories",
      "count": 5,
      "unit": "EA",
      "color": "#299bba",
      "basis": "SHOWN / SOURCE-LINKED",
      "status": "PLAN"
    },
    {
      "id": "sewer",
      "label": "Force-main structures",
      "count": 2,
      "unit": "EA",
      "color": "#d66a35",
      "basis": "SHOWN / SOURCE-LINKED",
      "status": "PLAN"
    },
    {
      "id": "bends",
      "label": "Printed bend callout groups",
      "count": 5,
      "unit": "REF",
      "color": "#876bd5",
      "basis": "SHOWN / SOURCE-LINKED",
      "status": "PLAN"
    }
  ],
  "measurements": [
    {
      "id": "c10-fire",
      "label": "6 IN DR14 fire line - visible centerline",
      "unit": "LF",
      "line": [
        [
          900,
          300
        ],
        [
          900,
          370
        ],
        [
          920,
          430
        ],
        [
          920,
          520
        ],
        [
          875,
          565
        ]
      ],
      "color": "#d9534f",
      "quantity": 107.6,
      "status": "MEASURED PATH - PRINTED SCALE",
      "basis": "Exact saved source polyline at 1 inch = 20 feet; curve endpoints are traced at visible centerline. Hidden depth, vertical, fittings and unshown continuation are excluded."
    },
    {
      "id": "c10-water6",
      "label": "6 IN DR18 water main - visible centerline",
      "unit": "LF",
      "line": [
        [
          865,
          300
        ],
        [
          865,
          410
        ],
        [
          860,
          520
        ],
        [
          830,
          610
        ]
      ],
      "color": "#299bba",
      "quantity": 118.1,
      "status": "MEASURED PATH - PRINTED SCALE",
      "basis": "Exact saved source polyline at 1 inch = 20 feet; curve endpoints are traced at visible centerline. Hidden depth, vertical, fittings and unshown continuation are excluded."
    },
    {
      "id": "c10-water4",
      "label": "4 IN DR18 water main - visible centerline",
      "unit": "LF",
      "line": [
        [
          925,
          390
        ],
        [
          925,
          500
        ],
        [
          925,
          580
        ],
        [
          875,
          620
        ]
      ],
      "color": "#876bd5",
      "quantity": 95.3,
      "status": "MEASURED PATH - PRINTED SCALE",
      "basis": "Exact saved source polyline at 1 inch = 20 feet; curve endpoints are traced at visible centerline. Hidden depth, vertical, fittings and unshown continuation are excluded."
    },
    {
      "id": "c10-force",
      "label": "2 IN force main - visible centerline",
      "unit": "LF",
      "line": [
        [
          705,
          760
        ],
        [
          725,
          690
        ],
        [
          940,
          690
        ],
        [
          1057,
          712
        ]
      ],
      "color": "#398d79",
      "quantity": 152.6,
      "status": "MEASURED PATH - PRINTED SCALE",
      "basis": "Exact saved source polyline at 1 inch = 20 feet; curve endpoints are traced at visible centerline. Hidden depth, vertical, fittings and unshown continuation are excluded."
    }
  ],
  "printedDimensions": [
    "Fire line: 6 IN DR14",
    "Domestic water: 6 IN DR18",
    "Domestic water branch: 4 IN DR18",
    "Force main: 2 IN",
    "Existing sanitary manhole rim: 13.16",
    "Existing sanitary manhole NW invert: 10.87",
    "Existing sanitary manhole S invert: 10.75",
    "Grinder pump rim: 12.50",
    "Grinder pump invert: 7.60"
  ],
  "issues": [
    {
      "id": "CIV-ADDR",
      "title": "Project address requires reconciliation",
      "text": "The civil set identifies 308 8th Street West. The architectural/MEP takeoff set identifies 716 3rd Avenue Drive West. Confirm the governing parcel and address before bid documents and RFIs are issued."
    },
    {
      "id": "CIV-ROOMS",
      "title": "Civil hotel program conflicts with architectural takeoff",
      "text": "C-8 through C-10 label a 131-room hotel. The architectural takeoff verifies 85 guestrooms, while the mechanical schedules reference 107. Preserve all three values until the design team identifies the governing program."
    },
    {
      "id": "C10-03",
      "title": "Building utility handoff is open",
      "text": "“Utility connections to building by others” does not identify the trade, exact termination, penetration, valve or responsibility limit."
    },
    {
      "id": "C10-04",
      "title": "Existing-main connection requires field verification",
      "text": "Contractor must connect to the existing 6-inch water main. Confirm location, elevation, shutdown, tapping method and City requirements."
    },
    {
      "id": "C10-05",
      "title": "Title-block sequence is offset",
      "text": "C-10 prints 11 of 20 in its title block although the cover index identifies it as C-10."
    },
    {
      "id": "C10-06",
      "title": "Future restaurant scope is unresolved",
      "text": "The restaurant is shown with utility support but no clear base/future/alternate construction boundary."
    }
  ]
}